Multi Output Permissive Gate — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 36 views
# Multi Output Permissive Gate — Usage Guide
## Overview
Shared permissive template that fans a common safety and readiness gate to multiple downstream outputs. Useful where several actuators must only operate when the same safety conditions are true.
## Commissioning
1. Verify each common permissive input independently
2. Confirm all output requests drop immediately when the permissive is lost
3. Avoid using this template as a substitute for certified safety hardware where required by risk assessment
---
## Control Logic — Vendor-Agnostic Pseudocode
# Multi Output Permissive Gate — Logic
## Standards: IEC 61131-3 | IEC 61508
## Scan Rate: 10ms | Pattern: shared permissive fan-out to multiple outputs
```
ROUTINE: MultiOutputPermissiveGate
SCAN_RATE: 10ms
// SECTION 1 — COMMON PERMISSIVE
COMMON_PERMIT := MASTER_ENABLE AND NOT ESTOP_ACTIVE AND GUARD_CLOSED AND POWER_HEALTHY
// SECTION 2 — FAN-OUT
OUT1_CMD := REQ1 AND COMMON_PERMIT
OUT2_CMD := REQ2 AND COMMON_PERMIT
OUT3_CMD := REQ3 AND COMMON_PERMIT
OUT4_CMD := REQ4 AND COMMON_PERMIT
// SECTION 3 — ALARMS
IF NOT COMMON_PERMIT AND (REQ1 OR REQ2 OR REQ3 OR REQ4) THEN
SET_ALARM(ALM_PERMIT_LOST, HIGH)
END_IF
IF ESTOP_ACTIVE THEN SET_ALARM(ALM_ESTOP, CRITICAL) END_IF
// SECTION 4 — HMI
HMI_COMMON_PERMIT := COMMON_PERMIT
HMI_OUT1 := OUT1_CMD
HMI_OUT2 := OUT2_CMD
HMI_OUT3 := OUT3_CMD
HMI_OUT4 := OUT4_CMD
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
MASTER_ENABLE,Master Enable,BOOL,input,,,,FALSE,
ESTOP_ACTIVE,E-Stop Active,BOOL,input,,,,FALSE,DI:0:0.0
GUARD_CLOSED,Guard Closed Interlock,BOOL,input,,,,TRUE,DI:0:0.1
POWER_HEALTHY,Power Supply Healthy,BOOL,input,,,,TRUE,DI:0:0.2
REQ1,Output 1 Request,BOOL,input,,,,FALSE,
REQ2,Output 2 Request,BOOL,input,,,,FALSE,
REQ3,Output 3 Request,BOOL,input,,,,FALSE,
REQ4,Output 4 Request,BOOL,input,,,,FALSE,
COMMON_PERMIT,Common Permissive,BOOL,calculated,,,,FALSE,
OUT1_CMD,Output 1 Command,BOOL,output,,,,FALSE,DO:1:0.0
OUT2_CMD,Output 2 Command,BOOL,output,,,,FALSE,DO:1:0.1
OUT3_CMD,Output 3 Command,BOOL,output,,,,FALSE,DO:1:0.2
OUT4_CMD,Output 4 Command,BOOL,output,,,,FALSE,DO:1:0.3
ALM_PERMIT_LOST,Common Permit Lost Alarm,BOOL,calculated,,,,FALSE,
ALM_ESTOP,E-Stop Alarm,BOOL,calculated,,,,FALSE,
HMI_COMMON_PERMIT,HMI: Common Permit,BOOL,output,,,,FALSE,
HMI_OUT1,HMI: Output 1,BOOL,output,,,,FALSE,
HMI_OUT2,HMI: Output 2,BOOL,output,,,,FALSE,
HMI_OUT3,HMI: Output 3,BOOL,output,,,,FALSE,
HMI_OUT4,HMI: Output 4,BOOL,output,,,,FALSE,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_ESTOP,ESTOP_ACTIVE = TRUE,N/A,critical,safety,Emergency stop active. All gated outputs inhibited.,0s,No
ALM_PERMIT_LOST,Any output requested while COMMON_PERMIT = FALSE,N/A,high,safety,Output request blocked by lost permissive. Investigate interlocks before re-enabling.,0s,No
```