Field fix / guidePLC / HMI Code & LogicVendor-agnostic (IEC 61131-3)Sorting Classificationindustrial-automation
Bottle Weight Verify — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 46 views
# Bottle Weight Verify — Usage Guide
## Overview
Bottle fill verification template using a pass/fail weight window and reject gate. Includes a basic SPC-style failure-rate alarm to highlight filler drift.
## Commissioning
1. Establish min/max weight limits from fill specification
2. Verify reject timing matches conveyor speed and reject station offset
3. Confirm failure-rate alarm is based on a representative sample size
---
## Control Logic — Vendor-Agnostic Pseudocode
# Bottle Weight Verify — Logic
## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2
## Scan Rate: 10ms | Pattern: pass/fail checkweigher with SPC alarm
```
ROUTINE: BottleWeightVerify
SCAN_RATE: 10ms
// SECTION 1 — PASS FAIL
IF SAMPLE_READY THEN
PASS := (WEIGHT_PV >= MIN_WEIGHT_SP) AND (WEIGHT_PV <= MAX_WEIGHT_SP)
IF PASS THEN PASS_COUNT := PASS_COUNT + 1 ELSE FAIL_COUNT := FAIL_COUNT + 1 END_IF
END_IF
// SECTION 2 — REJECT GATE
IF SAMPLE_READY AND NOT PASS THEN
REJECT_CMD := TRUE
END_IF
IF REJECT_CMD THEN
REJECT_TMR := REJECT_TMR + 1
IF REJECT_TMR >= REJECT_TIME_TICKS THEN REJECT_CMD := FALSE; REJECT_TMR := 0 END_IF
END_IF
// SECTION 3 — SPC
TOTAL_COUNT := PASS_COUNT + FAIL_COUNT
IF TOTAL_COUNT >= SPC_MIN_COUNT THEN
FAIL_RATE := (FAIL_COUNT * 100.0) / TOTAL_COUNT
IF FAIL_RATE >= FAIL_RATE_SP THEN SET_ALARM(ALM_HIGH_FAIL_RATE, HIGH) END_IF
END_IF
// SECTION 4 — HMI
HMI_PASS := PASS
HMI_WEIGHT := WEIGHT_PV
HMI_FAIL_RATE := FAIL_RATE
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
SAMPLE_READY,Weigh Sample Ready Pulse,BOOL,input,,,,FALSE,DI:0:0.0
WEIGHT_PV,Measured Bottle Weight,REAL,input,g,0,5000,0,AI:0:0.0
MIN_WEIGHT_SP,Minimum Accept Weight,REAL,internal,g,0,5000,490,
MAX_WEIGHT_SP,Maximum Accept Weight,REAL,internal,g,0,5000,510,
PASS,Pass/Fail Result,BOOL,calculated,,,,FALSE,
REJECT_CMD,Reject Gate Command,BOOL,output,,,,FALSE,DO:1:0.0
REJECT_TMR,Reject Pulse Timer,INT,internal,,0,1000,0,
REJECT_TIME_TICKS,Reject Pulse Duration,INT,internal,,0,1000,30,
PASS_COUNT,Accepted Bottle Count,DINT,internal,,0,999999,0,
FAIL_COUNT,Rejected Bottle Count,DINT,internal,,0,999999,0,
TOTAL_COUNT,Total Checked Count,DINT,calculated,,0,999999,0,
FAIL_RATE,Failure Rate,REAL,calculated,%,0,100,0,
SPC_MIN_COUNT,Minimum Sample Size for SPC,INT,internal,,0,999999,50,
FAIL_RATE_SP,Failure Rate Alarm Threshold,REAL,internal,%,0,100,3,
ALM_HIGH_FAIL_RATE,High Failure Rate Alarm,BOOL,calculated,,,,FALSE,
HMI_PASS,HMI: Pass Result,BOOL,output,,,,FALSE,
HMI_WEIGHT,HMI: Bottle Weight,REAL,output,g,0,5000,0,
HMI_FAIL_RATE,HMI: Failure Rate,REAL,output,%,0,100,0,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_HIGH_FAIL_RATE,FAIL_RATE >= FAIL_RATE_SP after SPC_MIN_COUNT samples,3%,high,process,Reject rate too high. Investigate filler calibration and bottle tare variation.,0s,No
```