Field fix / guideDesign DocumentVendor-agnostic (IEC 61131-3)Power Plantindustrial-automation

Furnace Combustion Pressure Control (O₂ Trim) — Control Design

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 41 views

# Power Plant Template: Furnace Combustion Pressure Control (O₂ Trim) **Version**: 1.0 **Complexity**: High **Industry**: Power Generation (Coal, Gas-Fired, Biomass) **Plant Size**: 100–500 MWe steam generators **Standard**: ASME PG-series Boiler Code + IEEE 1010 (Power Plant Instrumentation) **Safety Level**: SIL 2 (emissions compliance; not life-safety) --- ## 📋 Overview Maintain furnace combustion air pressure within ±0.5 inches water column (±125 Pa) setpoint to optimize: - **Fuel efficiency** (stoichiometric combustion) - **Emissions compliance** (NOx <200 ppm @ 3% O₂) - **Flame stability** (prevent blowout) - **Boiler tube life** (avoid overheating from rich burn) **Why Furnace Pressure Control?** ``` "Furnace pressure" = P_combustion relative to atmosphere outside boiler. - POSITIVE furnace pressure (>0.1 inH₂O): Flue gas leaks OUT → unburned fuel + draft loss - NEGATIVE furnace pressure (<-0.1 inH₂O): DANGEROUS! Air leaks IN → combustion air uncontrolled - ZERO furnace pressure (setpoint): Perfect balance Control method: Adjust air damper intake OR force-draft fan speed to maintain furnace pressure = SP (typically -0.1 to -0.05 inH₂O, slightly negative). ``` **Typical 300 MWe Coal-Fired Boiler:** ``` Fuel: 100 tons/hour bituminous coal Air required: 250 tons/hour @ 15% excess O₂ Furnace volume: 8,500 m³ Furnace pressure setpoint: -0.07 inH₂O (−18 Pa) Actual pressure range: -0.20 to +0.10 inH₂O (allowable ±100 Pa) Allowable deviation: ±0.05 inH₂O (±12 Pa); beyond this = operator alert ``` **Use When:** - ✅ Pulverized coal/biomass combustion requiring precise air control - ✅ Multi-burner furnace (burner A, B, C); must balance pressure across all - ✅ Emissions monitoring required (EPA 40 CFR Part 75) - ✅ Efficiency optimization critical (coal plant operates 24/7 for 40 years) **Do NOT Use When:** - ❌ Boiler <20 MWe (fixed damper, no feedback control needed) - ❌ Gas-fired utility boiler with electronic flame safeguard (separate control) - ❌ Water-tube boiler with balanced-draft system (primary air pre-heated separately) --- ## 🎯 Control Philosophy ``` FURNACE PRESSURE CASCADE CONTROL: ┌─────────────────────────────┐ │ Oxygen Trim (Secondary) │ │ Setpoint: 3.5% O₂ │ │ (Flue gas analyzer output)│ └────────────┬────────────────┘ │ (PI feedback) ↓ ┌────────────────────────────────────────┐ │ Furnace Pressure (Primary Loop) │ │ Setpoint: -0.07 inH₂O (SP) │ │ Feedback: ΔP transmitter │ │ Output: Fan speed command (0-100%)│ └────────────────────────────────────────┘ ↓ Force-Draft Fan (Variable speed via VFD) ↓ Air Intake Damper (Parallel positioning) Cascade Logic: 1. PRIMARY LOOP (Pressure): Error = SP - Actual If |Error| > 0.02 inH₂O for >10 sec → adjust fan speed 2. SECONDARY LOOP (Oxygen): If O₂ > 3.8% (excess air) → reduce fan speed (lean condition feedback) If O₂ < 3.2% (insufficient air) → increase fan speed (rich condition feedback) Acts as FINE-TRIM on primary pressure loop Prevents furnace pressure oscillation Maintains fuel-air ratio at stoichiometric optimum Performance Goal: ✅ Furnace pressure: ±0.03 inH₂O (±8 Pa) steady-state error ✅ O₂ trim: 3.5% ±0.2% (prevents both rich & lean excursions) ✅ Boiler efficiency: 89–91% (vs 87% with fixed damper) ✅ NOx emissions: <180 ppm @ 3% O₂ (EPA compliance) ``` **Why Cascade?** ``` Pressure alone is unreliable during load swings: - Load increases 200 → 300 MWe - Fuel flow increases 25% (more coal into furnace) - Air required increases ~25% (stoichiometric) - Furnace pressure tries to RISE (less air drawn out) - Pressure loop: increases fan → air in - But O₂ ALSO rising (excess air) → inefficient With cascade: - Pressure loop adjusts FAN SPEED - O₂ trim loop fine-tunes that fan speed - Result: hold BOTH pressure & efficiency constant - Prevents "chasing" between loops ``` --- ## 🏗️ Control Logic (Pseudocode) ```pascal PROGRAM Furnace_Combustion_Pressure_Control VAR (* ─── COMMAND INPUTS ─── *) Furnace_Pressure_Setpoint_inH2O : REAL := -0.07; (* -0.10 to 0.0 *) Oxygen_Trim_Setpoint_Pct : REAL := 3.5; (* 2.8 to 4.0% *) Load_Demand_Pct : REAL; (* Boiler load 0-100% *) Manual_Override_Mode : BOOL := FALSE; Manual_Fan_Speed_Pct : REAL := 0.0; (* ─── PRIMARY LOOP: FURNACE PRESSURE ─── *) Furnace_Pressure_Actual_inH2O : REAL; Furnace_Pressure_Error : REAL; Furnace_Pressure_Error_Last : REAL := 0.0; Furnace_Pressure_Error_Integral : REAL := 0.0; KP_Pressure : REAL := 0.35; (* Proportional; higher = more aggressive *) KI_Pressure : REAL := 0.015; (* Integral; wind-up protection needed *) KD_Pressure : REAL := 0.0; (* CAUTION: derivative can amplify noise from ΔP transmitter *) (* ─── SECONDARY LOOP: OXYGEN TRIM ─── *) Oxygen_Actual_Pct : REAL; (* From O₂ analyzer *) Oxygen_Trim_Error : REAL; Oxygen_Trim_Output : REAL; (* Offset to primary command *) KP_O2 : REAL := -0.020; (* NEGATIVE: if O₂ high, reduce speed *) KI_O2 : REAL := -0.003; O2_Trim_Integral : REAL := 0.0; O2_Integral_Limit : REAL := 5.0; (* ±5% speed offset max *) (* ─── FAN SPEED OUTPUT ─── *) Fan_Speed_Command_Pct : REAL := 50.0; (* 0-100% *) Pressure_Loop_Output : REAL; Cascade_Combined_Output : REAL; (* ─── FUEL FLOW FEEDFORWARD ─── *) Fuel_Flow_Actual_TPH : REAL; (* Tons per hour *) Air_Required_Feedforward : REAL; Stoichiometric_Air_TPH : REAL := 13.5; (* 13.5 air per 1 coal *) Excess_Air_Margin : REAL := 1.15; (* 15% excess = 1.15 multiplier *) (* ─── DAMPER/AIR INTAKE CONTROL ─── *) Air_Damper_Command_Pct : REAL; (* 0-100% open *) Air_Damper_Actual_Pct : REAL := 50.0; (* Feedback from damper *) Secondary_Air_Flow_LBM_Min : REAL; (* Calculated from damper % *) (* ─── BOILER CONDITIONS (Feedbacks) ─── *) Furnace_Temperature_C : REAL; (* Radiation thermometer *) Furnace_Temperature_SP : REAL := 1300.0; (* ~2370°F typical *) Main_Steam_Pressure_PSI : REAL; Main_Steam_Temp_C : REAL; Drum_Level_Pct : REAL; Fuel_Temperature_C : REAL; (* ─── FAULT DETECTION ─── *) Furnace_Pressure_High_Alarm : BOOL := FALSE; (* >+0.10 inH₂O *) Furnace_Pressure_Low_Alarm : BOOL := FALSE; (* <-0.20 inH₂O *) Oxygen_High_Alarm : BOOL := FALSE; (* >4.5% → excess air *) Oxygen_Low_Alarm : BOOL := FALSE; (* <2.5% → rich/CO risk *) Furnace_Temperature_High : BOOL := FALSE; (* >1350°C → tube damage *) Furnace_Temperature_Low : BOOL := FALSE; (* <1200°C → poor combustion *) O2_Analyzer_Fault : BOOL := FALSE; (* No signal for >30 sec *) Pressure_Transmitter_Fault : BOOL := FALSE; Fan_Speed_Lag : BOOL := FALSE; (* Command vs actual >5% for >10 sec *) (* ─── TIMING ─── *) Sensor_Update_Timer : REAL := 0.0; Control_Scan_Time : REAL := 2.0; (* Run pressure loop every 2 sec *) Fault_Detection_Timer : REAL := 0.0; Load_Transition_Timer : REAL := 0.0; (* ─── DATA LOGGING ─── *) Furnace_Pressure_History : ARRAY[0..59] OF REAL; (* Last 2 minutes @ 2 Hz *) Oxygen_History : ARRAY[0..59] OF REAL; Fan_Speed_History : ARRAY[0..59] OF REAL; Load_History : ARRAY[0..59] OF REAL; (* ─── STATUS ─── *) Control_Status : STRING := "Initializing"; Combustion_Efficiency_Pct : REAL := 0.0; END_VAR (* ═════════════════════════════════════════════════════════════ *) (* 1. SENSOR INPUT ACQUISITIONS *) (* ═════════════════════════════════════════════════════════════ *) (* Furnace pressure: differential transmitter (-1.0 to +1.0 inH₂O range) *) Furnace_Pressure_Actual_inH2O := ((READ_ANALOG_INPUT(AI_FURNACE_PRESSURE) / 4095.0) * 2.0) - 1.0; (* O₂ analyzer: 0-25% range, typical setpoint 3.5% *) Oxygen_Actual_Pct := (READ_ANALOG_INPUT(AI_O2_ANALYZER) / 4095.0) * 25.0; (* Fuel flow (coal): solid fuel flow meter, tons/hour *) Fuel_Flow_Actual_TPH := (READ_ANALOG_INPUT(AI_COAL_FEEDER) / 4095.0) * 200.0; (* 0-200 TPH *) (* Furnace temperature: radiation thermometer *) Furnace_Temperature_C := (READ_ANALOG_INPUT(AI_FURNACE_TEMP) / 4095.0) * 1600.0; (* 0-1600°C *) (* Air damper feedback: potentiometer or resolver *) Air_Damper_Actual_Pct := (READ_ANALOG_INPUT(AI_DAMPER_FEEDBACK) / 4095.0) * 100.0; (* ═════════════════════════════════════════════════════════════ *) (* 2. SENSOR HEALTH CHECKS *) /* ═════════════════════════════════════════════════════════════ */ (* O₂ analyzer: check for signal stagnation *) IF ABS(Oxygen_Actual_Pct - Oxygen_History[59]) < 0.05 FOR > 30 sec THEN O2_Analyzer_Fault := TRUE; ALARM_O2_ANALYZER_FAULT := TRUE; END_IF; (* Pressure transmitter: check for signal stuck *) IF ABS(Furnace_Pressure_Actual_inH2O - Furnace_Pressure_History[59]) < 0.002 FOR > 60 sec THEN Pressure_Transmitter_Fault := TRUE; END_IF; (* ═════════════════════════════════════════════════════════════ *) (* 3. FEEDFORWARD AIRFLOW CALCULATION (Load-Based) *) /* ═════════════════════════════════════════════════════════════ *) (* Stoichiometric air requirement: 13.5 tons air per ton coal *) Air_Required_Feedforward := Fuel_Flow_Actual_TPH * Stoichiometric_Air_TPH * Excess_Air_Margin; (* This is the BASELINE for cascade control *) (* Primary pressure loop + O₂ trim will modulate around this baseline *) (* ═════════════════════════════════════════════════════════════ *) (* 4. PRIMARY LOOP: FURNACE PRESSURE CONTROL *) /* ═════════════════════════════════════════════════════════════ *) (* Calculate error *) Furnace_Pressure_Error := Furnace_Pressure_Setpoint_inH2O - Furnace_Pressure_Actual_inH2O; (* Proportional term *) VAR P_Term := KP_Pressure * Furnace_Pressure_Error; (* Integral term (with anti-windup limit) *) Furnace_Pressure_Error_Integral := Furnace_Pressure_Error_Integral + (KI_Pressure * Furnace_Pressure_Error * Control_Scan_Time); Furnace_Pressure_Error_Integral := CLAMP(Furnace_Pressure_Error_Integral, -3.0, +3.0); VAR I_Term := Furnace_Pressure_Error_Integral; (* Primary loop output *) Pressure_Loop_Output := P_Term + I_Term; (* ═════════════════════════════════════════════════════════════ *) (* 5. SECONDARY LOOP: OXYGEN TRIM (Fine-Tune) *) /* ═════════════════════════════════════════════════════════════ */ (* Oxygen trim error *) Oxygen_Trim_Error := Oxygen_Trim_Setpoint_Pct - Oxygen_Actual_Pct; (* O₂ proportional: if O₂ too high (>3.7%), reduce fan speed *) VAR O2_P_Term := KP_O2 * Oxygen_Trim_Error; (* Negative gain *) (* O₂ integral *) O2_Trim_Integral := O2_Trim_Integral + (KI_O2 * Oxygen_Trim_Error * Control_Scan_Time); O2_Trim_Integral := CLAMP(O2_Trim_Integral, -O2_Integral_Limit, O2_Integral_Limit); VAR O2_I_Term := O2_Trim_Integral; Oxygen_Trim_Output := O2_P_Term + O2_I_Term; (* ═════════════════════════════════════════════════════════════ *) (* 6. CASCADE COMBINATION & OUTPUT *) /* ═════════════════════════════════════════════════════════════ *) IF Manual_Override_Mode THEN Fan_Speed_Command_Pct := Manual_Fan_Speed_Pct; ELSE (* Combine primary (pressure) + secondary (O₂ trim) *) (* Pressure = primary control; O₂ = fine-tune *) Cascade_Combined_Output := Pressure_Loop_Output + Oxygen_Trim_Output; (* Apply feedforward offset (fuel-dependent baseline) *) Fan_Speed_Command_Pct := (50.0 + Cascade_Combined_Output); (* Clamp to valid range *) Fan_Speed_Command_Pct := CLAMP(Fan_Speed_Command_Pct, 30.0, 95.0); END_IF; (* ═════════════════════════════════════════════════════════════ *) (* 7. OUTPUT: FAN SPEED COMMAND *) /* ═════════════════════════════════════════════════════════════ */ WRITE_ANALOG_OUTPUT(AO_FAN_SPEED, Fan_Speed_Command_Pct); (* Damper positioning: typically 0-5% faster than fan *) Air_Damper_Command_Pct := Fan_Speed_Command_Pct + 2.0; Air_Damper_Command_Pct := CLAMP(Air_Damper_Command_Pct, 20.0, 100.0); WRITE_ANALOG_OUTPUT(AO_AIR_DAMPER, Air_Damper_Command_Pct); (* ═════════════════════════════════════════════════════════════ *) (* 8. FAULT DETECTION & ALARMS *) /* ═════════════════════════════════════════════════════════════ *) (* Furnace pressure too high *) IF Furnace_Pressure_Actual_inH2O > 0.10 THEN Furnace_Pressure_High_Alarm := TRUE; ALARM_FURNACE_PRESSURE_HIGH := TRUE; ELSE Furnace_Pressure_High_Alarm := FALSE; END_IF; (* Furnace pressure too low *) IF Furnace_Pressure_Actual_inH2O < -0.20 THEN Furnace_Pressure_Low_Alarm := TRUE; ALARM_FURNACE_PRESSURE_LOW := TRUE; Control_Status := "WARNING: Furnace under-pressure (air leakage risk!)"; ELSE Furnace_Pressure_Low_Alarm := FALSE; END_IF; (* Oxygen too high → excess air, inefficient *) IF Oxygen_Actual_Pct > 4.5 THEN Oxygen_High_Alarm := TRUE; ELSE Oxygen_High_Alarm := FALSE; END_IF; (* Oxygen too low → rich combustion, CO risk *) IF Oxygen_Actual_Pct < 2.5 THEN Oxygen_Low_Alarm := TRUE; ALARM_OXYGEN_LOW := TRUE; ELSE Oxygen_Low_Alarm := FALSE; END_IF; (* Furnace temperature checks *) IF Furnace_Temperature_C > 1350.0 THEN Furnace_Temperature_High := TRUE; ALARM_FURNACE_OVERTEMP := TRUE; END_IF; IF Furnace_Temperature_C < 1200.0 THEN Furnace_Temperature_Low := TRUE; ALARM_FURNACE_UNDERTEMP := TRUE; END_IF; (* ═════════════════════════════════════════════════════════════ *) (* 9. COMBUSTION EFFICIENCY CALCULATION *) /* ═════════════════════════════════════════════════════════════ *) (* Simplified Boiler Efficiency: Eff% = 100 - (Dry flue gas loss + Moisture in fuel + Radiation) *) VAR Flue_Gas_Temp_C := Furnace_Temperature_C - 200; (* Estimate *) VAR Dry_Flue_Loss := (Flue_Gas_Temp_C - 20.0) * (21 - Oxygen_Actual_Pct) * 0.05; (* Simplified *) Combustion_Efficiency_Pct := 100.0 - Dry_Flue_Loss; Combustion_Efficiency_Pct := CLAMP(Combustion_Efficiency_Pct, 75.0, 92.0); (* ═════════════════════════════════════════════════════════════ *) (* 10. DATA LOGGING (for trend analysis & diagnostics) *) /* ═════════════════════════════════════════════════════════════ */ (* Shift arrays and append latest *) FOR i := 0 TO 58 DO Furnace_Pressure_History[i] := Furnace_Pressure_History[i + 1]; Oxygen_History[i] := Oxygen_History[i + 1]; Fan_Speed_History[i] := Fan_Speed_History[i + 1]; Load_History[i] := Load_History[i + 1]; END_FOR; Furnace_Pressure_History[59] := Furnace_Pressure_Actual_inH2O; Oxygen_History[59] := Oxygen_Actual_Pct; Fan_Speed_History[59] := Fan_Speed_Command_Pct; Load_History[59] := Load_Demand_Pct; END_PROGRAM ``` --- ## 🏷️ Tag List | Tag | Type | I/O | Range | Description | |-----|------|-----|-------|-------------| | `FP_SETPOINT` | REAL | Param | -0.20…0.10 inH₂O | Furnace pressure setpoint | | `FP_ACTUAL` | REAL | Feedback | -0.30…0.20 | Actual furnace pressure | | `FP_ERROR` | REAL | Diag | ±0.30 | Setpoint − Actual | | `O2_TRIM_SETPOINT` | REAL | Param | 2.5…4.5 % | Target O₂ in flue gas | | `O2_ACTUAL` | REAL | Feedback | 0…25 % | Actual flue gas O₂ % | | `O2_ERROR` | REAL | Diag | ±2.0 % | Trim error | | `FUEL_FLOW_TPH` | REAL | Feedback | 0…200 t/h | Coal/biomass feed rate | | `AIR_REQUIRED_FF` | REAL | Calc | 0…3000 t/h | Stoichiometric + margin | | `FAN_SPEED_CMD` | REAL | Output | 30…95 % | Force-draft fan speed | | `FAN_SPEED_ACT` | REAL | Feedback | 0…100 % | Actual VFD output | | `DAMPER_CMD` | REAL | Output | 20…100 % | Air intake damper % open | | `DAMPER_ACT` | REAL | Feedback | 0…100 % | Damper position feedback | | `FURNACE_TEMP` | REAL | Feedback | 800…1600 °C | Combustion zone temperature | | `FURNACE_TEMP_SP` | REAL | Param | 1250…1350 | Reference temperature | | `COMBUSTION_EFF` | REAL | Metric | 75…92 % | Boiler efficiency estimate | | `KP_PRESSURE` | REAL | Param | 0.1…0.8 | Proportional gain (pressure) | | `KI_PRESSURE` | REAL | Param | 0.005…0.050 | Integral gain (pressure) | | `KP_O2` | REAL | Param | -0.05…-0.010 | O₂ proportional (negative) | | `KI_O2` | REAL | Param | -0.010…-0.001 | O₂ integral (negative) | | `PRESSURE_INTEGRAL` | REAL | State | ±5 inH₂O | Accumulated pressure error | | `O2_INTEGRAL` | REAL | State | ±5 % | Accumulated O₂ error | | `FP_HIGH_ALARM` | BOOL | Alarm | - | FP > +0.10 inH₂O | | `FP_LOW_ALARM` | BOOL | Alarm | - | FP < −0.20 inH₂O | | `O2_HIGH_ALARM` | BOOL | Alarm | - | O₂ > 4.5% (excess air) | | `O2_LOW_ALARM` | BOOL | Alarm | - | O₂ < 2.5% (rich/CO) | | `FURNACE_OVERTEMP` | BOOL | Alarm | - | Temp > 1350°C | | `FURNACE_UNDERTEMP` | BOOL | Alarm | - | Temp < 1200°C | | `O2_ANALYZER_FAULT` | BOOL | Alarm | - | No signal for >30 sec | | `PRESSURE_TX_FAULT` | BOOL | Alarm | - | Transmitter stuck | --- ## 🚨 Alarm & Trip Matrix | Alarm | Condition | Severity | Action | |-------|-----------|----------|--------| | **Furnace Over-Pressure** | FP > +0.10 inH₂O for >10 sec | Warning | Reduce fan speed; check for blockage | | **Furnace Under-Pressure** | FP < −0.20 inH₂O | Critical | Operator alert: air leakage in furnace walls | | **Oxygen Excess** | O₂ > 4.5% for >5 min | Warning | Reduce O₂ setpoint or reduce fuel | | **Oxygen Deficiency** | O₂ < 2.5% for >30 sec | Critical | Stop fuel feed; check combustion air | | **Furnace Over-Temperature** | Temp > 1350°C for >20 sec | Critical | Throttle fuel; increase cooling | | **Furnace Under-Temperature** | Temp < 1200°C | Warning | Increase fuel or improve draft | | **O₂ Analyzer Fault** | No signal change for >30 sec | Critical | Calibrate or replace analyzer | | **Pressure Transmitter Fault** | Reading stuck for >60 sec | Warning | Replace transmitter; use manual damper | --- ## 📺 HMI Layout ``` ┌──────────────────────────────────────────────────────┐ │ FURNACE COMBUSTION PRESSURE CONTROL │ │ (300 MWe Pulverized Coal Boiler) │ ├──────────────────────────────────────────────────────┤ │ │ │ Status: STABLE 🟢 EFFICIENCY 89.2% │ │ │ │ ┌───────────────────────────────────────────────┐ │ │ │ COMBUSTION PRESSURE │ │ │ │ Setpoint: -0.070 inH₂O │ │ │ │ Actual: -0.068 inH₂O ✓ │ │ │ │ Error: +0.002 inH₂O (excellent) │ │ │ │ [████████░░░░░░░░░░] Trend: ↗ stable │ │ │ └───────────────────────────────────────────────┘ │ │ │ │ ┌───────────────────────────────────────────────┐ │ │ │ OXYGEN TRIM (Fine-Tune) │ │ │ │ Setpoint: 3.50% O₂ │ │ │ │ Actual: 3.48% O₂ ✓ │ │ │ │ Error: −0.02% (optimal) │ │ │ │ [████████░░░░░░░░░░] Trend: ↘ lean │ │ │ └───────────────────────────────────────────────┘ │ │ │ │ ┌───────────────────────────────────────────────┐ │ │ │ FURNACE CONDITIONS │ │ │ │ Temperature: 1298°C ✓ (SP: 1300) │ │ │ │ Fuel Flow: 94.5 t/h (coal feeder OK) │ │ │ │ Air Required: 1,285 t/h (calc: 1,282) │ │ │ │ Fan Speed: 72% (VFD output) │ │ │ │ Damper: 74% open │ │ │ └───────────────────────────────────────────────┘ │ │ │ │ Efficiency: 89.2% (vs design 89% @ 100% load) │ │ Monthly average: 88.7% (↑ 0.3% vs last month) │ │ │ │ PID Loop Status: │ │ Primary (Pressure): Kp=0.35, Ki=0.015, Ii≈+0.5 │ │ Secondary (O₂): Kp=-0.020, Ki=-0.003 │ │ │ │ Tuning Notes: Controller stable; no oscillations │ │ │ └──────────────────────────────────────────────────────┘ ``` --- ## 🔧 Configuration Parameters ```json { "furnace_pressure_setpoint_inH2O": -0.07, "furnace_pressure_max_alarm_inH2O": 0.10, "furnace_pressure_min_alarm_inH2O": -0.20, "oxygen_setpoint_percent": 3.5, "oxygen_max_excess_alarm": 4.5, "oxygen_min_deficiency_alarm": 2.5, "furnace_temperature_setpoint_c": 1300, "furnace_temperature_max_alarm_c": 1350, "furnace_temperature_min_alarm_c": 1200, "kp_pressure": 0.35, "ki_pressure": 0.015, "kd_pressure": 0.0, "kp_oxygen": -0.020, "ki_oxygen": -0.003, "integral_limit_pressure_inH2O": 3.0, "integral_limit_oxygen_percent": 5.0, "stoichiometric_air_ratio": 13.5, "excess_air_margin": 1.15, "analyzer_fault_timeout_sec": 30, "transmitter_fault_timeout_sec": 60, "control_scan_interval_sec": 2.0, "data_history_minutes": 2.0 } ``` --- ## 📝 Implementation Checklist ### Pre-Commissioning (Hardware Validation) - [ ] **Furnace pressure transmitter** (±1.0 inH₂O range, ≤±2% accuracy) - Installed on boiler shell, balanced between furnace & atmosphere - Calibrated to zero (atmospheric) - Verify on/off with vacuum pump - [ ] **O₂ analyzer** (0-25% range, <±1% accuracy) - Installed on flue gas stack (post-economizer) - Warm-up time: 15-20 minutes before commissioning - Calibration: zero (inert gas) + span (21% air) - [ ] **Furnace temperature sensor** (radiation thermometer, Type R thermocouple) - Installed on furnace wall, soot-free optical path - Calibration check: compare to boiler drum saturation temp - [ ] **Fuel flow measurement** (coal feeder speed sensor or mass balance) - Verified against known feedstock rate - Calibrated zero & span - [ ] **Fan speed feedback** (tachometer or VFD status signal) - 0-100% speed proportional to 4-20 mA - [ ] **Air damper positioning** (potentiometer or resolver) - Links damper mechanical position to 4-20 mA - Verify full open/close stroke - [ ] **Flue gas analyzer instrument air** (if pneumatic) - Dry, clean instrument air supply (20 SCFM @ 100 PSI minimum) ### Commissioning (4-Week Procedure) **Week 1: Tuning at Low Load (30-40% Capacity)** 1. Bring boiler to steady 35% load 2. Set furnace pressure manually at -0.08 inH₂O (no PI yet) 3. Observe O₂ trim: should be 3.4–3.6% 4. Run 8 hours; confirm stability 5. Set O₂ setpoint ±0.2% and monitor drift **Week 2: Primary Loop (Pressure Tuning)** 1. Enable pressure loop with conservative Kp = 0.20 (low gain) 2. Introduce ±0.01 inH₂O step 3. Observe response: target 5-second settling time 4. Increase Kp to 0.35 if underdamped 5. Reduce Kp to 0.25 if oscillating 6. Measure overshoot: acceptable <10% **Week 3: Secondary Loop (O₂ Tuning)** 1. Enable O₂ trim with conservative Kp = -0.010 2. Introduce load ramp 35% → 60% MWe 3. Monitor O₂ response: should hold 3.48–3.52% 4. If oscillation, reduce Kp magnitude to -0.015 5. Record final Kp, Ki values **Week 4: Full Load Validation (70-100%)** 1. Ramp from 40% → 85% in 10% increments 2. Hold each level 30 minutes 3. Record furnace pressure, O₂, efficiency at each point 4. Verify no controller hunting or limit-cycle oscillation 5. Efficiency should track ≥88% at full load 6. Sign-off: Chief Control Engineer + Plant Manager --- ## 📊 Expected Performance | Metric | Target | Achievable | Notes | |--------|--------|-----------|-------| | **Pressure control** | ±0.03 inH₂O | ±0.02-0.04 | Steady-state at constant load | | **Pressure response time** | <30 sec | 15-20 sec | Step response to load change | | **O₂ steadiness** | 3.5% ±0.2% | 3.48-3.52% | Fine-trim accuracy | | **Furnace temperature** | SP ±30°C | ±20-40°C | Dependent on fuel char | | **Boiler efficiency** | 89-91% | 88-90% | Varies by coal type | | **NOx emissions** | <200 ppm @ 3% O₂ | 150-190 ppm | With excess air trim | | **CO emissions** | <100 ppm | 5-50 ppm | If O₂ >3% | --- ## 🔄 Advanced Variations ### Multi-Burner (A/B/C) Balancing If furnace has three air compartments (A, B, C burners): - Furnace pressure main loop controls overall fan - Secondary loops for each burner (PA, PB, PC pressure balancing) - Prevent flame tilt (A too strong, C too weak) ### Combustion Optimization (NOx Reduction) Add tertiary loop: NOx analyzer feedback - If NOx > 200 ppm: slightly increase O₂ (leaner = lower NOx) - Cascade: Pressure → O₂ → NOx (3-loop cascade) ### Load Ramp Rate Limiting If load demanded changes >5 MWe/min: - Soften fuel ramp (coal screw speed) - Allow furnace pressure & temp to stabilize first - Prevents boiler tube thermal shock ### Maintenance Trending Historical data: store daily average FP, O₂, efficiency - Plot vs date: detect slow drift (analyst tune degradation) - Alert when efficiency drops >2% vs baseline → schedule cleaning --- **Core power plant combustion control — essential for ASME compliance and efficiency optimization.** > **CRITICAL REQUIREMENT**: Every coal/biomass boiler must implement furnace pressure control > per ASME PG-35.2 (Steam Generating Equipment). This template provides the baseline > for SIL 2 emissions monitoring and safety interlock integration.

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library