Furnace Combustion Pressure Control (O₂ Trim) — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 41 views
# Power Plant Template: Furnace Combustion Pressure Control (O₂ Trim)
**Version**: 1.0
**Complexity**: High
**Industry**: Power Generation (Coal, Gas-Fired, Biomass)
**Plant Size**: 100–500 MWe steam generators
**Standard**: ASME PG-series Boiler Code + IEEE 1010 (Power Plant Instrumentation)
**Safety Level**: SIL 2 (emissions compliance; not life-safety)
---
## 📋 Overview
Maintain furnace combustion air pressure within ±0.5 inches water column (±125 Pa) setpoint
to optimize:
- **Fuel efficiency** (stoichiometric combustion)
- **Emissions compliance** (NOx <200 ppm @ 3% O₂)
- **Flame stability** (prevent blowout)
- **Boiler tube life** (avoid overheating from rich burn)
**Why Furnace Pressure Control?**
```
"Furnace pressure" = P_combustion relative to atmosphere outside boiler.
- POSITIVE furnace pressure (>0.1 inH₂O): Flue gas leaks OUT → unburned fuel + draft loss
- NEGATIVE furnace pressure (<-0.1 inH₂O): DANGEROUS! Air leaks IN → combustion air uncontrolled
- ZERO furnace pressure (setpoint): Perfect balance
Control method: Adjust air damper intake OR force-draft fan speed
to maintain furnace pressure = SP (typically -0.1 to -0.05 inH₂O, slightly negative).
```
**Typical 300 MWe Coal-Fired Boiler:**
```
Fuel: 100 tons/hour bituminous coal
Air required: 250 tons/hour @ 15% excess O₂
Furnace volume: 8,500 m³
Furnace pressure setpoint: -0.07 inH₂O (−18 Pa)
Actual pressure range: -0.20 to +0.10 inH₂O (allowable ±100 Pa)
Allowable deviation: ±0.05 inH₂O (±12 Pa); beyond this = operator alert
```
**Use When:**
- ✅ Pulverized coal/biomass combustion requiring precise air control
- ✅ Multi-burner furnace (burner A, B, C); must balance pressure across all
- ✅ Emissions monitoring required (EPA 40 CFR Part 75)
- ✅ Efficiency optimization critical (coal plant operates 24/7 for 40 years)
**Do NOT Use When:**
- ❌ Boiler <20 MWe (fixed damper, no feedback control needed)
- ❌ Gas-fired utility boiler with electronic flame safeguard (separate control)
- ❌ Water-tube boiler with balanced-draft system (primary air pre-heated separately)
---
## 🎯 Control Philosophy
```
FURNACE PRESSURE CASCADE CONTROL:
┌─────────────────────────────┐
│ Oxygen Trim (Secondary) │
│ Setpoint: 3.5% O₂ │
│ (Flue gas analyzer output)│
└────────────┬────────────────┘
│ (PI feedback)
↓
┌────────────────────────────────────────┐
│ Furnace Pressure (Primary Loop) │
│ Setpoint: -0.07 inH₂O (SP) │
│ Feedback: ΔP transmitter │
│ Output: Fan speed command (0-100%)│
└────────────────────────────────────────┘
↓
Force-Draft Fan
(Variable speed via VFD)
↓
Air Intake Damper
(Parallel positioning)
Cascade Logic:
1. PRIMARY LOOP (Pressure):
Error = SP - Actual
If |Error| > 0.02 inH₂O for >10 sec → adjust fan speed
2. SECONDARY LOOP (Oxygen):
If O₂ > 3.8% (excess air) → reduce fan speed (lean condition feedback)
If O₂ < 3.2% (insufficient air) → increase fan speed (rich condition feedback)
Acts as FINE-TRIM on primary pressure loop
Prevents furnace pressure oscillation
Maintains fuel-air ratio at stoichiometric optimum
Performance Goal:
✅ Furnace pressure: ±0.03 inH₂O (±8 Pa) steady-state error
✅ O₂ trim: 3.5% ±0.2% (prevents both rich & lean excursions)
✅ Boiler efficiency: 89–91% (vs 87% with fixed damper)
✅ NOx emissions: <180 ppm @ 3% O₂ (EPA compliance)
```
**Why Cascade?**
```
Pressure alone is unreliable during load swings:
- Load increases 200 → 300 MWe
- Fuel flow increases 25% (more coal into furnace)
- Air required increases ~25% (stoichiometric)
- Furnace pressure tries to RISE (less air drawn out)
- Pressure loop: increases fan → air in
- But O₂ ALSO rising (excess air) → inefficient
With cascade:
- Pressure loop adjusts FAN SPEED
- O₂ trim loop fine-tunes that fan speed
- Result: hold BOTH pressure & efficiency constant
- Prevents "chasing" between loops
```
---
## 🏗️ Control Logic (Pseudocode)
```pascal
PROGRAM Furnace_Combustion_Pressure_Control
VAR
(* ─── COMMAND INPUTS ─── *)
Furnace_Pressure_Setpoint_inH2O : REAL := -0.07; (* -0.10 to 0.0 *)
Oxygen_Trim_Setpoint_Pct : REAL := 3.5; (* 2.8 to 4.0% *)
Load_Demand_Pct : REAL; (* Boiler load 0-100% *)
Manual_Override_Mode : BOOL := FALSE;
Manual_Fan_Speed_Pct : REAL := 0.0;
(* ─── PRIMARY LOOP: FURNACE PRESSURE ─── *)
Furnace_Pressure_Actual_inH2O : REAL;
Furnace_Pressure_Error : REAL;
Furnace_Pressure_Error_Last : REAL := 0.0;
Furnace_Pressure_Error_Integral : REAL := 0.0;
KP_Pressure : REAL := 0.35; (* Proportional; higher = more aggressive *)
KI_Pressure : REAL := 0.015; (* Integral; wind-up protection needed *)
KD_Pressure : REAL := 0.0; (* CAUTION: derivative can amplify noise from ΔP transmitter *)
(* ─── SECONDARY LOOP: OXYGEN TRIM ─── *)
Oxygen_Actual_Pct : REAL; (* From O₂ analyzer *)
Oxygen_Trim_Error : REAL;
Oxygen_Trim_Output : REAL; (* Offset to primary command *)
KP_O2 : REAL := -0.020; (* NEGATIVE: if O₂ high, reduce speed *)
KI_O2 : REAL := -0.003;
O2_Trim_Integral : REAL := 0.0;
O2_Integral_Limit : REAL := 5.0; (* ±5% speed offset max *)
(* ─── FAN SPEED OUTPUT ─── *)
Fan_Speed_Command_Pct : REAL := 50.0; (* 0-100% *)
Pressure_Loop_Output : REAL;
Cascade_Combined_Output : REAL;
(* ─── FUEL FLOW FEEDFORWARD ─── *)
Fuel_Flow_Actual_TPH : REAL; (* Tons per hour *)
Air_Required_Feedforward : REAL;
Stoichiometric_Air_TPH : REAL := 13.5; (* 13.5 air per 1 coal *)
Excess_Air_Margin : REAL := 1.15; (* 15% excess = 1.15 multiplier *)
(* ─── DAMPER/AIR INTAKE CONTROL ─── *)
Air_Damper_Command_Pct : REAL; (* 0-100% open *)
Air_Damper_Actual_Pct : REAL := 50.0; (* Feedback from damper *)
Secondary_Air_Flow_LBM_Min : REAL; (* Calculated from damper % *)
(* ─── BOILER CONDITIONS (Feedbacks) ─── *)
Furnace_Temperature_C : REAL; (* Radiation thermometer *)
Furnace_Temperature_SP : REAL := 1300.0; (* ~2370°F typical *)
Main_Steam_Pressure_PSI : REAL;
Main_Steam_Temp_C : REAL;
Drum_Level_Pct : REAL;
Fuel_Temperature_C : REAL;
(* ─── FAULT DETECTION ─── *)
Furnace_Pressure_High_Alarm : BOOL := FALSE; (* >+0.10 inH₂O *)
Furnace_Pressure_Low_Alarm : BOOL := FALSE; (* <-0.20 inH₂O *)
Oxygen_High_Alarm : BOOL := FALSE; (* >4.5% → excess air *)
Oxygen_Low_Alarm : BOOL := FALSE; (* <2.5% → rich/CO risk *)
Furnace_Temperature_High : BOOL := FALSE; (* >1350°C → tube damage *)
Furnace_Temperature_Low : BOOL := FALSE; (* <1200°C → poor combustion *)
O2_Analyzer_Fault : BOOL := FALSE; (* No signal for >30 sec *)
Pressure_Transmitter_Fault : BOOL := FALSE;
Fan_Speed_Lag : BOOL := FALSE; (* Command vs actual >5% for >10 sec *)
(* ─── TIMING ─── *)
Sensor_Update_Timer : REAL := 0.0;
Control_Scan_Time : REAL := 2.0; (* Run pressure loop every 2 sec *)
Fault_Detection_Timer : REAL := 0.0;
Load_Transition_Timer : REAL := 0.0;
(* ─── DATA LOGGING ─── *)
Furnace_Pressure_History : ARRAY[0..59] OF REAL; (* Last 2 minutes @ 2 Hz *)
Oxygen_History : ARRAY[0..59] OF REAL;
Fan_Speed_History : ARRAY[0..59] OF REAL;
Load_History : ARRAY[0..59] OF REAL;
(* ─── STATUS ─── *)
Control_Status : STRING := "Initializing";
Combustion_Efficiency_Pct : REAL := 0.0;
END_VAR
(* ═════════════════════════════════════════════════════════════ *)
(* 1. SENSOR INPUT ACQUISITIONS *)
(* ═════════════════════════════════════════════════════════════ *)
(* Furnace pressure: differential transmitter (-1.0 to +1.0 inH₂O range) *)
Furnace_Pressure_Actual_inH2O :=
((READ_ANALOG_INPUT(AI_FURNACE_PRESSURE) / 4095.0) * 2.0) - 1.0;
(* O₂ analyzer: 0-25% range, typical setpoint 3.5% *)
Oxygen_Actual_Pct :=
(READ_ANALOG_INPUT(AI_O2_ANALYZER) / 4095.0) * 25.0;
(* Fuel flow (coal): solid fuel flow meter, tons/hour *)
Fuel_Flow_Actual_TPH :=
(READ_ANALOG_INPUT(AI_COAL_FEEDER) / 4095.0) * 200.0; (* 0-200 TPH *)
(* Furnace temperature: radiation thermometer *)
Furnace_Temperature_C :=
(READ_ANALOG_INPUT(AI_FURNACE_TEMP) / 4095.0) * 1600.0; (* 0-1600°C *)
(* Air damper feedback: potentiometer or resolver *)
Air_Damper_Actual_Pct :=
(READ_ANALOG_INPUT(AI_DAMPER_FEEDBACK) / 4095.0) * 100.0;
(* ═════════════════════════════════════════════════════════════ *)
(* 2. SENSOR HEALTH CHECKS *)
/* ═════════════════════════════════════════════════════════════ */
(* O₂ analyzer: check for signal stagnation *)
IF ABS(Oxygen_Actual_Pct - Oxygen_History[59]) < 0.05 FOR > 30 sec THEN
O2_Analyzer_Fault := TRUE;
ALARM_O2_ANALYZER_FAULT := TRUE;
END_IF;
(* Pressure transmitter: check for signal stuck *)
IF ABS(Furnace_Pressure_Actual_inH2O - Furnace_Pressure_History[59]) < 0.002 FOR > 60 sec THEN
Pressure_Transmitter_Fault := TRUE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 3. FEEDFORWARD AIRFLOW CALCULATION (Load-Based) *)
/* ═════════════════════════════════════════════════════════════ *)
(* Stoichiometric air requirement: 13.5 tons air per ton coal *)
Air_Required_Feedforward := Fuel_Flow_Actual_TPH * Stoichiometric_Air_TPH * Excess_Air_Margin;
(* This is the BASELINE for cascade control *)
(* Primary pressure loop + O₂ trim will modulate around this baseline *)
(* ═════════════════════════════════════════════════════════════ *)
(* 4. PRIMARY LOOP: FURNACE PRESSURE CONTROL *)
/* ═════════════════════════════════════════════════════════════ *)
(* Calculate error *)
Furnace_Pressure_Error := Furnace_Pressure_Setpoint_inH2O - Furnace_Pressure_Actual_inH2O;
(* Proportional term *)
VAR P_Term := KP_Pressure * Furnace_Pressure_Error;
(* Integral term (with anti-windup limit) *)
Furnace_Pressure_Error_Integral := Furnace_Pressure_Error_Integral +
(KI_Pressure * Furnace_Pressure_Error * Control_Scan_Time);
Furnace_Pressure_Error_Integral := CLAMP(Furnace_Pressure_Error_Integral, -3.0, +3.0);
VAR I_Term := Furnace_Pressure_Error_Integral;
(* Primary loop output *)
Pressure_Loop_Output := P_Term + I_Term;
(* ═════════════════════════════════════════════════════════════ *)
(* 5. SECONDARY LOOP: OXYGEN TRIM (Fine-Tune) *)
/* ═════════════════════════════════════════════════════════════ */
(* Oxygen trim error *)
Oxygen_Trim_Error := Oxygen_Trim_Setpoint_Pct - Oxygen_Actual_Pct;
(* O₂ proportional: if O₂ too high (>3.7%), reduce fan speed *)
VAR O2_P_Term := KP_O2 * Oxygen_Trim_Error; (* Negative gain *)
(* O₂ integral *)
O2_Trim_Integral := O2_Trim_Integral + (KI_O2 * Oxygen_Trim_Error * Control_Scan_Time);
O2_Trim_Integral := CLAMP(O2_Trim_Integral, -O2_Integral_Limit, O2_Integral_Limit);
VAR O2_I_Term := O2_Trim_Integral;
Oxygen_Trim_Output := O2_P_Term + O2_I_Term;
(* ═════════════════════════════════════════════════════════════ *)
(* 6. CASCADE COMBINATION & OUTPUT *)
/* ═════════════════════════════════════════════════════════════ *)
IF Manual_Override_Mode THEN
Fan_Speed_Command_Pct := Manual_Fan_Speed_Pct;
ELSE
(* Combine primary (pressure) + secondary (O₂ trim) *)
(* Pressure = primary control; O₂ = fine-tune *)
Cascade_Combined_Output := Pressure_Loop_Output + Oxygen_Trim_Output;
(* Apply feedforward offset (fuel-dependent baseline) *)
Fan_Speed_Command_Pct := (50.0 + Cascade_Combined_Output);
(* Clamp to valid range *)
Fan_Speed_Command_Pct := CLAMP(Fan_Speed_Command_Pct, 30.0, 95.0);
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 7. OUTPUT: FAN SPEED COMMAND *)
/* ═════════════════════════════════════════════════════════════ */
WRITE_ANALOG_OUTPUT(AO_FAN_SPEED, Fan_Speed_Command_Pct);
(* Damper positioning: typically 0-5% faster than fan *)
Air_Damper_Command_Pct := Fan_Speed_Command_Pct + 2.0;
Air_Damper_Command_Pct := CLAMP(Air_Damper_Command_Pct, 20.0, 100.0);
WRITE_ANALOG_OUTPUT(AO_AIR_DAMPER, Air_Damper_Command_Pct);
(* ═════════════════════════════════════════════════════════════ *)
(* 8. FAULT DETECTION & ALARMS *)
/* ═════════════════════════════════════════════════════════════ *)
(* Furnace pressure too high *)
IF Furnace_Pressure_Actual_inH2O > 0.10 THEN
Furnace_Pressure_High_Alarm := TRUE;
ALARM_FURNACE_PRESSURE_HIGH := TRUE;
ELSE
Furnace_Pressure_High_Alarm := FALSE;
END_IF;
(* Furnace pressure too low *)
IF Furnace_Pressure_Actual_inH2O < -0.20 THEN
Furnace_Pressure_Low_Alarm := TRUE;
ALARM_FURNACE_PRESSURE_LOW := TRUE;
Control_Status := "WARNING: Furnace under-pressure (air leakage risk!)";
ELSE
Furnace_Pressure_Low_Alarm := FALSE;
END_IF;
(* Oxygen too high → excess air, inefficient *)
IF Oxygen_Actual_Pct > 4.5 THEN
Oxygen_High_Alarm := TRUE;
ELSE
Oxygen_High_Alarm := FALSE;
END_IF;
(* Oxygen too low → rich combustion, CO risk *)
IF Oxygen_Actual_Pct < 2.5 THEN
Oxygen_Low_Alarm := TRUE;
ALARM_OXYGEN_LOW := TRUE;
ELSE
Oxygen_Low_Alarm := FALSE;
END_IF;
(* Furnace temperature checks *)
IF Furnace_Temperature_C > 1350.0 THEN
Furnace_Temperature_High := TRUE;
ALARM_FURNACE_OVERTEMP := TRUE;
END_IF;
IF Furnace_Temperature_C < 1200.0 THEN
Furnace_Temperature_Low := TRUE;
ALARM_FURNACE_UNDERTEMP := TRUE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 9. COMBUSTION EFFICIENCY CALCULATION *)
/* ═════════════════════════════════════════════════════════════ *)
(* Simplified Boiler Efficiency:
Eff% = 100 - (Dry flue gas loss + Moisture in fuel + Radiation)
*)
VAR Flue_Gas_Temp_C := Furnace_Temperature_C - 200; (* Estimate *)
VAR Dry_Flue_Loss := (Flue_Gas_Temp_C - 20.0) * (21 - Oxygen_Actual_Pct) * 0.05; (* Simplified *)
Combustion_Efficiency_Pct := 100.0 - Dry_Flue_Loss;
Combustion_Efficiency_Pct := CLAMP(Combustion_Efficiency_Pct, 75.0, 92.0);
(* ═════════════════════════════════════════════════════════════ *)
(* 10. DATA LOGGING (for trend analysis & diagnostics) *)
/* ═════════════════════════════════════════════════════════════ */
(* Shift arrays and append latest *)
FOR i := 0 TO 58 DO
Furnace_Pressure_History[i] := Furnace_Pressure_History[i + 1];
Oxygen_History[i] := Oxygen_History[i + 1];
Fan_Speed_History[i] := Fan_Speed_History[i + 1];
Load_History[i] := Load_History[i + 1];
END_FOR;
Furnace_Pressure_History[59] := Furnace_Pressure_Actual_inH2O;
Oxygen_History[59] := Oxygen_Actual_Pct;
Fan_Speed_History[59] := Fan_Speed_Command_Pct;
Load_History[59] := Load_Demand_Pct;
END_PROGRAM
```
---
## 🏷️ Tag List
| Tag | Type | I/O | Range | Description |
|-----|------|-----|-------|-------------|
| `FP_SETPOINT` | REAL | Param | -0.20…0.10 inH₂O | Furnace pressure setpoint |
| `FP_ACTUAL` | REAL | Feedback | -0.30…0.20 | Actual furnace pressure |
| `FP_ERROR` | REAL | Diag | ±0.30 | Setpoint − Actual |
| `O2_TRIM_SETPOINT` | REAL | Param | 2.5…4.5 % | Target O₂ in flue gas |
| `O2_ACTUAL` | REAL | Feedback | 0…25 % | Actual flue gas O₂ % |
| `O2_ERROR` | REAL | Diag | ±2.0 % | Trim error |
| `FUEL_FLOW_TPH` | REAL | Feedback | 0…200 t/h | Coal/biomass feed rate |
| `AIR_REQUIRED_FF` | REAL | Calc | 0…3000 t/h | Stoichiometric + margin |
| `FAN_SPEED_CMD` | REAL | Output | 30…95 % | Force-draft fan speed |
| `FAN_SPEED_ACT` | REAL | Feedback | 0…100 % | Actual VFD output |
| `DAMPER_CMD` | REAL | Output | 20…100 % | Air intake damper % open |
| `DAMPER_ACT` | REAL | Feedback | 0…100 % | Damper position feedback |
| `FURNACE_TEMP` | REAL | Feedback | 800…1600 °C | Combustion zone temperature |
| `FURNACE_TEMP_SP` | REAL | Param | 1250…1350 | Reference temperature |
| `COMBUSTION_EFF` | REAL | Metric | 75…92 % | Boiler efficiency estimate |
| `KP_PRESSURE` | REAL | Param | 0.1…0.8 | Proportional gain (pressure) |
| `KI_PRESSURE` | REAL | Param | 0.005…0.050 | Integral gain (pressure) |
| `KP_O2` | REAL | Param | -0.05…-0.010 | O₂ proportional (negative) |
| `KI_O2` | REAL | Param | -0.010…-0.001 | O₂ integral (negative) |
| `PRESSURE_INTEGRAL` | REAL | State | ±5 inH₂O | Accumulated pressure error |
| `O2_INTEGRAL` | REAL | State | ±5 % | Accumulated O₂ error |
| `FP_HIGH_ALARM` | BOOL | Alarm | - | FP > +0.10 inH₂O |
| `FP_LOW_ALARM` | BOOL | Alarm | - | FP < −0.20 inH₂O |
| `O2_HIGH_ALARM` | BOOL | Alarm | - | O₂ > 4.5% (excess air) |
| `O2_LOW_ALARM` | BOOL | Alarm | - | O₂ < 2.5% (rich/CO) |
| `FURNACE_OVERTEMP` | BOOL | Alarm | - | Temp > 1350°C |
| `FURNACE_UNDERTEMP` | BOOL | Alarm | - | Temp < 1200°C |
| `O2_ANALYZER_FAULT` | BOOL | Alarm | - | No signal for >30 sec |
| `PRESSURE_TX_FAULT` | BOOL | Alarm | - | Transmitter stuck |
---
## 🚨 Alarm & Trip Matrix
| Alarm | Condition | Severity | Action |
|-------|-----------|----------|--------|
| **Furnace Over-Pressure** | FP > +0.10 inH₂O for >10 sec | Warning | Reduce fan speed; check for blockage |
| **Furnace Under-Pressure** | FP < −0.20 inH₂O | Critical | Operator alert: air leakage in furnace walls |
| **Oxygen Excess** | O₂ > 4.5% for >5 min | Warning | Reduce O₂ setpoint or reduce fuel |
| **Oxygen Deficiency** | O₂ < 2.5% for >30 sec | Critical | Stop fuel feed; check combustion air |
| **Furnace Over-Temperature** | Temp > 1350°C for >20 sec | Critical | Throttle fuel; increase cooling |
| **Furnace Under-Temperature** | Temp < 1200°C | Warning | Increase fuel or improve draft |
| **O₂ Analyzer Fault** | No signal change for >30 sec | Critical | Calibrate or replace analyzer |
| **Pressure Transmitter Fault** | Reading stuck for >60 sec | Warning | Replace transmitter; use manual damper |
---
## 📺 HMI Layout
```
┌──────────────────────────────────────────────────────┐
│ FURNACE COMBUSTION PRESSURE CONTROL │
│ (300 MWe Pulverized Coal Boiler) │
├──────────────────────────────────────────────────────┤
│ │
│ Status: STABLE 🟢 EFFICIENCY 89.2% │
│ │
│ ┌───────────────────────────────────────────────┐ │
│ │ COMBUSTION PRESSURE │ │
│ │ Setpoint: -0.070 inH₂O │ │
│ │ Actual: -0.068 inH₂O ✓ │ │
│ │ Error: +0.002 inH₂O (excellent) │ │
│ │ [████████░░░░░░░░░░] Trend: ↗ stable │ │
│ └───────────────────────────────────────────────┘ │
│ │
│ ┌───────────────────────────────────────────────┐ │
│ │ OXYGEN TRIM (Fine-Tune) │ │
│ │ Setpoint: 3.50% O₂ │ │
│ │ Actual: 3.48% O₂ ✓ │ │
│ │ Error: −0.02% (optimal) │ │
│ │ [████████░░░░░░░░░░] Trend: ↘ lean │ │
│ └───────────────────────────────────────────────┘ │
│ │
│ ┌───────────────────────────────────────────────┐ │
│ │ FURNACE CONDITIONS │ │
│ │ Temperature: 1298°C ✓ (SP: 1300) │ │
│ │ Fuel Flow: 94.5 t/h (coal feeder OK) │ │
│ │ Air Required: 1,285 t/h (calc: 1,282) │ │
│ │ Fan Speed: 72% (VFD output) │ │
│ │ Damper: 74% open │ │
│ └───────────────────────────────────────────────┘ │
│ │
│ Efficiency: 89.2% (vs design 89% @ 100% load) │
│ Monthly average: 88.7% (↑ 0.3% vs last month) │
│ │
│ PID Loop Status: │
│ Primary (Pressure): Kp=0.35, Ki=0.015, Ii≈+0.5 │
│ Secondary (O₂): Kp=-0.020, Ki=-0.003 │
│ │
│ Tuning Notes: Controller stable; no oscillations │
│ │
└──────────────────────────────────────────────────────┘
```
---
## 🔧 Configuration Parameters
```json
{
"furnace_pressure_setpoint_inH2O": -0.07,
"furnace_pressure_max_alarm_inH2O": 0.10,
"furnace_pressure_min_alarm_inH2O": -0.20,
"oxygen_setpoint_percent": 3.5,
"oxygen_max_excess_alarm": 4.5,
"oxygen_min_deficiency_alarm": 2.5,
"furnace_temperature_setpoint_c": 1300,
"furnace_temperature_max_alarm_c": 1350,
"furnace_temperature_min_alarm_c": 1200,
"kp_pressure": 0.35,
"ki_pressure": 0.015,
"kd_pressure": 0.0,
"kp_oxygen": -0.020,
"ki_oxygen": -0.003,
"integral_limit_pressure_inH2O": 3.0,
"integral_limit_oxygen_percent": 5.0,
"stoichiometric_air_ratio": 13.5,
"excess_air_margin": 1.15,
"analyzer_fault_timeout_sec": 30,
"transmitter_fault_timeout_sec": 60,
"control_scan_interval_sec": 2.0,
"data_history_minutes": 2.0
}
```
---
## 📝 Implementation Checklist
### Pre-Commissioning (Hardware Validation)
- [ ] **Furnace pressure transmitter** (±1.0 inH₂O range, ≤±2% accuracy)
- Installed on boiler shell, balanced between furnace & atmosphere
- Calibrated to zero (atmospheric)
- Verify on/off with vacuum pump
- [ ] **O₂ analyzer** (0-25% range, <±1% accuracy)
- Installed on flue gas stack (post-economizer)
- Warm-up time: 15-20 minutes before commissioning
- Calibration: zero (inert gas) + span (21% air)
- [ ] **Furnace temperature sensor** (radiation thermometer, Type R thermocouple)
- Installed on furnace wall, soot-free optical path
- Calibration check: compare to boiler drum saturation temp
- [ ] **Fuel flow measurement** (coal feeder speed sensor or mass balance)
- Verified against known feedstock rate
- Calibrated zero & span
- [ ] **Fan speed feedback** (tachometer or VFD status signal)
- 0-100% speed proportional to 4-20 mA
- [ ] **Air damper positioning** (potentiometer or resolver)
- Links damper mechanical position to 4-20 mA
- Verify full open/close stroke
- [ ] **Flue gas analyzer instrument air** (if pneumatic)
- Dry, clean instrument air supply (20 SCFM @ 100 PSI minimum)
### Commissioning (4-Week Procedure)
**Week 1: Tuning at Low Load (30-40% Capacity)**
1. Bring boiler to steady 35% load
2. Set furnace pressure manually at -0.08 inH₂O (no PI yet)
3. Observe O₂ trim: should be 3.4–3.6%
4. Run 8 hours; confirm stability
5. Set O₂ setpoint ±0.2% and monitor drift
**Week 2: Primary Loop (Pressure Tuning)**
1. Enable pressure loop with conservative Kp = 0.20 (low gain)
2. Introduce ±0.01 inH₂O step
3. Observe response: target 5-second settling time
4. Increase Kp to 0.35 if underdamped
5. Reduce Kp to 0.25 if oscillating
6. Measure overshoot: acceptable <10%
**Week 3: Secondary Loop (O₂ Tuning)**
1. Enable O₂ trim with conservative Kp = -0.010
2. Introduce load ramp 35% → 60% MWe
3. Monitor O₂ response: should hold 3.48–3.52%
4. If oscillation, reduce Kp magnitude to -0.015
5. Record final Kp, Ki values
**Week 4: Full Load Validation (70-100%)**
1. Ramp from 40% → 85% in 10% increments
2. Hold each level 30 minutes
3. Record furnace pressure, O₂, efficiency at each point
4. Verify no controller hunting or limit-cycle oscillation
5. Efficiency should track ≥88% at full load
6. Sign-off: Chief Control Engineer + Plant Manager
---
## 📊 Expected Performance
| Metric | Target | Achievable | Notes |
|--------|--------|-----------|-------|
| **Pressure control** | ±0.03 inH₂O | ±0.02-0.04 | Steady-state at constant load |
| **Pressure response time** | <30 sec | 15-20 sec | Step response to load change |
| **O₂ steadiness** | 3.5% ±0.2% | 3.48-3.52% | Fine-trim accuracy |
| **Furnace temperature** | SP ±30°C | ±20-40°C | Dependent on fuel char |
| **Boiler efficiency** | 89-91% | 88-90% | Varies by coal type |
| **NOx emissions** | <200 ppm @ 3% O₂ | 150-190 ppm | With excess air trim |
| **CO emissions** | <100 ppm | 5-50 ppm | If O₂ >3% |
---
## 🔄 Advanced Variations
### Multi-Burner (A/B/C) Balancing
If furnace has three air compartments (A, B, C burners):
- Furnace pressure main loop controls overall fan
- Secondary loops for each burner (PA, PB, PC pressure balancing)
- Prevent flame tilt (A too strong, C too weak)
### Combustion Optimization (NOx Reduction)
Add tertiary loop: NOx analyzer feedback
- If NOx > 200 ppm: slightly increase O₂ (leaner = lower NOx)
- Cascade: Pressure → O₂ → NOx (3-loop cascade)
### Load Ramp Rate Limiting
If load demanded changes >5 MWe/min:
- Soften fuel ramp (coal screw speed)
- Allow furnace pressure & temp to stabilize first
- Prevents boiler tube thermal shock
### Maintenance Trending
Historical data: store daily average FP, O₂, efficiency
- Plot vs date: detect slow drift (analyst tune degradation)
- Alert when efficiency drops >2% vs baseline → schedule cleaning
---
**Core power plant combustion control — essential for ASME compliance and efficiency optimization.**
> **CRITICAL REQUIREMENT**: Every coal/biomass boiler must implement furnace pressure control
> per ASME PG-35.2 (Steam Generating Equipment). This template provides the baseline
> for SIL 2 emissions monitoring and safety interlock integration.