4 Conveyor Interlock — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 45 views
# 4 Conveyor Interlock — Usage Guide
## Overview
Downstream-first conveyor start sequence for four linked conveyors. Each upstream conveyor requires the downstream conveyor to be healthy and running before it can start. Any downstream fault propagates upstream shutdown.
## Sequence
1. Start Conveyor 4
2. After feedback, start Conveyor 3
3. After feedback, start Conveyor 2
4. After feedback, start Conveyor 1
This prevents product pile-up and ensures downstream flow path is available before feeding material.
## Commissioning
1. Verify each conveyor run feedback before enabling auto sequence
2. Test downstream fault propagation from Conveyor 4 backward
3. Test E-stop and confirm all commands drop immediately
---
## Control Logic — Vendor-Agnostic Pseudocode
# 4 Conveyor Interlock — Logic
## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2
## Scan Rate: 10ms | Pattern: downstream permissive start sequence with E-stop cascade
```
ROUTINE: FourConveyorInterlock
SCAN_RATE: 10ms
// SECTION 1 — SAFETY AND PERMISSIVES
SYSTEM_READY := NOT ESTOP_ACTIVE AND NOT GLOBAL_FAULT
C4_READY := SYSTEM_READY AND C4_HEALTHY
C3_READY := C4_READY AND C3_HEALTHY
C2_READY := C3_READY AND C2_HEALTHY
C1_READY := C2_READY AND C1_HEALTHY
// SECTION 2 — START SEQUENCE (downstream to upstream)
IF AUTO_START_CMD AND C4_READY THEN
C4_CMD := TRUE
END_IF
IF C4_RUN_FB AND C3_READY THEN
C3_START_TMR := C3_START_TMR + 1
IF C3_START_TMR >= START_DELAY_TICKS THEN C3_CMD := TRUE END_IF
END_IF
IF C3_RUN_FB AND C2_READY THEN
C2_START_TMR := C2_START_TMR + 1
IF C2_START_TMR >= START_DELAY_TICKS THEN C2_CMD := TRUE END_IF
END_IF
IF C2_RUN_FB AND C1_READY THEN
C1_START_TMR := C1_START_TMR + 1
IF C1_START_TMR >= START_DELAY_TICKS THEN C1_CMD := TRUE END_IF
END_IF
// SECTION 3 — STOP CASCADE (upstream to downstream)
IF STOP_CMD OR ESTOP_ACTIVE THEN
C1_CMD := FALSE
C2_CMD := FALSE
C3_CMD := FALSE
C4_CMD := FALSE
END_IF
// SECTION 4 — FAULT PROPAGATION
IF C4_FAULT THEN C1_CMD := FALSE; C2_CMD := FALSE; C3_CMD := FALSE; SET_ALARM(ALM_C4_FAULT, HIGH) END_IF
IF C3_FAULT THEN C1_CMD := FALSE; C2_CMD := FALSE; SET_ALARM(ALM_C3_FAULT, HIGH) END_IF
IF C2_FAULT THEN C1_CMD := FALSE; SET_ALARM(ALM_C2_FAULT, HIGH) END_IF
IF C1_FAULT THEN SET_ALARM(ALM_C1_FAULT, HIGH) END_IF
IF ESTOP_ACTIVE THEN SET_ALARM(ALM_ESTOP, CRITICAL) END_IF
// SECTION 5 — HMI OUTPUTS
HMI_C1 := C1_RUN_FB
HMI_C2 := C2_RUN_FB
HMI_C3 := C3_RUN_FB
HMI_C4 := C4_RUN_FB
HMI_READY := C1_READY
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
AUTO_START_CMD,Auto Start Command,BOOL,input,,,,FALSE,
STOP_CMD,Stop Command,BOOL,input,,,,FALSE,
ESTOP_ACTIVE,E-Stop Active,BOOL,input,,,,FALSE,DI:0:0.0
GLOBAL_FAULT,Global System Fault,BOOL,input,,,,FALSE,
START_DELAY_TICKS,Inter-conveyor Start Delay (10ms ticks),INT,internal,,0,1000,100,
C1_HEALTHY,Conveyor 1 Healthy,BOOL,input,,,,TRUE,DI:0:0.1
C2_HEALTHY,Conveyor 2 Healthy,BOOL,input,,,,TRUE,DI:0:0.2
C3_HEALTHY,Conveyor 3 Healthy,BOOL,input,,,,TRUE,DI:0:0.3
C4_HEALTHY,Conveyor 4 Healthy,BOOL,input,,,,TRUE,DI:0:0.4
C1_FAULT,Conveyor 1 Fault,BOOL,input,,,,FALSE,DI:0:0.5
C2_FAULT,Conveyor 2 Fault,BOOL,input,,,,FALSE,DI:0:0.6
C3_FAULT,Conveyor 3 Fault,BOOL,input,,,,FALSE,DI:0:0.7
C4_FAULT,Conveyor 4 Fault,BOOL,input,,,,FALSE,DI:0:1.0
C1_RUN_FB,Conveyor 1 Run Feedback,BOOL,input,,,,FALSE,DI:0:1.1
C2_RUN_FB,Conveyor 2 Run Feedback,BOOL,input,,,,FALSE,DI:0:1.2
C3_RUN_FB,Conveyor 3 Run Feedback,BOOL,input,,,,FALSE,DI:0:1.3
C4_RUN_FB,Conveyor 4 Run Feedback,BOOL,input,,,,FALSE,DI:0:1.4
C1_CMD,Conveyor 1 Run Command,BOOL,output,,,,FALSE,DO:1:0.0
C2_CMD,Conveyor 2 Run Command,BOOL,output,,,,FALSE,DO:1:0.1
C3_CMD,Conveyor 3 Run Command,BOOL,output,,,,FALSE,DO:1:0.2
C4_CMD,Conveyor 4 Run Command,BOOL,output,,,,FALSE,DO:1:0.3
C1_READY,Conveyor 1 Permissive Ready,BOOL,calculated,,,,FALSE,
C2_READY,Conveyor 2 Permissive Ready,BOOL,calculated,,,,FALSE,
C3_READY,Conveyor 3 Permissive Ready,BOOL,calculated,,,,FALSE,
C4_READY,Conveyor 4 Permissive Ready,BOOL,calculated,,,,FALSE,
C1_START_TMR,Conveyor 1 Start Delay Timer,INT,internal,,0,1000,0,
C2_START_TMR,Conveyor 2 Start Delay Timer,INT,internal,,0,1000,0,
C3_START_TMR,Conveyor 3 Start Delay Timer,INT,internal,,0,1000,0,
ALM_C1_FAULT,Conveyor 1 Fault Alarm,BOOL,calculated,,,,FALSE,
ALM_C2_FAULT,Conveyor 2 Fault Alarm,BOOL,calculated,,,,FALSE,
ALM_C3_FAULT,Conveyor 3 Fault Alarm,BOOL,calculated,,,,FALSE,
ALM_C4_FAULT,Conveyor 4 Fault Alarm,BOOL,calculated,,,,FALSE,
ALM_ESTOP,E-Stop Active Alarm,BOOL,calculated,,,,FALSE,
HMI_C1,HMI: Conveyor 1 Status,BOOL,output,,,,FALSE,
HMI_C2,HMI: Conveyor 2 Status,BOOL,output,,,,FALSE,
HMI_C3,HMI: Conveyor 3 Status,BOOL,output,,,,FALSE,
HMI_C4,HMI: Conveyor 4 Status,BOOL,output,,,,FALSE,
HMI_READY,HMI: System Ready,BOOL,output,,,,FALSE,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_ESTOP,ESTOP_ACTIVE = TRUE,N/A,critical,safety,Emergency stop active. All conveyors stopped. Investigate before reset.,0s,No
ALM_C4_FAULT,C4_FAULT = TRUE,N/A,high,equipment,Downstream conveyor fault. Entire line stopped to prevent pile-up.,0s,No
ALM_C3_FAULT,C3_FAULT = TRUE,N/A,high,equipment,Conveyor 3 fault. Upstream conveyors stopped to protect line.,0s,No
ALM_C2_FAULT,C2_FAULT = TRUE,N/A,high,equipment,Conveyor 2 fault. Conveyor 1 stopped to prevent accumulation.,0s,No
ALM_C1_FAULT,C1_FAULT = TRUE,N/A,medium,equipment,Conveyor 1 fault. Inspect motor and belt condition.,0s,No
```