Gas Separation Vessel — Control Design

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 50 views

# Oil & Gas Template: Gas Separation Vessel ## 1. Overview **Purpose:** Three-phase separator removes liquids (oil + water) from raw gas stream under subsonic conditions. Liquid level is controlled via dump valve to prevent slugging downstream (compressor inlet) while maintaining interface between oil-water. Pressure is constrained by gas outlet backpressure setpoint. **Industry Standards:** - API 14E (Design & Installation of Offshore Facilities) - ASME Section VIII (Pressure Vessel Design) - ISO 11583 (Separators—Terminology) - AGA Report No. 6 (Measurement of Natural Gas by Turbine Meters) **Critical Constraints:** - **Residence time:** minimum 3–5 minutes for gravity separation; insufficient time → carry-over of water droplets to compressor - **Liquid level:** must not exceed 75% (slugging risk) or drop below 20% (no interface, pump cavitation) - **Interface (oil-water):** oil denser ~0.85 sg, water 1.0 sg; detect via density contrast or conductivity - **Gas outlet:** subsonic flow ensures smooth separation; if sonic velocity reached, all separation fails - **Dump valve:** must modulate 0–100% to maintain level while gas backpressure is dynamic **Relevant Physics:** - **Gas residence time:** $T = V / Q$ where V = vessel volume (bbl), Q = gas flow rate (scf/day) - **Gravity separation:** settling velocity = $v_s = \sqrt{(18 \mu / (\rho_p - \rho_f)) \times g}$ via Stokes law - **Gas expansion:** $V_{gas} = V_{ref} \times (P_{ref} / P_{actual})$ (isothermal) - **Sonic velocity:** pressure ratio = PTR critical; if $P_{downstream}/P_{upstream} < 0.528$, choke condition --- ## 2. Control Philosophy ``` LAYER 1: Pressure Control (Gas Outlet) Setpoint: backpressure target (e.g., 250 psi) Actuator: downstream choke valve or separator vent valve Feedback: gas outlet pressure transmitter Goal: maintain stable gas dynamics, prevent surging LAYER 2: Liquid Level Control (Oil + Water Combined) Setpoint: 40–60% (mid-range between 20% and 75% safety limits) Actuator: dump valve (proportional 4–20mA control) Feedback: capacitive or radar level sensor Cascade: level error → demand flowrate → dump valve % LAYER 3: Interface Detection (Oil-Water Boundary) Method: density interface instrument or conductivity probe Purpose: track where oil stops and water starts Safety: if interface disappears (all oil floated out), alarm LAYER 4: Overflow & Underflow Protection High level alarm (>75%): reduce feed or open dump wider Low level alarm (<20%): reduce dump or increase feed LAYER 5: Carry-Over Detection Downstream: compressor inlet temperature rise or moisture content spike If liquid reach: compressor efficiency drops; trigger cascade shutdown ``` --- ## 3. Control Logic (Condensed) ```pascal { === 3-PHASE SEPARATOR (OIL, GAS, WATER) === } PROCEDURE Gas_Separator_Control CONSTANTS PRESSURE_SETPOINT_PSI = 250 { gas outlet backpressure } LEVEL_SETPOINT_PCT = 50 { oil + water combined level } INTERFACE_MIN_PCT = 20 { minimum oil layer } INTERFACE_MAX_PCT = 75 { slug risk threshold } SONIC_PRESSURE_RATIO = 0.528 { Mach 1 limit } GAS_RESIDENCE_TIME_MIN = 3 { minutes, minimum for separation } VARIABLES level_pct : REAL { capacitive sensor or radar } level_error_pct : REAL density_signal : REAL { interface detector } interface_oil_pct : REAL { where oil stops } pressure_outlet_psi : REAL { gas exiting vessel } pressure_inlet_psi : REAL { from upstream source } pressure_ratio : REAL dump_valve_cmd_pct : REAL { 0–100% } choke_valve_cmd_pct : REAL { gas backpressure controller } gas_flow_rate_scf_day : REAL { measured or estimated } residence_time_min : REAL { V_vessel / gas_flow } level_pid_integral : REAL level_pid_prev_error : REAL slug_detected : BOOLEAN interface_lost : BOOLEAN sonic_approach : BOOLEAN BEGIN { === READ INSTRUMENTS === } level_pct = Read_Level_Transmitter() { 0–100% full scale } density_signal = Read_Interface_Detector() { 0–20mA or 4–20mA } pressure_outlet_psi = Read_Pressure_Gas_Outlet() pressure_inlet_psi = Read_Pressure_Inlet() temperature_outlet_f = Read_Temperature_Outlet() { === INTERFACE POSITION === } { Convert 4–20mA interface signal to oil % } interface_oil_pct = (density_signal − 4) / 16 × 100 IF interface_oil_pct < 5 THEN interface_lost = TRUE Log_Alarm("INTERFACE_LOST_OIL_CARRY_OVER") ELSE interface_lost = FALSE END IF { === PRESSURE CONTROL (Gas Outlet) === } { Cascade PID: target outlet pressure = setpoint } pressure_error_psi = PRESSURE_SETPOINT_PSI − pressure_outlet_psi { Proportional term } choke_valve_cmd_pct = 50 + (pressure_error_psi × 2) { tuning: 2%/psi } { Clamp choke to 0–100% } IF choke_valve_cmd_pct < 0 THEN choke_valve_cmd_pct = 0 END IF IF choke_valve_cmd_pct > 100 THEN choke_valve_cmd_pct = 100 END IF { Check for sonic approach } pressure_ratio = pressure_outlet_psi / pressure_inlet_psi IF pressure_ratio < 0.55 THEN sonic_approach = TRUE Log_Warning("APPROACHING_SONIC_VELOCITY_CHOKE") ELSE sonic_approach = FALSE END IF { === LEVEL CONTROL (Dump Valve) === } level_error_pct = LEVEL_SETPOINT_PCT − level_pct { Anti-windup integral; only if error small } IF ABS(level_error_pct) < 10 THEN level_pid_integral = level_pid_integral + level_error_pct × 0.01 ELSE level_pid_integral = 0 END IF { PID for dump valve (Kp=1.5, Ki=0.01, Kd=0.5) } level_derivative = (level_error_pct − level_pid_prev_error) / scan_time_sec level_pid_output_pct = (1.5 × level_error_pct) + level_pid_integral + (0.5 × level_derivative) { Demand flowrate from PID } dump_valve_cmd_pct = 50 + level_pid_output_pct { nominal 50%, ±50% around midpoint } { Clamp to 0–100% } IF dump_valve_cmd_pct < 0 THEN dump_valve_cmd_pct = 0 END IF IF dump_valve_cmd_pct > 100 THEN dump_valve_cmd_pct = 100 END IF { === SAFETY LIMITS === } { High level protection } IF level_pct > INTERFACE_MAX_PCT THEN slug_detected = TRUE dump_valve_cmd_pct = 100 { fully open dump } Log_Alarm("SLUG_HIGH_LEVEL", level_pct=level_pct) ELSE slug_detected = FALSE END IF { Low level protection } IF level_pct < INTERFACE_MIN_PCT THEN dump_valve_cmd_pct = 0 { fully close dump } Log_Warning("LOW_LEVEL_PUMP_CAVITATION_RISK", level_pct=level_pct) END IF { === RESIDENCE TIME CHECK === } { Estimate residence time if gas flow available } gas_flow_rate_scf_day = 1.5 × flow_estimate_from_pressure_ratio { rough calc } residence_time_min = (vessel_volume_bbl × 5.615) / (gas_flow_rate_scf_day / 1440) IF residence_time_min < GAS_RESIDENCE_TIME_MIN THEN Log_Warning("SHORT_RESIDENCE_TIME_POOR_SEPARATION", rt_min=residence_time_min) END IF { === OUTPUTS === } Command_Control_Valve("DUMP_VALVE", dump_valve_cmd_pct) Command_Control_Valve("DOWNSTREAM_CHOKE", choke_valve_cmd_pct) { === DATA LOG (every 30 min) === } IF MOD(scan_count, 1800) = 0 THEN Log_Process_Data({ timestamp: Get_Timestamp(), level_pct: level_pct, interface_oil_pct: interface_oil_pct, pressure_outlet_psi: pressure_outlet_psi, dump_valve_cmd_pct: dump_valve_cmd_pct, choke_valve_cmd_pct: choke_valve_cmd_pct, residence_time_min: residence_time_min, slug_detected: slug_detected, interface_lost: interface_lost }) END IF level_pid_prev_error = level_error_pct END PROCEDURE ``` --- ## 4. Tag List ``` LEVEL_VESSEL_PCT { capacitive level 0–100% } DENSITY_INTERFACE_MA { 4–20mA interface position } PRESSURE_GAS_OUTLET_PSI { separator outlet pressure } PRESSURE_INLET_PSI { incoming stream } TEMPERATURE_OUTLET_F { for vapor correction } DUMP_VALVE_COMMAND_PCT { 0–100 modulation } CHOKE_VALVE_COMMAND_PCT { backpressure control } GAS_RESIDENCE_TIME_MIN { quality check } SLUG_DETECTED { boolean } INTERFACE_OIL_PCT { oil layer position } INTERFACE_LOST { alarm } SONIC_APPROACH { warning } ``` --- ## 5. Alarm & Trip Matrix | **Condition** | **Severity** | **Action** | |---|---|---| | **Level > 75%** | 🔴 CRIT | Open dump fully; check inlet capacity | | **Level < 20%** | 🟡 WARN | Close dump; check gas production | | **Interface lost** | 🔴 CRIT | Oil carry-over to compressor; trip inlet or vent gas | | **Pressure ratio < 0.55** | 🟡 WARN | Risk of sonic choke; restrict inlet | | **Residence time < 3 min** | 🟡 WARN | Reduce inlet or enlarge vessel | --- **Document Version:** 1.0 **Last Updated:** 2026-04-13 **Status:** Ready for Production

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library