Auto Water Refill — PLC Control Template

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 96 views

# Auto Water Refill — Usage Guide ## Overview Simple on/off solenoid valve refill control. Starts filling when level drops to `SP_START`, stops when it reaches `SP_STOP`. Includes timeout guard, supply fault detection, and HH safety override. Suitable for: cooling towers, buffer tanks, plating baths, wash water tanks, irrigation reservoirs. ## Setpoint Hierarchy ``` SP_HH ─────────────────────────────────── 95% (Critical — fill forced off) SP_H ────────────────────────────────── 85% (High alarm) SP_STOP ───────────────────────────────── 75% (Auto refill stops here) ↑ Hysteresis band SP_START ──────────────────────────────── 25% (Auto refill starts here) SP_L ────────────────────────────────── 15% (Low alarm) SP_LL ─────────────────────────────────── 5% (Critical) ``` The hysteresis band (`SP_STOP` − `SP_START`) prevents rapid cycling. Minimum recommended band: 10%. ## Timeout Sizing `FILL_TIMEOUT_TICKS = TANK_VOLUME_L / FILL_RATE_LPM × 60 × 10 × 1.5` Example: 1000 L tank, 10 L/min fill rate → 1000/10 × 600 × 1.5 = 90,000 ticks (150 min safety margin). ## Commissioning 1. Verify level transmitter: check 4mA = empty, 20mA = full 2. In MANUAL mode: open fill solenoid, confirm level rises 3. Test SP_HH override: force level to 95% — confirm solenoid closes 4. In AUTO mode: let level drop to SP_START, confirm auto-refill starts and stops at SP_STOP 5. Test timeout: set `FILL_TIMEOUT_TICKS` low, run fill, confirm fault and alarm --- ## Control Logic — Vendor-Agnostic Pseudocode # Auto Water Refill — Logic ## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2 ## Scan Rate: 100ms | Pattern: Simple reservoir low-level auto-refill with high cutoff ``` ROUTINE: AutoWaterRefill SCAN_RATE: 100ms // ═══════════════════════════════════════════════════════════════ // SECTION 1 — LEVEL MEASUREMENT & VALIDATION // ═══════════════════════════════════════════════════════════════ LT001_MA := SCALE(LT001_RAW, 0, 27648, 4.0, 20.0) LT001_VALID := (LT001_MA >= 3.8) AND (LT001_MA <= 20.5) IF LT001_VALID THEN LT001_PV := SCALE(LT001_MA, 4.0, 20.0, 0.0, 100.0) LT001_LAST_GOOD := LT001_PV ELSE LT001_PV := LT001_LAST_GOOD SET_ALARM(ALM_XMTR_FAIL, HIGH) // Fail safe: close fill solenoid on xmtr failure FILL_SOL_CMD := FALSE END_IF // ═══════════════════════════════════════════════════════════════ // SECTION 2 — REFILL CONTROL LOGIC // Hysteresis: start at SP_START, stop at SP_STOP. // Manual override: operator can force fill on/off. // Permissive: supply pressure OK and no fault. // ═══════════════════════════════════════════════════════════════ SUPPLY_OK := SUPPLY_PRESS_OK AND NOT SUPPLY_FAULT FILL_ALLOWED := LT001_VALID AND SUPPLY_OK AND NOT REFILL_FAULT CASE MODE_SELECTOR OF 0: // OFF FILL_SOL_CMD := FALSE 1: // MANUAL FILL_SOL_CMD := MAN_FILL_CMD AND FILL_ALLOWED 2: // AUTO IF LT001_PV <= SP_START AND NOT FILL_ACTIVE AND FILL_ALLOWED THEN FILL_ACTIVE := TRUE FILL_START_TIME := SYS_TICK AUDIT_LOG(EVENT="REFILL_STARTED", LEVEL=LT001_PV) END_IF IF LT001_PV >= SP_STOP THEN FILL_ACTIVE := FALSE AUDIT_LOG(EVENT="REFILL_COMPLETE", LEVEL=LT001_PV) END_IF FILL_SOL_CMD := FILL_ACTIVE AND FILL_ALLOWED END_CASE // ═══════════════════════════════════════════════════════════════ // SECTION 3 — REFILL TIMEOUT // Prevents solenoid staying open if tank never fills. // ═══════════════════════════════════════════════════════════════ IF FILL_ACTIVE THEN FILL_TMR := FILL_TMR + 1 IF FILL_TMR >= FILL_TIMEOUT_TICKS THEN FILL_ACTIVE := FALSE FILL_SOL_CMD := FALSE REFILL_FAULT := TRUE SET_ALARM(ALM_FILL_TIMEOUT, HIGH) AUDIT_LOG(EVENT="REFILL_TIMEOUT_FAULT") END_IF ELSE FILL_TMR := 0 END_IF // Reset fault IF RESET_CMD AND NOT FILL_ACTIVE THEN REFILL_FAULT := FALSE RESET_CMD := FALSE END_IF // ═══════════════════════════════════════════════════════════════ // SECTION 4 — ALARMS (ISA-18.2) // ═══════════════════════════════════════════════════════════════ IF LT001_PV >= SP_HH THEN SET_ALARM(ALM_LEVEL_HH, CRITICAL) FILL_SOL_CMD := FALSE END_IF IF LT001_PV >= SP_H THEN SET_ALARM(ALM_LEVEL_H, HIGH) END_IF IF LT001_PV <= SP_L THEN SET_ALARM(ALM_LEVEL_L, HIGH) END_IF IF LT001_PV <= SP_LL THEN SET_ALARM(ALM_LEVEL_LL, CRITICAL) END_IF // ═══════════════════════════════════════════════════════════════ // SECTION 5 — HMI OUTPUTS // ═══════════════════════════════════════════════════════════════ HMI_LEVEL := LT001_PV HMI_FILL := FILL_SOL_CMD HMI_MODE := MODE_SELECTOR HMI_FILL_ACTIVE := FILL_ACTIVE HMI_FAULT := REFILL_FAULT HMI_XMTR_FAIL := NOT LT001_VALID END_ROUTINE ``` --- ## Tag List ```csv Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address LT001_RAW,Level Transmitter Raw ADC,INT,input,,0,27648,,AI:0:0.0 LT001_MA,Level mA,REAL,calculated,mA,3.8,20.5,, LT001_PV,Level Process Value,REAL,calculated,%,0,100,, LT001_VALID,Transmitter Healthy,BOOL,calculated,,,,TRUE, LT001_LAST_GOOD,Last Good Level,REAL,internal,%,0,100,50, FILL_SOL_CMD,Fill Solenoid Valve Command,BOOL,output,,,,FALSE,DO:1:0.0 SUPPLY_PRESS_OK,Water Supply Pressure OK,BOOL,input,,,,TRUE,DI:0:0.0 SUPPLY_FAULT,Water Supply Fault,BOOL,input,,,,FALSE,DI:0:0.1 MODE_SELECTOR,Operating Mode (0=OFF 1=MAN 2=AUTO),INT,input,,0,2,2, MAN_FILL_CMD,Manual Fill Command,BOOL,input,,,,FALSE, RESET_CMD,Fault Reset Command,BOOL,input,,,,FALSE, FILL_ACTIVE,Refill Cycle Active,BOOL,internal,,,,FALSE, FILL_ALLOWED,Refill Conditions Met,BOOL,calculated,,,,FALSE, SUPPLY_OK,Supply Healthy and Available,BOOL,calculated,,,,FALSE, REFILL_FAULT,Refill Fault — Reset Required,BOOL,internal,,,,FALSE, SP_START,Refill Start Setpoint (low level trigger),REAL,internal,%,0,100,25, SP_STOP,Refill Stop Setpoint (high cutoff),REAL,internal,%,0,100,75, SP_LL,Level Low-Low Critical Setpoint,REAL,internal,%,0,100,5, SP_L,Level Low Alarm Setpoint,REAL,internal,%,0,100,15, SP_H,Level High Alarm Setpoint,REAL,internal,%,0,100,85, SP_HH,Level High-High Critical Setpoint,REAL,internal,%,0,100,95, FILL_TMR,Fill Timeout Timer (100ms ticks),INT,internal,,0,999999,0, FILL_TIMEOUT_TICKS,Maximum Fill Duration (100ms ticks),INT,internal,,100,999999,18000, FILL_START_TIME,Refill Start Timestamp,DINT,internal,,0,999999,, SYS_TICK,System Tick Counter,DINT,input,,0,999999,, ALM_XMTR_FAIL,Level Transmitter Failure,BOOL,calculated,,,,FALSE, ALM_LEVEL_HH,Level High-High,BOOL,calculated,,,,FALSE, ALM_LEVEL_H,Level High,BOOL,calculated,,,,FALSE, ALM_LEVEL_L,Level Low,BOOL,calculated,,,,FALSE, ALM_LEVEL_LL,Level Low-Low,BOOL,calculated,,,,FALSE, ALM_FILL_TIMEOUT,Refill Timeout — Tank Not Filling,BOOL,calculated,,,,FALSE, HMI_LEVEL,HMI: Level,REAL,output,%,0,100,, HMI_FILL,HMI: Fill Solenoid,BOOL,output,,,,FALSE, HMI_MODE,HMI: Mode,INT,output,,0,2,2, HMI_FILL_ACTIVE,HMI: Refill Active,BOOL,output,,,,FALSE, HMI_FAULT,HMI: Fault Active,BOOL,output,,,,FALSE, HMI_XMTR_FAIL,HMI: Transmitter Fault,BOOL,output,,,,FALSE, ``` --- ## Alarm Matrix ```csv Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge ALM_LEVEL_HH,LT001_PV >= SP_HH,95%,critical,safety,Fill solenoid forced closed. Overflow risk. Check demand side for blockage or valve stuck open.,0s,No ALM_LEVEL_LL,LT001_PV <= SP_LL,5%,critical,process,Critically low level. Check water supply pressure and solenoid operation.,0s,No ALM_XMTR_FAIL,LT001_VALID = FALSE,wire-break,high,equipment,Level transmitter failed. Fill solenoid closed for safety. Check wiring and loop power.,5s,No ALM_FILL_TIMEOUT,Refill active for longer than FILL_TIMEOUT_TICKS,30 min,high,process,Tank not filling. Check water supply pressure and solenoid valve. Sequence faulted — manual reset required.,0s,No ALM_LEVEL_H,LT001_PV >= SP_H,85%,high,process,Level above normal high. Verify refill solenoid closed. Check for inadvertent supply.,10s,No ALM_LEVEL_L,LT001_PV <= SP_L,15%,high,process,Level below normal low. Refill should be active. Check supply and solenoid.,10s,No ```

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library