Vehicle Washing — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 35 views
# Vehicle Washing — Usage Guide
## Overview
Simple vehicle-triggered wash spray control for wheel washes or spray arches.
## Commissioning
1. Verify vehicle detection coverage and false-trigger immunity
2. Set spray duration to achieve coverage without waste
3. Confirm low-water alarm before unattended operation
---
## Control Logic — Vendor-Agnostic Pseudocode
# Vehicle Washing — Logic
## Standards: IEC 61131-3
## Scan Rate: 100ms | Pattern: wheel wash / spray arch control
```
ROUTINE: VehicleWashing
SCAN_RATE: 100ms
IF VEHICLE_DETECTED THEN SPRAY_CMD := TRUE; SPRAY_TMR := 0 END_IF
IF SPRAY_CMD THEN SPRAY_TMR := SPRAY_TMR + 1 END_IF
IF SPRAY_TMR >= SPRAY_TIME_TICKS THEN SPRAY_CMD := FALSE END_IF
IF LOW_WATER THEN SET_ALARM(ALM_LOW_WATER, HIGH) END_IF
HMI_SPRAY := SPRAY_CMD
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
VEHICLE_DETECTED,Vehicle Detection Sensor,BOOL,input,,,,FALSE,DI:0:0.0
LOW_WATER,Low Water Level Alarm Input,BOOL,input,,,,FALSE,DI:0:0.1
SPRAY_CMD,Spray Pump/Valve Command,BOOL,output,,,,FALSE,DO:1:0.0
SPRAY_TMR,Spray Timer,INT,internal,,0,100000,0,
SPRAY_TIME_TICKS,Spray Duration,INT,internal,,0,100000,80,
ALM_LOW_WATER,Low Water Alarm,BOOL,calculated,,,,FALSE,
HMI_SPRAY,HMI: Spray Active,BOOL,output,,,,FALSE,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_LOW_WATER,LOW_WATER = TRUE,N/A,high,process,Low water supply. Washing performance degraded or unavailable.,0s,No
```