Alarm Investigation & Management — Engineering Guide
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 50 views
#
Alarm Investigation & Management
TSIMEREZIVO implements ISA-18.2 alarm management across all process screens. This guide explains
how to investigate active alarms, use the alarm priority matrix, acknowledge and journal alarms,
and manage nuisance alarm flooding — all essential skills for control room operators.
15 min
## ISA-18.2 Alarm Priority Matrix
ISA-18.2 defines four alarm priorities based on consequence and operator response time.
Every alarm in TSIMEREZIVO must be assigned a priority that reflects the process consequence
if the operator does not respond within the response time.
| priority | consequence | response |
|---|---|---|
| Critical\n(HIHI/LOLO) | Immediate safety or environmental incident, plant damage, personnel injury. Requires immediate action to prevent escalation. |
## Investigating an Active Alarm
### Step 1 — Read the Alarm Banner
The alarm banner at the top of every operator screen shows active unacknowledged alarms.
Read the alarm tag, priority colour, current value, and trip setpoint.
Example: TT201 HIHI — 347°C — Trip: 340°C — 08:23:41
### Step 2 — Navigate to the Equipment
Click the alarm in the banner. TSIMEREZIVO navigates to the screen containing TT-201 and
opens its faceplate automatically. The faceplate shows:
- Current PV value with trend (last 15 minutes)
- Active alarm trip points on the trend
- Operating mode (Auto/Manual)
- Related interlocks status
### Step 3 — Diagnose the Root Cause
Use the trend and related tags to diagnose. Ask:
- Is the PV rising or falling? How fast?
- Did a setpoint change recently? (Check SP trend on same chart)
- Is the control valve (CV) at its limit — stuck open/closed?
- Did a related upstream alarm occur first? (Check alarm history time sequence)
- Is the measurement valid? (Check quality code — STALE or BAD = instrument fault)
### Step 4 — Take Action
Based on the diagnosis:
- **Switch to Manual**: if the control loop is not responding, switch PID to Manual in the faceplate and manually adjust CV
- **Adjust Setpoint**: if the SP is wrong, correct it in the faceplate (if permitted by role)
- **Initiate Safe Shutdown**: if temperature continues rising and you cannot control it, follow the site emergency procedure
- **Call Engineering**: if the cause is not clear, call the on-call engineer
### Step 5 — Acknowledge and Journal
Once you have responded, click **Acknowledge**
on the alarm faceplate. A journal entry box opens — enter what you observed and what action
you took. This is stored in the ISA-18.2 alarm log with timestamp and operator name.
The alarm returns to green when the process value returns to normal range.
## Alarm History Log
Access the full alarm history at **Alarms → History**.
Filter by time range, priority, equipment, or tag name.
| time | tag | eq | val | pri | desc | status | statusColor |
|---|---|---|---|---|---|---|---|
| 08:23:41 | TT201 | Reactor A | 347°C | HIHI | Temperature High-High — cooling water valve not responding | ACK | #22c55e |
| 08:19:05 | PP101_FAULT | CW Pump | FAULT | Critical | Motor starter overload trip — current > 42A | ACK | #22c55e |
| 08:11:22 | LT301_LO | Buffer Tank | 12% | High | Tank level Low — check feed pump PP-201 | UNACK | #ef4444 |
| 07:45:00 | FT401_LO | CW Supply | 180 L/m | Medium | Flow low warning — normal for overnight demand | ACK | #22c55e |
## Managing Alarm Floods
> **ISA-18.2 Alarm Rate Guideline** —
ISA-18.2 recommends a maximum of **1–2 alarms per operator per 10 minutes** during normal operation,
and no more than 10 alarms in the first 10 minutes of an abnormal event.
More than this constitutes an alarm flood — operators cannot effectively respond.
If you are experiencing alarm floods:
| action | desc |
|---|---|
| Alarm Shelving | Temporarily suppress a nuisance alarm for a defined period (max 24h). Requires a reason code. Shelved alarms still log but do not appear in the active alarm banner. |
| Alarm Rationalisation | Engineering review of trip setpoints — are limits correctly set? Use historical alarm data (Alarms → Analytics) to identify top 10 most frequent alarms and widen deadbands. |
| Alarm Suppression | Suppress alarms that occur during known transient conditions (startup, shutdown). Configurable as state-based suppression linked to a mode tag. |
| Priority Review | Many plants over-assign Critical priority. Review whether an alarm truly requires