Latching Interlock Pump — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 49 views
# Latching & Interlocking Pump Control — Usage Guide
## Overview
This template implements production-grade pump motor control with full IEC 61131-3 seal-in latch, 7-condition permissive interlock gate, manual/auto/off mode, hard-reset fault latch, star-delta soft-start sequencing, runtime accumulation, and ISA-18.2 alarm hierarchy.
Suitable for: process pumps, cooling water pumps, transfer pumps, fire-water jockey pumps, condensate pumps, chemical dosing pumps.
## Standards Compliance
| Standard | Application |
|----------|-------------|
| IEC 61131-3 | Ladder logic / ST structured text |
| ISA-5.1 | P&ID symbology (pump, valves, transmitters) |
| ISA-18.2 | Alarm management — 4-tier priority |
| IEC 61508 SIL1 | E-Stop circuit design (NC loop, hardwired) |
| ISO 10816-3 | Vibration trip level (11.2 mm/s Class II) |
| NEMA MG1 | Motor thermal protection (starts per hour) |
## I/O Requirements
| Signal | Type | Address | Notes |
|--------|------|---------|-------|
| Start PB (NO) | DI 24VDC | DI:0:0.0 | Debounced 20ms |
| Stop PB (NC) | DI 24VDC | DI:0:0.1 | Fail-safe wiring |
| Run Feedback | DI 24VDC | DI:0:0.2 | Contactor aux contact |
| Reset PB | DI 24VDC | DI:0:0.3 | Manual fault reset |
| Overload Relay (NC) | DI 24VDC | DI:0:0.4 | MCC auxiliary |
| E-Stop Circuit (NC) | DI 24VDC | DI:0:0.5 | Safety relay output |
| XV-Suction Open LS | DI 24VDC | DI:0:0.6 | Limit switch |
| XV-Discharge Open LS | DI 24VDC | DI:0:0.7 | Limit switch |
| Suction Pressure | AI 4-20mA | AI:2:0.0 | 0–1000 kPag |
| Discharge Pressure | AI 4-20mA | AI:2:0.1 | 0–2000 kPag |
| Bearing Temperature | AI 4-20mA | AI:2:0.2 | 0–150°C RTD/TC |
| Motor Current | AI 4-20mA | AI:2:0.3 | Via CT/ammeter relay |
| Vibration (RMS) | AI 4-20mA | AI:2:0.4 | ISO 10816 probe |
| Pump Output (DOL) | DO 24VDC | DO:1:0.0 | To MCC control voltage |
| Main Contactor (Y/Δ) | DO 24VDC | DO:1:0.0 | Star-delta only |
| Star Contactor | DO 24VDC | DO:1:0.1 | Star-delta only |
| Delta Contactor | DO 24VDC | DO:1:0.2 | Star-delta only |
## Permissive Configuration
Adjust setpoints in the Internal tags before commissioning:
| Parameter | Default | Tune Based On |
|-----------|---------|---------------|
| `SUCTION_MIN_SETPOINT` | 50 kPag | Pump NPSH curve |
| `DISCHARGE_MAX_SETPOINT` | 1500 kPag | Pipe/equipment rating |
| `BEARING_TEMP_MAX` | 85°C | Bearing manufacturer spec |
| `VIBRATION_TRIP_MMSEC` | 11.2 mm/s | ISO 10816-3 Class II |
| `MOTOR_TRIP_AMPS` | 120 A | Motor FLA × 1.15 |
| `MAX_STARTS_PER_HOUR` | 6 | Motor manufacturer data |
## Star-Delta Configuration
Enable `SOFT_START_ENABLED = TRUE` for motors ≥ 15 kW.
Set `STAR_DELTA_TIME_TICKS` (10ms ticks):
- 4s transition = 400 ticks (default)
- 6s transition = 600 ticks (large motors)
**Wiring**: Ensure electrical interlock between Star and Delta contactors — never close both simultaneously.
## Mode Selector
| Mode | Value | Behaviour |
|------|-------|-----------|
| OFF | 0 | Force stop. Inhibits all start signals |
| MANUAL | 1 | Start/stop by operator pushbutton only |
| AUTO | 2 | Process logic can start/stop; PB still overrides |
## Commissioning Checklist
- [ ] All I/O loop-checked with 24VDC and mA sources
- [ ] Verify E-Stop NC loop energised (ESTOP_CIRCUIT_OK = TRUE when safe)
- [ ] Verify overload relay NC contact wiring
- [ ] Stroke pump by hand; check rotation before first energisation
- [ ] Test each permissive individually — force tag FALSE, confirm start blocked
- [ ] Test each trip — force tag to trip value, confirm immediate stop and fault latch
- [ ] Test fault reset — verify fault clears only when condition resolved
- [ ] Test star-delta sequencing — confirm no simultaneous contactor energisation
- [ ] Check discrepancy alarm — remove feedback wire; confirm alarm after 3s
- [ ] Verify vibration probe reading at idle vs running
- [ ] Set maintenance interval to match pump class (consult OEM)
- [ ] Review alarm setpoints with operations and process engineer
## Tuning Notes
- Start `BEARING_TEMP_MAX` at OEM spec less 10°C margin
- Set `DISCHARGE_HH_SETPOINT` at minimum of: pipe pressure rating × 0.90 or pump shutoff head
- For HVAC pumps: reduce `VIBRATION_TRIP_MMSEC` to 7.1 mm/s (ISO 10816-3 Class I)
- For fire-water jockey: disable `DISCHARGE_MAX_SETPOINT` permissive (pumps into dead-end)
---
## Control Logic — Vendor-Agnostic Pseudocode
# Latching & Interlocking Pump Control — Logic
## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2 | IEC 61508 SIL1
## Scan Rate: 10ms | Watchdog: 100ms
```
ROUTINE: LatchingInterlockPumpControl
SCAN_RATE: 10ms
// ═══════════════════════════════════════════════════════════════
// SECTION 1 — INPUT DEBOUNCE & SIGNAL VALIDATION
// Per IEC 61131-3: never act on raw discrete inputs directly.
// 20ms debounce prevents contact bounce causing false starts/stops.
// ═══════════════════════════════════════════════════════════════
// Debounce Start pushbutton (NO contact, normally open)
IF PB_START_RAW = TRUE THEN
PB_START_DB_CTR := PB_START_DB_CTR + 1
ELSE
PB_START_DB_CTR := 0
END_IF
PB_START := (PB_START_DB_CTR >= 2) // 2 × 10ms = 20ms confirmed
// Debounce Stop pushbutton (NC contact, normally closed)
// Fail-safe: loss of signal = STOP command
IF PB_STOP_RAW = FALSE THEN
PB_STOP_DB_CTR := PB_STOP_DB_CTR + 1
ELSE
PB_STOP_DB_CTR := 0
END_IF
PB_STOP_ACTIVE := (PB_STOP_DB_CTR >= 2) // True when NC contact opens (stop)
// Validate run feedback signal (contactor auxiliary contact)
// Discrepancy alarm if command ≠ feedback for > 3s
IF PUMP_CMD <> PUMP_RUN_FB THEN
DISCREPANCY_TMR := DISCREPANCY_TMR + 1 // 10ms increments
IF DISCREPANCY_TMR >= 300 THEN // 3.0s
DISCREPANCY_ALARM := TRUE
END_IF
ELSE
DISCREPANCY_TMR := 0
DISCREPANCY_ALARM := FALSE
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 2 — PERMISSIVE INTERLOCK EVALUATION
// ALL permissives must be TRUE before START is accepted.
// Modelled as an AND-gate; any FALSE blocks start.
// Each permissive has an individual alarm tag for diagnostics.
// ═══════════════════════════════════════════════════════════════
// P1: Suction pressure adequate (prevent cavitation)
PERM_SUCTION_OK := (PT_SUCTION_PV > SUCTION_MIN_SETPOINT)
IF NOT PERM_SUCTION_OK THEN
ALM_LOW_SUCTION := TRUE
END_IF
// P2: Discharge pressure not high (prevent deadhead/overpressure)
PERM_DISC_OK := (PT_DISCHARGE_PV < DISCHARGE_MAX_SETPOINT)
IF NOT PERM_DISC_OK THEN
ALM_HIGH_DISCHARGE := TRUE
END_IF
// P3: Bearing temperature within limits
PERM_BEARING_OK := (TT_BEARING_PV < BEARING_TEMP_MAX)
IF NOT PERM_BEARING_OK THEN
ALM_HIGH_BEARING_TEMP := TRUE
END_IF
// P4: Motor thermal overload relay healthy (NC contact from MCC)
PERM_OL_OK := (OVERLOAD_RELAY_OK = TRUE)
IF NOT PERM_OL_OK THEN
ALM_OVERLOAD := TRUE
END_IF
// P5: E-Stop circuit healthy (hardwired, NC loop)
PERM_ESTOP_OK := (ESTOP_CIRCUIT_OK = TRUE)
IF NOT PERM_ESTOP_OK THEN
ALM_ESTOP_ACTIVE := TRUE
END_IF
// P6: Process system ready (upstream valve open, downstream path clear)
PERM_PROCESS_OK := (XV_SUCTION_OPEN AND XV_DISCHARGE_OPEN)
IF NOT PERM_PROCESS_OK THEN
ALM_PROCESS_NOT_READY := TRUE
END_IF
// P7: Previous fault cleared
PERM_FAULT_CLR := NOT PUMP_FAULT_LATCHED
// Master permissive gate — all 7 conditions required
PERMISSIVES_OK := (PERM_SUCTION_OK AND
PERM_DISC_OK AND
PERM_BEARING_OK AND
PERM_OL_OK AND
PERM_ESTOP_OK AND
PERM_PROCESS_OK AND
PERM_FAULT_CLR)
// ═══════════════════════════════════════════════════════════════
// SECTION 3 — MODE SELECTION
// 0 = OFF (force stop, inhibit auto)
// 1 = MANUAL (operator control only)
// 2 = AUTO (remote/PLC start/stop signals accepted)
// ═══════════════════════════════════════════════════════════════
CASE MODE_SELECTOR OF
0: // OFF MODE — force stop regardless
PUMP_CMD := FALSE
AUTO_START_ENABLED := FALSE
1: // MANUAL MODE — operator PB controls with permissives
AUTO_START_ENABLED := FALSE
// Seal-in latch: START sets latch, STOP clears it
IF PB_START AND PERMISSIVES_OK AND NOT PUMP_LATCH THEN
PUMP_LATCH := TRUE
START_TIMESTAMP := SYSTEM_CLOCK
END_IF
IF PB_STOP_ACTIVE OR NOT PERMISSIVES_OK THEN
PUMP_LATCH := FALSE
END_IF
PUMP_CMD := PUMP_LATCH
2: // AUTO MODE — remote signals accepted; PB still overrides
AUTO_START_ENABLED := TRUE
// Auto start from process demand
IF AUTO_START_REQUEST AND PERMISSIVES_OK AND NOT PUMP_LATCH THEN
PUMP_LATCH := TRUE
START_TIMESTAMP := SYSTEM_CLOCK
END_IF
// Auto stop from process demand, OR manual stop, OR permissive lost
IF AUTO_STOP_REQUEST OR PB_STOP_ACTIVE OR NOT PERMISSIVES_OK THEN
PUMP_LATCH := FALSE
END_IF
// Manual start still works in AUTO mode (local override)
IF PB_START AND PERMISSIVES_OK AND NOT PUMP_LATCH THEN
PUMP_LATCH := TRUE
START_TIMESTAMP := SYSTEM_CLOCK
END_IF
PUMP_CMD := PUMP_LATCH
END_CASE
// ═══════════════════════════════════════════════════════════════
// SECTION 4 — TRIP / FAULT LATCH
// Once a trip occurs the latch holds PUMP_CMD=FALSE until
// operator explicitly resets AND the fault condition clears.
// IEC 61508: trip latch must be manual-reset only.
// ═══════════════════════════════════════════════════════════════
// Trip conditions (any causes immediate stop and latches fault)
TRIP_HIGH_BEARING := (TT_BEARING_PV > BEARING_TEMP_TRIP)
TRIP_HIGH_VIBRATION := (ZT_VIBRATION_PV > VIBRATION_TRIP_MMSEC)
TRIP_HIGH_CURRENT := (ET_MOTOR_AMPS > MOTOR_TRIP_AMPS)
TRIP_ESTOP := NOT ESTOP_CIRCUIT_OK
TRIP_OL := NOT OVERLOAD_RELAY_OK
// Any trip → latch fault
IF (TRIP_HIGH_BEARING OR TRIP_HIGH_VIBRATION OR
TRIP_HIGH_CURRENT OR TRIP_ESTOP OR TRIP_OL) THEN
PUMP_FAULT_LATCHED := TRUE
PUMP_LATCH := FALSE // Immediately de-energise output
PUMP_CMD := FALSE
FAULT_CODE := ENCODE_FAULT_CODE(TRIP_HIGH_BEARING,
TRIP_HIGH_VIBRATION,
TRIP_HIGH_CURRENT,
TRIP_ESTOP,
TRIP_OL)
ALM_PUMP_TRIP := TRUE
END_IF
// Manual reset: all trip conditions cleared AND operator presses reset
IF RESET_CMD AND NOT (TRIP_HIGH_BEARING OR TRIP_HIGH_VIBRATION OR
TRIP_HIGH_CURRENT OR TRIP_ESTOP OR TRIP_OL) THEN
PUMP_FAULT_LATCHED := FALSE
ALM_PUMP_TRIP := FALSE
FAULT_CODE := 0
RESET_CMD := FALSE // Self-clear reset bit
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 5 — SOFT-START / STAR-DELTA SEQUENCING (if applicable)
// Reduces inrush current; protects mechanical couplings.
// Timer controls transition from star (Y) to delta (Δ) winding.
// ═══════════════════════════════════════════════════════════════
IF PUMP_CMD AND SOFT_START_ENABLED THEN
IF NOT STAR_DELTA_COMPLETE THEN
CONTACTOR_MAIN := TRUE
CONTACTOR_STAR := TRUE
CONTACTOR_DELTA := FALSE
STAR_DELTA_TMR := STAR_DELTA_TMR + 1 // 10ms ticks
IF STAR_DELTA_TMR >= STAR_DELTA_TIME_TICKS THEN // Default 400 ticks = 4s
// Transition: open star, pause 50ms, close delta
CONTACTOR_STAR := FALSE
IF TRANSITION_PAUSE_CTR < 5 THEN // 50ms pause
TRANSITION_PAUSE_CTR := TRANSITION_PAUSE_CTR + 1
ELSE
CONTACTOR_DELTA := TRUE
STAR_DELTA_COMPLETE := TRUE
TRANSITION_PAUSE_CTR := 0
END_IF
END_IF
END_IF
ELSIF NOT PUMP_CMD THEN
CONTACTOR_MAIN := FALSE
CONTACTOR_STAR := FALSE
CONTACTOR_DELTA := FALSE
STAR_DELTA_TMR := 0
STAR_DELTA_COMPLETE := FALSE
TRANSITION_PAUSE_CTR := 0
ELSE
// No soft-start: direct-on-line
CONTACTOR_MAIN := PUMP_CMD
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 6 — RUNTIME ACCUMULATION & MAINTENANCE TIMERS
// ISA-5.1: track run hours per pump for preventive maintenance.
// ═══════════════════════════════════════════════════════════════
IF PUMP_RUN_FB THEN
RUNTIME_ACCUM_TICKS := RUNTIME_ACCUM_TICKS + 1
IF RUNTIME_ACCUM_TICKS >= 360000 THEN // 3,600,000ms / 10ms = 360000 ticks per hour
RUNTIME_HOURS := RUNTIME_HOURS + 1.0
RUNTIME_ACCUM_TICKS := 0
END_IF
END_IF
// Maintenance due alarm
IF RUNTIME_HOURS >= MAINTENANCE_INTERVAL_HOURS THEN
ALM_MAINTENANCE_DUE := TRUE
END_IF
// Start counter
IF RISING_EDGE(PUMP_RUN_FB) THEN
START_COUNT := START_COUNT + 1
END_IF
// Excessive starts alarm (prevents thermal motor damage)
// ISA-88: track restart interval; block if > N starts per hour
IF START_COUNT_HOURLY > MAX_STARTS_PER_HOUR THEN
ALM_EXCESSIVE_STARTS := TRUE
PUMP_LATCH := FALSE
PUMP_CMD := FALSE
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 7 — PROCESS ALARMS (ISA-18.2 priority hierarchy)
// ═══════════════════════════════════════════════════════════════
// CRITICAL — immediate action, audible alarm
IF PT_DISCHARGE_PV > DISCHARGE_HH_SETPOINT THEN
SET_ALARM(ALM_DISC_PRESS_HH, CRITICAL, AUDIBLE)
PUMP_LATCH := FALSE // Trip on high-high discharge (overpressure)
PUMP_CMD := FALSE
END_IF
// HIGH — urgent action within 10 minutes
IF PT_DISCHARGE_PV > DISCHARGE_H_SETPOINT THEN
SET_ALARM(ALM_DISC_PRESS_H, HIGH)
END_IF
IF PT_SUCTION_PV < SUCTION_L_SETPOINT THEN
SET_ALARM(ALM_SUCT_PRESS_L, HIGH)
END_IF
IF TT_BEARING_PV > BEARING_H_SETPOINT THEN
SET_ALARM(ALM_BEARING_TEMP_H, HIGH)
END_IF
// MEDIUM — action within 1 hour
IF DISCREPANCY_ALARM THEN
SET_ALARM(ALM_CMD_FB_DISCREPANCY, MEDIUM)
END_IF
// LOW — informational
IF ALM_MAINTENANCE_DUE THEN
SET_ALARM(ALM_MAINTENANCE, LOW)
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 8 — AUDIT LOG
// Per TSIMEREZIVO RULE-P5: every state change generates audit entry.
// ═══════════════════════════════════════════════════════════════
IF RISING_EDGE(PUMP_CMD) THEN
AUDIT_LOG(EVENT="PUMP_START", USER=OPERATOR_ID,
MODE=MODE_SELECTOR, PERMISSIVES=PERMISSIVES_OK,
TIMESTAMP=SYSTEM_CLOCK)
END_IF
IF FALLING_EDGE(PUMP_CMD) THEN
AUDIT_LOG(EVENT="PUMP_STOP", USER=OPERATOR_ID,
RUNTIME_HRS=RUNTIME_HOURS, FAULT=FAULT_CODE,
TIMESTAMP=SYSTEM_CLOCK)
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 9 — HMI STATUS OUTPUTS
// ═══════════════════════════════════════════════════════════════
HMI_PUMP_RUNNING := PUMP_RUN_FB
HMI_PUMP_CMD := PUMP_CMD
HMI_MODE := MODE_SELECTOR
HMI_PERMISSIVES_OK := PERMISSIVES_OK
HMI_FAULT_CODE := FAULT_CODE
HMI_RUNTIME_HOURS := RUNTIME_HOURS
HMI_START_COUNT := START_COUNT
HMI_SUCTION_PRESS := PT_SUCTION_PV
HMI_DISCHARGE_PRESS := PT_DISCHARGE_PV
HMI_BEARING_TEMP := TT_BEARING_PV
HMI_MOTOR_AMPS := ET_MOTOR_AMPS
HMI_VIBRATION := ZT_VIBRATION_PV
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
PB_START_RAW,Start Pushbutton Raw Input (NO),BOOL,input,,,,FALSE,DI:0:0.0
PB_STOP_RAW,Stop Pushbutton Raw Input (NC),BOOL,input,,,,TRUE,DI:0:0.1
PB_START,Start Pushbutton Debounced,BOOL,calculated,,,,FALSE,
PB_STOP_ACTIVE,Stop Command Active (after debounce),BOOL,calculated,,,,FALSE,
PB_START_DB_CTR,Start Debounce Counter (10ms ticks),INT,internal,,0,10,0,
PB_STOP_DB_CTR,Stop Debounce Counter (10ms ticks),INT,internal,,0,10,0,
PUMP_CMD,Pump Output Command,BOOL,output,,,,FALSE,DO:1:0.0
PUMP_RUN_FB,Pump Running Feedback (Contactor Aux),BOOL,input,,,,FALSE,DI:0:0.2
PUMP_LATCH,Pump Start Latch (Seal-In Bit),BOOL,internal,,,,FALSE,
PUMP_FAULT_LATCHED,Pump Fault Latch (Manual Reset Required),BOOL,internal,,,,FALSE,
FAULT_CODE,Encoded Fault Code (bitmask),INT,internal,,0,31,0,
RESET_CMD,Fault Reset Command from HMI/PB,BOOL,input,,,,FALSE,DI:0:0.3
MODE_SELECTOR,Operating Mode (0=OFF 1=MAN 2=AUTO),INT,input,,0,2,1,
AUTO_START_REQUEST,Auto Start Request from Process Logic,BOOL,input,,,,FALSE,
AUTO_STOP_REQUEST,Auto Stop Request from Process Logic,BOOL,input,,,,FALSE,
AUTO_START_ENABLED,Auto Mode Currently Active,BOOL,calculated,,,,FALSE,
PT_SUCTION_PV,Suction Pressure Process Value,REAL,input,kPag,0,1000,,AI:2:0.0
PT_DISCHARGE_PV,Discharge Pressure Process Value,REAL,input,kPag,0,2000,,AI:2:0.1
TT_BEARING_PV,Bearing Temperature Process Value,REAL,input,°C,0,150,,AI:2:0.2
ET_MOTOR_AMPS,Motor Current Process Value,REAL,input,A,0,1000,,AI:2:0.3
ZT_VIBRATION_PV,Pump Vibration RMS Velocity,REAL,input,mm/s,0,50,,AI:2:0.4
SUCTION_MIN_SETPOINT,Minimum Suction Pressure Permissive,REAL,internal,kPag,0,500,50,
DISCHARGE_MAX_SETPOINT,Maximum Discharge Pressure Permissive,REAL,internal,kPag,500,2000,1500,
DISCHARGE_H_SETPOINT,Discharge Pressure High Alarm Setpoint,REAL,internal,kPag,500,2000,1400,
DISCHARGE_HH_SETPOINT,Discharge Pressure High-High Trip Setpoint,REAL,internal,kPag,500,2000,1600,
SUCTION_L_SETPOINT,Suction Pressure Low Alarm Setpoint,REAL,internal,kPag,0,500,30,
BEARING_TEMP_MAX,Bearing Temperature Permissive Limit,REAL,internal,°C,0,150,85,
BEARING_H_SETPOINT,Bearing Temperature High Alarm Setpoint,REAL,internal,°C,0,150,80,
BEARING_TEMP_TRIP,Bearing Temperature Trip Setpoint,REAL,internal,°C,0,150,95,
VIBRATION_TRIP_MMSEC,Vibration Trip Level (ISO 10816 Class II),REAL,internal,mm/s,0,50,11.2,
MOTOR_TRIP_AMPS,Motor Overcurrent Trip Level,REAL,internal,A,0,1000,120,
OVERLOAD_RELAY_OK,Thermal Overload Relay Healthy (NC),BOOL,input,,,,TRUE,DI:0:0.4
ESTOP_CIRCUIT_OK,E-Stop Circuit Healthy (NC Safety Relay),BOOL,input,,,,TRUE,DI:0:0.5
XV_SUCTION_OPEN,Suction Isolation Valve Open Limit,BOOL,input,,,,FALSE,DI:0:0.6
XV_DISCHARGE_OPEN,Discharge Isolation Valve Open Limit,BOOL,input,,,,FALSE,DI:0:0.7
PERM_SUCTION_OK,Suction Pressure Permissive,BOOL,calculated,,,,FALSE,
PERM_DISC_OK,Discharge Pressure Permissive,BOOL,calculated,,,,FALSE,
PERM_BEARING_OK,Bearing Temperature Permissive,BOOL,calculated,,,,FALSE,
PERM_OL_OK,Overload Relay Permissive,BOOL,calculated,,,,FALSE,
PERM_ESTOP_OK,E-Stop Circuit Permissive,BOOL,calculated,,,,FALSE,
PERM_PROCESS_OK,Process System Ready Permissive,BOOL,calculated,,,,FALSE,
PERM_FAULT_CLR,No Latched Fault Permissive,BOOL,calculated,,,,FALSE,
PERMISSIVES_OK,All Permissives Satisfied,BOOL,calculated,,,,FALSE,
SOFT_START_ENABLED,Star-Delta Soft Start Enabled,BOOL,internal,,,,FALSE,
CONTACTOR_MAIN,Main Contactor Output,BOOL,output,,,,FALSE,DO:1:0.0
CONTACTOR_STAR,Star Contactor Output (Y),BOOL,output,,,,FALSE,DO:1:0.1
CONTACTOR_DELTA,Delta Contactor Output (Δ),BOOL,output,,,,FALSE,DO:1:0.2
STAR_DELTA_TMR,Star-Delta Transition Timer (10ms ticks),INT,internal,,0,1000,0,
STAR_DELTA_TIME_TICKS,Star-Delta Transition Time Setting (ticks),INT,internal,,100,1000,400,
STAR_DELTA_COMPLETE,Star-Delta Transition Completed,BOOL,internal,,,,FALSE,
TRANSITION_PAUSE_CTR,Star-Delta Inter-Transition Pause Counter,INT,internal,,0,10,0,
DISCREPANCY_TMR,Command/Feedback Discrepancy Timer (10ms ticks),INT,internal,,0,500,0,
DISCREPANCY_ALARM,Command/Feedback Discrepancy Alarm,BOOL,calculated,,,,FALSE,
RUNTIME_HOURS,Total Accumulated Runtime Hours,REAL,internal,h,0,99999,0,
RUNTIME_ACCUM_TICKS,Runtime Accumulator (10ms ticks),INT,internal,,0,360000,0,
START_COUNT,Total Start Count,DINT,internal,,0,999999,0,
START_COUNT_HOURLY,Starts in Last 60 Minutes,INT,internal,,0,100,0,
MAX_STARTS_PER_HOUR,Maximum Allowed Starts per Hour (thermal protection),INT,internal,,1,20,6,
MAINTENANCE_INTERVAL_HOURS,Preventive Maintenance Interval,REAL,internal,h,1000,50000,4000,
START_TIMESTAMP,Last Start Timestamp (epoch ms),DINT,internal,,,,0,
OPERATOR_ID,Operator ID for Audit Log,STRING,input,,,,SYSTEM,
ALM_LOW_SUCTION,Low Suction Pressure Alarm,BOOL,calculated,,,,FALSE,
ALM_HIGH_DISCHARGE,High Discharge Pressure Alarm,BOOL,calculated,,,,FALSE,
ALM_HIGH_BEARING_TEMP,High Bearing Temperature Alarm,BOOL,calculated,,,,FALSE,
ALM_OVERLOAD,Thermal Overload Alarm,BOOL,calculated,,,,FALSE,
ALM_ESTOP_ACTIVE,E-Stop Active Alarm,BOOL,calculated,,,,FALSE,
ALM_PROCESS_NOT_READY,Process Not Ready Alarm,BOOL,calculated,,,,FALSE,
ALM_PUMP_TRIP,Pump Trip Alarm (Latched),BOOL,calculated,,,,FALSE,
ALM_DISC_PRESS_HH,Discharge Pressure High-High Trip Alarm,BOOL,calculated,,,,FALSE,
ALM_DISC_PRESS_H,Discharge Pressure High Alarm,BOOL,calculated,,,,FALSE,
ALM_SUCT_PRESS_L,Suction Pressure Low Alarm,BOOL,calculated,,,,FALSE,
ALM_BEARING_TEMP_H,Bearing Temperature High Alarm,BOOL,calculated,,,,FALSE,
ALM_CMD_FB_DISCREPANCY,Command/Feedback Discrepancy Alarm,BOOL,calculated,,,,FALSE,
ALM_MAINTENANCE_DUE,Preventive Maintenance Due,BOOL,calculated,,,,FALSE,
ALM_EXCESSIVE_STARTS,Excessive Motor Starts Alarm,BOOL,calculated,,,,FALSE,
HMI_PUMP_RUNNING,HMI: Pump Running Status,BOOL,output,,,,FALSE,
HMI_PUMP_CMD,HMI: Pump Command State,BOOL,output,,,,FALSE,
HMI_MODE,HMI: Active Mode Display,INT,output,,0,2,1,
HMI_PERMISSIVES_OK,HMI: All Permissives Satisfied Display,BOOL,output,,,,FALSE,
HMI_FAULT_CODE,HMI: Active Fault Code,INT,output,,0,31,0,
HMI_RUNTIME_HOURS,HMI: Accumulated Runtime Hours,REAL,output,h,0,99999,0,
HMI_START_COUNT,HMI: Total Start Count,DINT,output,,0,999999,0,
HMI_SUCTION_PRESS,HMI: Suction Pressure Display,REAL,output,kPag,0,1000,0,
HMI_DISCHARGE_PRESS,HMI: Discharge Pressure Display,REAL,output,kPag,0,2000,0,
HMI_BEARING_TEMP,HMI: Bearing Temperature Display,REAL,output,°C,0,150,0,
HMI_MOTOR_AMPS,HMI: Motor Current Display,REAL,output,A,0,1000,0,
HMI_VIBRATION,HMI: Vibration Level Display,REAL,output,mm/s,0,50,0,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_DISC_PRESS_HH,PT_DISCHARGE_PV >= DISCHARGE_HH_SETPOINT,1600 kPag,critical,safety,Pump trips automatically. Check discharge valve; notify shift engineer immediately. Inspect for deadhead condition.,0s,No
ALM_PUMP_TRIP,PUMP_FAULT_LATCHED = TRUE,N/A,critical,equipment,Identify and clear root-cause fault. Press RESET only after fault confirmed cleared. Check FAULT_CODE register for detail.,0s,No
ALM_ESTOP_ACTIVE,ESTOP_CIRCUIT_OK = FALSE,N/A,critical,safety,Investigate E-Stop activation. Verify area is safe before resetting. Check safety relay and wiring loop.,0s,No
ALM_DISC_PRESS_H,PT_DISCHARGE_PV >= DISCHARGE_H_SETPOINT,1400 kPag,high,process,Check downstream system for blockage or valve closure. Prepare for possible trip at HH.,5s,No
ALM_SUCT_PRESS_L,PT_SUCTION_PV <= SUCTION_L_SETPOINT,30 kPag,high,process,Check suction source level. Verify suction isolation valve is fully open. Risk of cavitation.,5s,No
ALM_HIGH_BEARING_TEMP,TT_BEARING_PV >= BEARING_H_SETPOINT,80°C,high,equipment,Reduce load if possible. Check lubrication oil level and condition. Schedule bearing inspection.,10s,No
ALM_OVERLOAD,OVERLOAD_RELAY_OK = FALSE,N/A,high,equipment,Motor thermal overload tripped. Allow motor to cool (min 20 min). Investigate overload cause before reset.,0s,No
ALM_LOW_SUCTION,PT_SUCTION_PV <= SUCTION_MIN_SETPOINT,50 kPag,high,process,Pump blocked from starting by low suction permissive. Restore suction pressure before starting.,2s,No
ALM_CMD_FB_DISCREPANCY,ABS(PUMP_CMD vs PUMP_RUN_FB) > 3s,3s timeout,medium,equipment,Output commanded but feedback disagrees. Check MCC control power. Check contactor and auxiliary contact.,3s,Yes
ALM_EXCESSIVE_STARTS,START_COUNT_HOURLY > MAX_STARTS_PER_HOUR,6 starts/hr,medium,equipment,Pump restart rate exceeds thermal limit. Investigate process instability. Pump locked out until hour resets.,0s,No
ALM_HIGH_BEARING_TEMP,TT_BEARING_PV >= BEARING_TEMP_TRIP,95°C,critical,equipment,Pump will trip automatically. Immediate maintenance required. Do not restart until bearing inspected.,0s,No
ALM_MAINTENANCE_DUE,RUNTIME_HOURS >= MAINTENANCE_INTERVAL_HOURS,4000 h,low,diagnostic,Schedule preventive maintenance (bearing grease/replacement, mechanical seal check, vibration survey).,0s,Yes
ALM_HIGH_DISCHARGE,PT_DISCHARGE_PV >= DISCHARGE_MAX_SETPOINT,1500 kPag,medium,process,Start blocked by high discharge permissive. Verify downstream path is clear before restarting.,2s,No
ALM_PROCESS_NOT_READY,XV_SUCTION_OPEN=FALSE OR XV_DISCHARGE_OPEN=FALSE,N/A,medium,process,Isolation valve(s) not fully open. Open valves before starting pump.,2s,No
```