Importing & Creating Tags — Engineering Guide
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 44 views
#
Importing & Creating Tags
Tags are the bridge between physical field signals and TSIMEREZIVO logic, HMI displays, and historical
data. This guide covers all three import methods: CSV batch upload, Studio 5000 L5X export,
and manual tag creation one-at-a-time.
15 min
## What is a Tag?
A tag is a named process variable — a single data point from a PLC, DCS or sensor.
Tags have a name,
a data type,
a PLC address,
engineering units, and optionally alarm limits. Every value you see in an HMI display,
trend chart, or alarm list is driven by a tag.
### Step 2 — Upload the CSV
Go to **Tags → Import → Upload CSV**.
Drag and drop your completed CSV file or click Browse. TSIMEREZIVO validates every row
and shows a preview table with any errors highlighted in red before committing.
### Step 3 — Review the Validation Report
TSIMEREZIVO shows a pre-import report: total rows, valid rows, error rows.
Common errors: duplicate tag names, unknown data_type, missing required columns,
invalid PLC address format. Fix errors in Excel and re-upload — or fix individual
rows in the preview table directly.
### Step 4 — Confirm Import
Click **Import Tags**. Tags are created instantly.
A success toast shows the count: e.g. *✓ 246 tags imported*.
## Method 2 — Studio 5000 L5X Export
If you use Allen-Bradley Studio 5000 or Logix Designer, you can export your entire controller
tag database as a standard L5X (XML) file and import it directly into TSIMEREZIVO.
### Step 1 — Export from Studio 5000
In Studio 5000: **File → Save As → Logix Designer XML (.L5X)**.
Include Controller Tags and Program Tags. Save the file.
### Step 2 — Upload the L5X
In TSIMEREZIVO: **Tags → Import → Upload L5X**.
TSIMEREZIVO parses the XML, extracts all controller-scope and program-scope tags,
their data types (including User-Defined Types / UDTs), and maps addresses automatically.
> **UDT / AOI Member Tags** —
TSIMEREZIVO expands UDT members into individual dot-notation tags.
E.g. a `MOTOR_FB` UDT
becomes `PP101.Speed`,
` PP101.Current`,
` PP101.Fault` etc.
AOI tags are similarly expanded.
## Method 3 — Manual Tag Creation
### Step 1 — Go to Tags → New Tag
Navigate to **Tags → + New Tag**.
Fill in the tag form fields as described in the CSV column definitions above.
Use manual entry for individual tags when making a small change or adding tags post-commissioning.
### Step 2 — Assign to Equipment
Every tag should be linked to an Equipment record. Use the **Equipment**
dropdown to associate this tag with a pump, valve, transmitter, or motor.
This enables equipment-level dashboards and tag grouping in HMI faceplates.
## PLC Data Types Reference
| type | bits | range | use |
|---|---|---|---|
| BOOL | 1 | 0 or 1 | Coils, discrete I/O, flags, alarms, push-buttons |
| INT | 16 | -32,768 to 32,767 | Raw ADC counts, speed setpoints, counters |
| DINT | 32 | -2,147,483,648 to 2,147,483,647 | High-resolution counters, time stamps in ms |
| REAL | 32 | ±3.4×10³⁸ (IEEE 754 float) | Scaled process values: temperature, flow, pressure |
| LREAL | 64 | ±1.8×10³⁰⁸ (double precision) | High-precision measurement, gas chromatographs |
| STRING | var | Up to 82 chars (AB), 254 (S7) | Batch IDs, recipe names, operator messages |
| WORD | 16 | 0 to 65,535 | Packed boolean words, status bytes, bitfield registers |
| DWORD | 32 | 0 to 4,294,967,295 | 32-bit status, packed alarms, Modbus 32-bit integers |
## Bulk Editing Tags
After import, you can edit multiple tags at once:
### Step 1 — Select Multiple Tags
In the Tags list, tick the checkboxes on multiple rows. Use Shift+Click to select a range.
The bulk action bar appears at the bottom of the screen.
### Step 2 — Apply Bulk Changes
You can change **Engineering Unit**,
** Alarm Limits**,
** Equipment Assignment**, or
** Controller Assignment** across all selected tags simultaneously.
Confirm in the dialog. A change log entry is created for each tag (ISA-18.2 audit trail).
### What's Next?
| href | label | desc |
|---|---|---|
| /dashboard/docs/live-connection | Go Live | Subscribe tags to see live PLC values |
| /dashboard/docs/ladder-logic | Ladder Logic | Write LD control logic using your new tags |
| /dashboard/docs/tag-binding | HMI Tag Binding | Bind tags to SCADA symbols and faceplates |