Connection Diagnostics
When a PLC connection fails, a systematic diagnostic approach gets you back online fast.
This guide walks through the offline troubleshooting decision tree, protocol-specific checks,
Wireshark capture techniques, and the complete TSIMEREZIVO error code reference.
18 min
## Offline Troubleshooting Decision Tree
| q | yes | no | isStart |
|---|---|---|---|
| Is the TSIMEREZIVO connection status RED (OFFLINE)? | Continue → | Check quality codes (STALE/BAD) | true |
| Can you ping the PLC IP address from your machine? | Network OK → skip to Step 4 | → Network problem | false |
| Is the PLC in RUN/REMOTE mode (not PROGRAM mode)? | Continue → | → Change PLC to RUN mode | false |
| Is the protocol port open? (EIP: 44818, Modbus: 502) | Continue → | → Firewall rule blocking port | false |
| Does TSIMEREZIVO show the correct IP and slot/unit ID? | Continue → | → Edit connection settings and retry | false |
| Is any other client already connected? (S7 max 1–4) | Disconnect other clients first | → Check TSIMEREZIVO bridge logs | false |
## Network Ping Test
### Step 1 — Ping the PLC IP Address
TSIMEREZIVO includes a built-in network test at **Connections → [PLC] → Diagnostics → Ping**.
This sends 4 ICMP echo requests to the PLC IP and shows round-trip times.
Alternatively, from your terminal:
```bash
# macOS / Linux
ping -c 4 192.168.1.10
# Windows
ping -n 4 192.168.1.10
# Expected result (healthy connection):
64 bytes from 192.168.1.10: icmp_seq=0 ttl=128 time=0.8 ms
64 bytes from 192.168.1.10: icmp_seq=1 ttl=128 time=0.9 ms
# Bad result — packet loss:
Request timeout for icmp_seq 0
→ Check: Ethernet cable, switch port, PLC IP settings
```
### Step 2 — Check TCP Port Connectivity
Ping succeeds but TSIMEREZIVO still cannot connect? Check if the protocol port is open:
```bash
# EtherNet/IP (ControlLogix, CompactLogix)
nc -zv 192.168.1.10 44818
# Modbus TCP
nc -zv 192.168.1.10 502
# Siemens S7comm
nc -zv 192.168.1.10 102
# OPC-UA
nc -zv 192.168.1.10 4840
# Expected result: Connection succeeded!
# If failed: port is closed — check PLC firewall or IT network rules
```
## Protocol-Specific Diagnostics
| proto | tips | limit | CompactLogix |
|---|---|---|---|
| EtherNet/IP (Allen-Bradley) | [
'Verify slot number — ControlLogix CPU is typically slot 0. Wrong slot = connection refused.' | 500 bytes per request. Very wide tag arrays may need to be split.' | IP is on the CPU itself |
| Siemens S7comm (S7-300/400/1200/1500) | [
'S7-1200/1500: You MUST enable "PUT/GET communication" in TIA Portal → PLC Properties → Protection. Default is disabled.' | | |
| Modbus TCP | [
'Unit ID (slave ID) must match the device configuration. Default is usually 1 or 255.' | | |
| OPC-UA | [
'Security policy: TSIMEREZIVO supports None | | |
))}
## Wireshark Protocol Capture
### Step 1 — Capture Filter by Protocol
```wireshark
# EtherNet/IP
tcp port 44818
# Modbus TCP
tcp port 502
# Siemens S7
tcp port 102
# OPC-UA
tcp port 4840
```
### Step 2 — What to Look For
- **TCP RST (Reset)**: The PLC is refusing the connection — port closed or firewall
- **TCP SYN with no SYN-ACK**: No response from PLC — check network route
- **Modbus Exception Code 01**: Illegal function — FC not supported by device
- **Modbus Exception Code 02**: Illegal data address — register address out of range
- **S7 Error 0x8104**: PUT/GET not enabled — enable in TIA Portal
- **EIP Error 0x08**: Connection refused — another exclusive owner connected
## TSIMEREZIVO Error Code Reference
| code | meaning | resolution |
|---|---|---|
| CONN_TIMEOUT | TCP connection timed out after 10 seconds | Check network route, IP address, firewall rules. Try ping first. |
| CONN_REFUSED | PLC actively rejected the TCP connection | Check port is open. Check PLC is in RUN mode. Check max connections not exceeded. |
| AUTH_FAILED | OPC-UA session authentication rejected | Check username/password in connection settings. Import certificate if security mode is Basic256. |
| BAD_CONFIG | Connection parameters invalid | Review slot number (EIP), unit ID (Modbus), TSAP (S7), or endpoint URL (OPC-UA). |
| TAG_NOT_FOUND | Tag address does not exist in PLC | Verify tag name spelling and data type match PLC program. Check tag is not a local variable. |
| STALE_DATA | Last successful read > 2 polling cycles ago | PLC connection may be intermittent. Check network for high packet loss. |
| WRITE_BLOCKED | Write command blocked — safety tag | Tag has _ES, _STO, or _SIL suffix. Safety tags cannot be written via TSIMEREZIVO (RULE-P2). |
| POLL_TOO_FAST | Requested poll interval
### Related Guides
| href | label | desc |
|---|---|---|
| /dashboard/docs/controller-setup | Controller Setup | Initial connection wizard for all protocols |
| /dashboard/docs/live-connection | Live Tag Monitor | Quality codes: GOOD, STALE, BAD explained |
| /dashboard/docs/alarm-investigation | Alarm Investigation | STALE quality codes can cause false alarms |