Field fix / guidePLC / HMI Code & LogicVendor-agnostic (IEC 61131-3)Mixing Dosingindustrial-automation

3 Material 4 Tank Batch — PLC Control Template

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 32 views

# 3 Material 4 Tank Batch — Usage Guide ## Overview Batch recipe template that pulls three materials from four available source tanks into a single batch vessel, then runs a timed mix phase. ## Commissioning 1. Verify each source tank low permissive 2. Confirm each valve stops at cumulative weight target 3. Validate mix time and product homogeneity before release --- ## Control Logic — Vendor-Agnostic Pseudocode # 3 Material 4 Tank Batch — Logic ## Standards: IEC 61131-3 | ISA-88 | ISA-18.2 ## Scan Rate: 100ms | Pattern: staged fill from four tanks into batch vessel ``` ROUTINE: ThreeMaterialFourTankBatch SCAN_RATE: 100ms // SECTION 1 — SOURCE SELECTION SRC1_OK := TK1_LEVEL > TK1_LOW_SP SRC2_OK := TK2_LEVEL > TK2_LOW_SP SRC3_OK := TK3_LEVEL > TK3_LOW_SP SRC4_OK := TK4_LEVEL > TK4_LOW_SP // SECTION 2 — SEQUENCE CASE SEQ_STATE OF 0: IF START_CMD THEN SEQ_STATE := 1 END_IF 1: XV1_CMD := SRC1_OK; IF BATCH_WEIGHT >= MAT1_SP THEN XV1_CMD := FALSE; SEQ_STATE := 2 END_IF 2: XV2_CMD := SRC2_OK; IF BATCH_WEIGHT >= (MAT1_SP + MAT2_SP) THEN XV2_CMD := FALSE; SEQ_STATE := 3 END_IF 3: XV3_CMD := SRC3_OK OR SRC4_OK; IF BATCH_WEIGHT >= (MAT1_SP + MAT2_SP + MAT3_SP) THEN XV3_CMD := FALSE; XV4_CMD := FALSE; SEQ_STATE := 4 END_IF 4: MIXER_CMD := TRUE; MIX_TMR := MIX_TMR + 1; IF MIX_TMR >= MIX_TIME_TICKS THEN MIXER_CMD := FALSE; MIX_TMR := 0; SEQ_STATE := 5 END_IF 5: COMPLETE := TRUE; IF ACK_CMD THEN COMPLETE := FALSE; SEQ_STATE := 0 END_IF END_CASE // SECTION 3 — ALARMS IF NOT SRC1_OK OR NOT SRC2_OK OR (NOT SRC3_OK AND NOT SRC4_OK) THEN SET_ALARM(ALM_SOURCE_LOW, HIGH) END_IF IF ESTOP_ACTIVE THEN SET_ALARM(ALM_ESTOP, CRITICAL) END_IF // SECTION 4 — HMI HMI_SEQ_STATE := SEQ_STATE HMI_BATCH_WEIGHT := BATCH_WEIGHT END_ROUTINE ``` --- ## Tag List ```csv Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address START_CMD,Batch Start Command,BOOL,input,,,,FALSE, ACK_CMD,Batch Complete Acknowledge,BOOL,input,,,,FALSE, ESTOP_ACTIVE,E-Stop Active,BOOL,input,,,,FALSE,DI:0:0.0 TK1_LEVEL,Tank 1 Level,REAL,input,%,0,100,100,AI:0:0.0 TK2_LEVEL,Tank 2 Level,REAL,input,%,0,100,100,AI:0:0.1 TK3_LEVEL,Tank 3 Level,REAL,input,%,0,100,100,AI:0:0.2 TK4_LEVEL,Tank 4 Level,REAL,input,%,0,100,100,AI:0:0.3 TK1_LOW_SP,Tank 1 Low Limit,REAL,internal,%,0,100,15, TK2_LOW_SP,Tank 2 Low Limit,REAL,internal,%,0,100,15, TK3_LOW_SP,Tank 3 Low Limit,REAL,internal,%,0,100,15, TK4_LOW_SP,Tank 4 Low Limit,REAL,internal,%,0,100,15, SRC1_OK,Tank 1 Available,BOOL,calculated,,,,FALSE, SRC2_OK,Tank 2 Available,BOOL,calculated,,,,FALSE, SRC3_OK,Tank 3 Available,BOOL,calculated,,,,FALSE, SRC4_OK,Tank 4 Available,BOOL,calculated,,,,FALSE, BATCH_WEIGHT,Batch Vessel Weight,REAL,input,kg,0,10000,0,AI:0:0.4 MAT1_SP,Material 1 Target Weight,REAL,input,kg,0,10000,40, MAT2_SP,Material 2 Target Weight,REAL,input,kg,0,10000,30, MAT3_SP,Material 3 Target Weight,REAL,input,kg,0,10000,20, SEQ_STATE,Sequence State,INT,internal,,0,5,0, XV1_CMD,Tank 1 Valve Command,BOOL,output,,,,FALSE,DO:1:0.0 XV2_CMD,Tank 2 Valve Command,BOOL,output,,,,FALSE,DO:1:0.1 XV3_CMD,Tank 3 Valve Command,BOOL,output,,,,FALSE,DO:1:0.2 XV4_CMD,Tank 4 Valve Command,BOOL,output,,,,FALSE,DO:1:0.3 MIXER_CMD,Mixer Command,BOOL,output,,,,FALSE,DO:1:0.4 MIX_TMR,Mix Timer,INT,internal,,0,100000,0, MIX_TIME_TICKS,Mix Duration,INT,internal,,0,100000,1200, COMPLETE,Batch Complete Flag,BOOL,internal,,,,FALSE, ALM_SOURCE_LOW,Source Tank Low Alarm,BOOL,calculated,,,,FALSE, ALM_ESTOP,E-Stop Alarm,BOOL,calculated,,,,FALSE, HMI_SEQ_STATE,HMI: Sequence State,INT,output,,0,5,0, HMI_BATCH_WEIGHT,HMI: Batch Weight,REAL,output,kg,0,10000,0, ``` --- ## Alarm Matrix ```csv Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge ALM_ESTOP,ESTOP_ACTIVE = TRUE,N/A,critical,safety,Emergency stop active. Batch motion stopped immediately.,0s,No ALM_SOURCE_LOW,Any required source unavailable,low level,high,process,One or more source tanks do not have sufficient inventory for batch execution.,0s,No ```

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library