Pump Control (Single — On/Off with Protection) — Control Design

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 38 views

# Generic Module: Pump Control (Single — On/Off with Protection) **Version**: 1.0 **Complexity**: Low-Medium **Industries**: Water, Chemical, Oil & Gas, Food, Pharmaceuticals **Motor Type**: 3-phase induction, 5-400 kW typical **Control**: Soft-starter or VFD (recommended), or across-line contactor --- ## 📋 Overview Start/stop a single electric motor pump with automatic overload protection, dry-run prevention, and fault reporting. **Use When:** - ✅ Simple on/off pump operation (not needing speed modulation) - ✅ Constant flow demand meeting - ✅ Overload protection mandatory (motor thermal protection) - ✅ Dry-run protection required (cavitation/damage prevention) **Do NOT Use When:** - ❌ Variable speed needed (use VFD Motor Control template instead) - ❌ Dual pump duty/standby needed (use Pump Lead/Lag) - ❌ Soft-start capability not available (use simpler contactor relay) --- ## 🎯 Control Philosophy ``` Startup Sequence: 1. Check initial conditions (motor cool, suction pressure OK) 2. Energize motor (contactor or soft-starter) 3. Monitor current ramp (inrush → running steady ~70% rated) 4. Hold run state until stop command 5. De-energize on demand or on fault Fault Protection: - Current > nameplate × 1.2 for >5 sec → thermal fault - Current = 0 while running → loss of supply - Suction pressure < 0.5 bar → dry-run, stop motor ``` **Why This Matters:** - ✅ Prevents pump bearing damage from dry-running - ✅ Protects motor winding temperature - ✅ Reduces mechanical shock at startup - ✅ Automatic fault recovery capability --- ## 🏗️ Control Logic (Pseudocode) ```pascal PROGRAM Pump_Single_Control VAR (* ─── COMMAND INPUTS ─── *) Start_Command : BOOL := FALSE; Stop_Command : BOOL := FALSE; Remote_Mode : BOOL := TRUE; (* TRUE = PLC control, FALSE = local *) (* ─── FEEDBACK FROM MOTOR ─── *) Motor_Current : REAL; (* Amps from current transformer *) Motor_Temperature : REAL; (* °C from thermal overload relay *) Supply_Voltage_OK : BOOL := TRUE; (* 480V ±10% available *) (* ─── FEEDBACK FROM PUMP ─── *) Suction_Pressure : REAL; (* bar, inlet side *) Discharge_Pressure : REAL; (* bar, outlet side *) (* ─── SETTINGS ─── *) Nameplate_Current : REAL := 25.0; (* Amps, from motor nameplate *) Inrush_Current_Max : REAL := 75.0; (* 3× nameplate typical *) Overload_Threshold : REAL := 30.0; (* 1.2× nameplate *) Overload_Timeout_Sec : REAL := 5.0; (* Allow 5 sec inrush *) Low_Suction_Pressure : REAL := 0.5; (* bar, dry-run threshold *) Soft_Starter_Acceleration_Sec : REAL := 3.0; (* ─── STATE MACHINE ─── *) Pump_State : INT := 0; (* 0 = Stopped 1 = Starting (ramping) 2 = Running 3 = Fault (overload or dry-run) *) (* ─── RUN TIME & CYCLING ─── *) Pump_Runtime_Seconds : REAL := 0.0; Pump_Runtime_Hours : REAL := 0.0; Pump_Cycles : INT := 0; (* Count of start/stop cycles *) (* ─── FAULT HANDLING ─── *) Motor_Overload : BOOL := FALSE; Dry_Run_Condition : BOOL := FALSE; Supply_Lost : BOOL := FALSE; Motor_Fault : BOOL := FALSE; Last_Fault_Code : INT := 0; (* For diagnostics *) (* ─── TIMING ─── *) Inrush_Timer_Sec : REAL := 0.0; Overload_Duration_Sec : REAL := 0.0; Restart_Delay_Sec : REAL := 0.0; (* ─── OUTPUT COMMAND ─── *) Motor_Contactor_Coil : BOOL := FALSE; Soft_Starter_Reference : REAL := 0.0; (* 0-100% ramp *) (* ─── STATUS ─── *) Motor_Running : BOOL := FALSE; Ready_To_Start : BOOL := TRUE; END_VAR (* ═════════════════════════════════════════════════════════════ *) (* 1. SENSOR INPUTS & CONVERSIONS *) (* ═════════════════════════════════════════════════════════════ *) (* Motor current (from CT transformer, 5A secondary) *) Motor_Current := READ_ANALOG_INPUT(AI_MOTOR_CURRENT) / 100.0; (* 0-50A *) (* Suction pressure (pump inlet, measured in bar) *) Suction_Pressure := (READ_ANALOG_INPUT(AI_SUCTION) / 4095.0) * 10.0; (* 0-10 bar *) (* Discharge pressure *) Discharge_Pressure := (READ_ANALOG_INPUT(AI_DISCHARGE) / 4095.0) * 100.0; (* 0-100 bar *) (* ═════════════════════════════════════════════════════════════ *) (* 2. FAULT DETECTION LAYER *) (* ═════════════════════════════════════════════════════════════ *) (* Dry-run protection: stop motor if suction pressure too low *) IF Suction_Pressure < Low_Suction_Pressure AND Motor_Running THEN Dry_Run_Condition := TRUE; Motor_Fault := TRUE; Last_Fault_Code := 3; (* Dry-run code *) ELSE Dry_Run_Condition := FALSE; END_IF; (* Motor overload: too much current too long *) IF Motor_Current > Overload_Threshold THEN Overload_Duration_Sec := Overload_Duration_Sec + SCAN_TIME_SEC; IF Overload_Duration_Sec > Overload_Timeout_Sec THEN Motor_Overload := TRUE; Motor_Fault := TRUE; Last_Fault_Code := 1; (* Overload code *) END_IF; ELSE Overload_Duration_Sec := 0.0; Motor_Overload := FALSE; END_IF; (* Supply voltage loss *) IF NOT Supply_Voltage_OK AND Motor_Running THEN Supply_Lost := TRUE; Motor_Fault := TRUE; Last_Fault_Code := 2; (* Supply loss code *) ELSE Supply_Lost := FALSE; END_IF; (* ═════════════════════════════════════════════════════════════ *) (* 3. STATE MACHINE (Core Logic) *) (* ═════════════════════════════════════════════════════════════ *) CASE Pump_State OF (* ───────────────────── STATE 0: STOPPED ───────────────────── *) 0: Motor_Contactor_Coil := FALSE; Soft_Starter_Reference := 0.0; Motor_Running := FALSE; Overload_Duration_Sec := 0.0; Inrush_Timer_Sec := 0.0; (* Check if we can transition to starting *) IF Start_Command AND Remote_Mode AND Ready_To_Start THEN (* Pre-start checks *) IF Suction_Pressure >= Low_Suction_Pressure THEN (* Suction OK, safe to start *) Pump_State := 1; (* Go to STARTING *) Pump_Cycles := Pump_Cycles + 1; ALARM_STARTING := TRUE; ELSE (* Suction pressure too low *) ALARM_DRY_RUN_PROTECTION := TRUE; Ready_To_Start := FALSE; END_IF; END_IF; (* ───────────────────── STATE 1: STARTING ───────────────────── *) 1: (* Soft-starter ramp-up (0% → 100% over 3 seconds) *) Soft_Starter_Reference := (Inrush_Timer_Sec / Soft_Starter_Acceleration_Sec) * 100.0; Soft_Starter_Reference := MIN(100.0, Soft_Starter_Reference); Inrush_Timer_Sec := Inrush_Timer_Sec + SCAN_TIME_SEC; (* Check for faults during starting *) IF Motor_Fault THEN Pump_State := 3; (* Go to FAULT *) (* Ramp complete, transition to running *) ELSIF Inrush_Timer_Sec >= Soft_Starter_Acceleration_Sec THEN Motor_Contactor_Coil := TRUE; Motor_Running := TRUE; Pump_State := 2; (* Go to RUNNING *) ALARM_RUNNING := TRUE; END_IF; (* ───────────────────── STATE 2: RUNNING ───────────────────── *) 2: Motor_Contactor_Coil := TRUE; Soft_Starter_Reference := 100.0; (* Full speed *) Motor_Running := TRUE; (* Accumulate runtime *) Pump_Runtime_Seconds := Pump_Runtime_Seconds + SCAN_TIME_SEC; IF Pump_Runtime_Seconds >= 3600.0 THEN Pump_Runtime_Seconds := 0.0; Pump_Runtime_Hours := Pump_Runtime_Hours + 1.0; END_IF; (* Check for fault conditions *) IF Motor_Fault THEN Pump_State := 3; (* Go to FAULT *) (* Stop command *) ELSIF Stop_Command THEN Motor_Contactor_Coil := FALSE; Pump_State := 0; (* Go to STOPPED *) END_IF; (* ───────────────────── STATE 3: FAULT ───────────────────── *) 3: Motor_Contactor_Coil := FALSE; Soft_Starter_Reference := 0.0; Motor_Running := FALSE; (* Mandatory restart delay (30 seconds) *) Restart_Delay_Sec := Restart_Delay_Sec + SCAN_TIME_SEC; IF Restart_Delay_Sec > 30.0 THEN (* Conditions for auto-recovery *) IF NOT Motor_Fault AND Suction_Pressure >= Low_Suction_Pressure THEN Ready_To_Start := TRUE; Restart_Delay_Sec := 0.0; Pump_State := 0; (* Return to STOPPED, ready for restart *) END_IF; END_IF; (* Manual reset command *) IF (Reset_Fault_Command) THEN Motor_Fault := FALSE; Ready_To_Start := TRUE; Restart_Delay_Sec := 0.0; Pump_State := 0; END_IF; END_CASE; (* ═════════════════════════════════════════════════════════════ *) (* 4. OUTPUTS TO FIELD EQUIPMENT *) (* ═════════════════════════════════════════════════════════════ *) (* Motor contactor coil (outputs digital DO_MOTOR_CONTACTOR) *) WRITE_DIGITAL_OUTPUT(DO_MOTOR_CONTACTOR, Motor_Contactor_Coil); (* Soft-starter ramp command (outputs analog AO_SOFT_STARTER) *) WRITE_ANALOG_OUTPUT(AO_SOFT_STARTER, Soft_Starter_Reference); (* ═════════════════════════════════════════════════════════════ *) (* 5. ALARMS & STATUS LOGGING *) (* ═════════════════════════════════════════════════════════════ *) (* Map fault codes to messages *) IF Motor_Fault THEN CASE Last_Fault_Code OF 1: ALARM_TEXT := "Motor overload - current > threshold"; 2: ALARM_TEXT := "Supply voltage lost during run"; 3: ALARM_TEXT := "Dry-run condition detected (low suction)"; END_CASE; END_IF; END_PROGRAM ``` --- ## 🏷️ Tag List | Tag | Type | I/O | Range | Description | |-----|------|-----|-------|-------------| | `PUMP_01_START` | BOOL | Cmd | - | Start pump (rising edge) | | `PUMP_01_STOP` | BOOL | Cmd | - | Stop pump (any logic) | | `PUMP_01_RESET_FAULT` | BOOL | Cmd | - | Clear fault & allow restart | | `PUMP_01_RUNNING` | BOOL | Status | - | Motor contactor energized | | `PUMP_01_STATE` | INT | Status | 0-3 | State: 0=Stopped, 1=Starting, 2=Running, 3=Fault | | `PUMP_01_READY` | BOOL | Status | - | Ready to start (all checks pass) | | `PUMP_01_CURRENT` | REAL | Feedback | 0-100 A | Motor current draw | | `PUMP_01_CURRENT_NP` | REAL | Param | 5-400 A | Nameplate rated current | | `PUMP_01_TEMPERATURE` | REAL | Feedback | 0-120 °C | Motor winding temperature (if sensor) | | `PUMP_01_SUCTION_PRESSURE` | REAL | Feedback | 0-10 bar | Pump inlet pressure | | `PUMP_01_DISCHARGE_PRESSURE` | REAL | Feedback | 0-100 bar | Pump outlet pressure | | `PUMP_01_SUPPLY_OK` | BOOL | Status | - | 480V ±10% available | | `PUMP_01_FAULT` | BOOL | Alarm | - | ANY fault detected | | `PUMP_01_FAULT_CODE` | INT | Alarm | 0-3 | 0=OK, 1=Overload, 2=SupplyLoss, 3=DryRun | | `PUMP_01_RUNTIME_HOURS` | REAL | Metric | 0-99999 | Total cumulative hours | | `PUMP_01_RUNTIME_SECONDS` | REAL | Metric | 0-3600 | Seconds in current hour | | `PUMP_01_CYCLES` | INT | Metric | 0-999999 | Total start/stop cycles | | `PUMP_01_SOFT_START_RAMP` | REAL | Param | 1-30 sec | Acceleration time on startup | | `PUMP_01_OVERLOAD_TIMEOUT` | REAL | Param | 1-60 sec | How long to tolerate overcurrent | | `PUMP_01_DRY_RUN_THRESHOLD` | REAL | Param | 0-5 bar | Suction pressure cutoff | --- ## 🚨 Alarm & Trip Matrix | Alarm | Condition | Severity | Auto-Reset | |-------|-----------|----------|-----------| | **Motor Overload** | Current > Nameplate × 1.2 for >5 sec | Critical | Auto (after 30 sec cooldown) | | **Dry-Run Protection** | Suction pressure < 0.5 bar while running | Critical | Auto (when pressure recovers) | | **Supply Voltage Lost** | 480V dropped during run | Critical | Auto (manual reset recommended) | | **Soft-Starter Failure** | Ramp stuck at 50% for 10 sec | Critical | Manual | | **Contactor Stuck-On** | Can't de-energize despite command | Critical | Manual | | **Motor Temperature High** | Winding > 110°C (if RTD available) | Warning | Auto | | **Low Suction Pressure** | Below 0.5 bar during idle | Warning | Auto | | **High Discharge Pressure** | Exceeds line rating | Warning | Manual (check for blockage) | --- ## 📺 HMI Layout ``` ┌──────────────────────────────────────────┐ │ PUMP MOTOR CONTROL #1 │ ├──────────────────────────────────────────┤ │ │ │ Status: [RUNNING] 🟢 (2h 47m) │ │ │ │ Motor Current: 18.5A / 25A rated ✓ │ │ [████████░░░░░░░░░░] 74% │ │ │ │ Suction: 3.2 bar ✓ (Min: 0.5 bar) │ │ Discharge: 42.5 bar ✓ │ │ │ │ Soft-Start Ramp: Complete (100%) │ │ Cycles: 847 (avg 15 min each) │ │ Runtime: 210 hours total │ │ │ │ ┌────────────────────────────────┐ │ │ │ Quick Actions │ │ │ │ [STOP] [START] [RESET FAULT] │ │ │ └────────────────────────────────┘ │ │ │ │ Last Fault: None (7 days clean) │ │ │ │ Alerts: ○ None │ │ │ └──────────────────────────────────────────┘ ``` --- ## 🔧 Configuration Parameters ```json { "nameplate_current_amps": 25.0, "nameplate_voltage_volts": 480.0, "nameplate_power_kw": 18.5, "motor_pole_pairs": 2, "inrush_current_max_amps": 75.0, "overload_threshold_amps": 30.0, "overload_timeout_seconds": 5.0, "soft_starter_acceleration_seconds": 3.0, "dry_run_suction_threshold_bar": 0.5, "low_suction_alarm_bar": 1.0, "high_discharge_alarm_bar": 50.0, "restart_delay_after_fault_seconds": 30, "pump_type": "centrifugal", "pump_head_meters": 45, "pump_flow_m3_h": 120, "supply_voltage_acceptable_range_percent": 10 } ``` --- ## 📝 Implementation Checklist ### Before Deployment - [ ] **Motor nameplate** (verify current, voltage, power, cooling type) - [ ] **Current transformer (CT) verified** (5A secondary, burden <2VA) - [ ] **Soft-starter tested** (acceleration ramp smooth, no noise) - [ ] **Contactor tested** (pickup voltage <90V, dropout >75V) - [ ] **Suction line checked** (no air leaks, foot valve holding prime) - [ ] **Discharge line tested** (check for blockages or kinks) - [ ] **Grounding verified** (motor frame bonded to plant ground) ### During Commissioning 1. **Manual soft-start test**: - 0% ramp → verify no current - 25% ramp → motor hums (no full torque) - 50% ramp → motor torque increasing - 100% ramp → full speed (inrush settled to ~70% rated) 2. **Auto start/stop test**: - Remote mode ON - Issue START command - Monitor ramp over 3 seconds - Verify RUNNING bit sets at completion - Issue STOP command - Verify RUNNING clears immediately 3. **Current monitoring**: - At idle: ~70% nameplate (4-20mA: 14mA = 25A) - At 10% flow demand: ~50% nameplate - At 100% flow demand: ~100% nameplate 4. **Dry-run protection test**: - Close suction isolation valve (simulate dry-run) - Suction pressure drops - Verify pump stops within 5 seconds - Verify fault code = 3 (dry-run) 5. **Overload test**: - Close discharge valve (max back-pressure) - Current rises to 150% nameplate - Monitor timer (should count 0-5 seconds) - At 5 seconds: verify pump shuts down - Verify fault code = 1 (overload) --- ## 📊 Expected Performance | Metric | Target | Achievable | |--------|--------|-----------| | **Ramp time** | 3-5 sec | 3.0 sec (configurable) | | **Inrush current** | <3× nameplate | 2.8× nameplate typical | | **Dry-run detection** | <5 seconds | 1-3 seconds | | **Overload detection** | <5 seconds | 1-5 seconds | | **Start cycle overhead** | <60 sec total | 5-10 sec actual | | **Motor protection** | Zero burnouts | <1 per 10,000 hours | --- ## 🔄 Advanced Variations ### Dual Pump Redundancy Two identical pumps, either can supply demand (cross-check valves). → Use with Pump Lead/Lag for duty cycling ### Flow-Compensated Start If discharge pressure very high at startup, reduce ramp rate to avoid water hammer. ### Condition Monitoring Log vibration, temperature trends per cycle. → Predict bearing wear before failure ### Energy Optimization Monitor suction/discharge over time. If system aging (pressure rising for same flow), alert for impeller wear, seal leakage. --- **Production-ready single pump control for water, chemical, and oil/gas applications.**

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library