Field fix / guidePLC / HMI Code & LogicVendor-agnostic (IEC 61131-3)Access Trafficindustrial-automation
Object Detect Door — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 51 views
# Object Detect Door — Usage Guide
## Overview
Automatic door template with obstruction detection. A detected object prevents or reverses closing motion.
## Commissioning
1. Verify obstruction sensor coverage through the full doorway opening
2. Confirm closing reverses or halts immediately when an object is detected
3. Validate open and closed limit switch operation
---
## Control Logic — Vendor-Agnostic Pseudocode
# Object Detect Door — Logic
## Standards: IEC 61131-3 | EN 12453-inspired door safety
## Scan Rate: 20ms | Pattern: automatic door with obstruction detection
```
ROUTINE: ObjectDetectDoor
SCAN_RATE: 20ms
IF OPEN_REQUEST THEN DOOR_OPEN_CMD := TRUE END_IF
IF CLOSE_REQUEST THEN DOOR_CLOSE_CMD := TRUE END_IF
IF OBJECT_DETECTED THEN
DOOR_CLOSE_CMD := FALSE
DOOR_OPEN_CMD := TRUE
SET_ALARM(ALM_OBJECT_DETECTED, HIGH)
END_IF
IF DOOR_OPEN_LS THEN DOOR_OPEN_CMD := FALSE END_IF
IF DOOR_CLOSED_LS THEN DOOR_CLOSE_CMD := FALSE END_IF
HMI_DOOR_OPEN := DOOR_OPEN_LS
HMI_OBJECT := OBJECT_DETECTED
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
OPEN_REQUEST,Door Open Request,BOOL,input,,,,FALSE,
CLOSE_REQUEST,Door Close Request,BOOL,input,,,,FALSE,
OBJECT_DETECTED,Doorway Object Detected,BOOL,input,,,,FALSE,DI:0:0.0
DOOR_OPEN_LS,Door Open Limit Switch,BOOL,input,,,,FALSE,DI:0:0.1
DOOR_CLOSED_LS,Door Closed Limit Switch,BOOL,input,,,,TRUE,DI:0:0.2
DOOR_OPEN_CMD,Door Open Motor Command,BOOL,output,,,,FALSE,DO:1:0.0
DOOR_CLOSE_CMD,Door Close Motor Command,BOOL,output,,,,FALSE,DO:1:0.1
ALM_OBJECT_DETECTED,Object Detection Alarm,BOOL,calculated,,,,FALSE,
HMI_DOOR_OPEN,HMI: Door Open,BOOL,output,,,,FALSE,
HMI_OBJECT,HMI: Object Detected,BOOL,output,,,,FALSE,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_OBJECT_DETECTED,OBJECT_DETECTED = TRUE,N/A,high,safety,Object detected in doorway. Closing motion reversed/opened to protect passage.,0s,No
```