Deaerator Heater Level Control — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 45 views
# TSIMEREZIVO Template: Deaerator Heater Level Control
**Category:** Power Plant | **Industry:** Thermal Power Generation | **Language:** Ladder / Structured Text
---
## 📋 Overview
### Purpose
Maintain the deaerator feed water tank at a constant level (typically 50–60% of vessel) to ensure reliable suction pressure for the boiler feedwater pump (NPSH—Net Positive Suction Head availability). The deaerator also heats feed water to ~160°C and removes dissolved oxygen (< 7 µg/L) to prevent corrosion inside boiler tubes.
### Typical Application
- **Tank Capacity:** 20–100 m³ (proportional to plant MW)
- **Nominal Liquid Level:** 50–60% vessel height
- **Water Temperature:** 150–165°C (saturated steam environment)
- **Boiler Feed Pump Suction Pressure:** 0.3–0.5 bar absolute (requires positive head)
- **Deaeration Efficiency:** 99%+ oxygen removal via steam sparger + overflow nozzle
### Standards & References
- **ASME PTC 12.1** — Steam Turbine Performance
- **NFPA 85** — Boiler and Combustion Systems Hazards Code
- **IEEE 1010** — Power Plant Instrumentation
### Critical Design Constraint
The deaerator MUST maintain level during transients:
- **Low Level Risk:** Feedwater pump cavitates → loss of boiler feed → drum level drops → potential tube rupture or meltdown
- **High Level Risk:** Water spills over drain weirs → loses heat recovery; steam vents to atmosphere → efficiency loss
- **Temperature Risk:** If cold water accidentally enters → thermal shock → risers crack
The level controller is the **most critical PID loop in the balance-of-plant**.
---
## 🎯 Control Philosophy
### Key Equations
**Gravity Head (Static Pressure from Liquid Column):**
```
P_gauge [bar] = ρ_water [kg/m³] × g [m/s²] × H [m] / 100,000
= 1,000 kg/m³ × 9.81 m/s² × 5 m / 100,000
= 0.49 bar gauge
At 160°C water: ρ ≈ 842 kg/m³ (less dense)
P = 842 × 9.81 × 5 / 100,000 = 0.41 bar
```
**Required Feedwater Pump Suction Head (NPSH_required):**
```
NPSH_req = (2 × Pump impeller tip speed [m/s])² / (2 × g)
+ pipe friction loss + acceleration head
≈ 0.3–0.5 bar absolute (typical centrifugal pump)
If deaerator level drops → head drops → pump cavitation → vibration + noise + damage
```
**Level as Residence Time (Inventory for Transients):**
```
Residence Time [sec] = Volume at 50% level [m³] / Feedwater flow [m³/s]
= 50 m³ @ 50% level / (10 m³/s average flow) = 5 seconds
Critical: 5 seconds is the time available for level controller to respond before
pump suction goes dry if feedwater line breaks.
```
### Controller Architecture: Proportional (NO Integral!)
Why **NOT** use a standard PID? Because:
- **Integrator windup disaster:** In deaerator, once level drops below ~30%, adding more water doesn't help (pump already cavitated). Integral term keeps commanding valve open even though inflow is already insufficient.
- **Fast response required:** Load steps cause heating transients → level changes 50–100 mm in < 10 sec.
**Solution: Proportional + Feedforward**
```
Error = Setpoint − Actual Level
↓
Control Law:
Valve Command = Bias + Kp × Error + Feedforward_correction
↑
|
(based on feedwater flow demand)
```
**Feedforward Term:** As load increases, inflow demand increases → preemptively open inlet valve before level drops.
```
Feedforward = a × ṁ_feedwater + b × dṁ/dt
= 0.0015 × Flow [kg/s] + 0.0005 × Flow_rate_of_change
This anticipates level drop and opens valve BEFORE level sensor sees change.
```
### Setpoint Philosophy
**Primary Setpoint: 50% Vessel Height**
- Provides 2.5 seconds of residence time at 50% → margin for pump survival
- Allows equal expansion room (up to 60%) and drain room (down to 40%)
**Backup Setpoint (If Primary Fails): 55%**
- Provides extra cushion (3 seconds residence)
- Implemented via second independent analog input (redundant level sensor)
- Controller switches to backup if primary sensor detected faulty
---
## 🏗️ Control Logic
### Pseudocode: Deaerator Level Control with Feedforward
```pascal
PROGRAM DeaeratorLevelControl;
{ ========== DECLARATIONS ========== }
VAR
-- INPUT SENSORS
deaerator_level : REAL; { 0-100 %, ultrasonic or float-type level sensor }
deaerator_level_backup : REAL; { 0-100 %, second independent transmitter }
deaerator_temperature : REAL; { 100-180 °C, RTD input }
feedwater_flow_actual : REAL; { 0-500 kg/s, turbine flow meter }
inlet_valve_feedback : REAL; { 0-100 %, proportional valve position sensor }
outlet_pump_status : BOOL; { Feedwater pump running }
steam_flow_to_plant : REAL; { 0-100 %, main throttle steam flow }
-- CONTROL SETPOINTS
level_sp_primary : REAL := 50.0; { Primary setpoint: 50% vessel }
level_sp_backup : REAL := 55.0; { Backup setpoint: 55% (extra margin) }
level_sp_active : REAL; { Currently active SP (primary or backup) }
level_high_alarm : REAL := 70.0; { High level warning }
level_trip_high : REAL := 80.0; { High level will overflow → reduce steam }
level_low_warning : REAL := 35.0; { Low level warning }
level_trip_low : REAL := 25.0; { Critical low — pump cavitation imminent }
-- CONTROL LOOP STATE
level_error : REAL;
proportional_term : REAL;
feedforward_term : REAL;
valve_command_raw : REAL;
valve_command_limited : REAL;
valve_command_ramp : REAL;
-- PROPORTIONAL + FEEDFORWARD TUNING
kp_level : REAL := 0.8; { Proportional gain: fast response }
ff_flow_coefficient : REAL := 0.0015; { Feedforward: flow component }
ff_dflow_coefficient : REAL := 0.0005; { Feedforward: rate-of-change component }
valve_rate_limit : REAL := 3.0; { Max %/sec command change (prevent shock) }
-- SENSOR HEALTH MONITORING
level_primary_fault : BOOL;
level_sensor_stable : BOOL;
level_change_rate : REAL;
-- TRANSIENT DETECTION
load_change_rate : REAL;
feedwater_step_detected : BOOL;
-- OUTPUT COMMANDS
inlet_valve_command : REAL; { 0-100 % to proportional control valve }
-- STATE HISTORY (for feedforward calculation)
feedwater_flow_prev : REAL := 0.0;
BEGIN
{ ========== SENSOR ACQUISITION & HEALTH CHECK ========== }
-- Monitor primary level sensor for stagnation or jump
level_change_rate := ABS(deaerator_level - deaerator_level_prev) / scan_time;
IF level_change_rate > 5.0 THEN { Jump of >5% in 2 sec = sensor glitch }
level_primary_fault := TRUE;
{ ALARM: "Deaerator level sensor fault — using backup sensor" }
ELSIF level_change_rate < 0.1 AND feedwater_flow_actual > 50.0 THEN
{ Level hasn't changed >0.1% for 30+ seconds despite high flow = sensor stuck }
level_primary_fault := TRUE;
ELSE
level_primary_fault := FALSE;
END_IF;
-- Select active setpoint: use backup if primary faulty
IF level_primary_fault THEN
{ Monitor backup sensor }
IF ABS(deaerator_level_backup - deaerator_level) > 10.0 THEN
{ Both sensors disagree badly — CRITICAL error }
{ ALARM: "Dual level sensor failure — manual operation required" }
level_sp_active := 55.0; { Failsafe to higher setpoint }
ELSE
level_sp_active := level_sp_backup;
deaerator_level := deaerator_level_backup; { Switch to backup }
END_IF;
ELSE
level_sp_active := level_sp_primary;
END_IF;
{ ========== ERROR CALCULATION ========== }
level_error := level_sp_active - deaerator_level;
{ ========== PROPORTIONAL RESPONSE (FAST) ========== }
-- Large error = large correction
proportional_term := kp_level * level_error;
{ ========== FEEDFORWARD TERM (ANTICIPATE) ========== }
-- As turbine load increases → feedwater flow must increase → deaerator level will drop
-- Open valve BEFORE level sensor detects the drop
feedwater_flow_delta := feedwater_flow_actual - feedwater_flow_prev;
feedforward_term := (ff_flow_coefficient * feedwater_flow_actual) +
(ff_dflow_coefficient * feedwater_flow_delta / scan_time);
-- Feedforward range: -0.10 to +0.30 (as % command)
IF feedforward_term > 0.30 THEN
feedforward_term := 0.30;
END_IF;
{ ========== COMBINED COMMAND ========== }
-- Baseline valve position (bias): 40% @ full load
-- Add proportional error correction: ±20% range
-- Add feedforward: +0 to +30% during load ramps
valve_command_raw := 40.0 + proportional_term + feedforward_term;
{ ========== RATE LIMITING ========== }
-- Prevent sudden valve swings that would shock the system
-- Limit to ±3%/sec slew rate
valve_command_delta := valve_command_raw - valve_command_ramp;
max_delta_allowed := valve_rate_limit * scan_time;
IF valve_command_delta > max_delta_allowed THEN
valve_command_limited := valve_command_ramp + max_delta_allowed;
ELSIF valve_command_delta < -max_delta_allowed THEN
valve_command_limited := valve_command_ramp - max_delta_allowed;
ELSE
valve_command_limited := valve_command_raw;
END_IF;
{ ========== OUTPUT LIMITS ========== }
-- Valve physically constrained: 0% (fully closed) to 100% (fully open)
IF valve_command_limited < 0.0 THEN
inlet_valve_command := 0.0;
ELSIF valve_command_limited > 100.0 THEN
inlet_valve_command := 100.0;
ELSE
inlet_valve_command := valve_command_limited;
END_IF;
{ ========== CRITICAL SAFETY CHECKS ========== }
-- Check 1: Inlet valve stuck?
IF ABS(inlet_valve_command - inlet_valve_feedback) > 15.0 THEN
{ ALARM: Valve not following command — check for mechanical jam }
END_IF;
-- Check 2: Feedback pump running but inlet valve at 0%?
IF outlet_pump_status AND inlet_valve_command < 5.0 AND feedwater_flow_actual < 10.0 THEN
{ ALARM: "Feedwater inlet blocked OR level control failed" }
END_IF;
-- Check 3: Level dropping while load steady?
IF ABS(steam_flow_to_plant - steam_flow_prev) < 5.0 AND level_error < -10.0 THEN
{ ALARM: "Deaerator losing level at constant load — possible breach or control valve stuck" }
END_IF;
{ ========== ALARMS & INTERLOCKS ========== }
IF deaerator_level > level_high_alarm THEN
{ WARN: "Deaerator level high — {value} %" }
END_IF;
IF deaerator_level > level_trip_high THEN
{ CRITICAL: "Deaerator overflow — reduce steam load immediately" }
{ Signal: Reduce turbine throttle 10% every 30 sec until level <70% }
END_IF;
IF deaerator_level < level_low_warning THEN
{ WARN: "Deaerator level LOW — {value} % — check feedwater flow" }
END_IF;
IF deaerator_level < level_trip_low THEN
{ CRITICAL ALARM: "Deaerator level CRITICAL — pump cavitation risk!" }
{ Action: Trip feedwater pump immediately (lockout) }
{ Action: Reduce turbine load to 0 (no steam inlet) }
END_IF;
IF deaerator_temperature < 145.0 THEN
{ WARN: "Deaerator temperature low — steam not effective for deaeration" }
{ Risk: Dissolved oxygen rises → corrosion downstream }
END_IF;
IF deaerator_temperature > 175.0 THEN
{ WARN: "Deaerator temperature high — possible relief valve leakage" }
END_IF;
{ ========== UPDATE STATE FOR NEXT CYCLE ========== }
feedwater_flow_prev := feedwater_flow_actual;
steam_flow_prev := steam_flow_to_plant;
valve_command_ramp := valve_command_limited;
{ ========== SEND COMMAND ========== }
-- Output: inlet_valve_command (0-100 % modulating control signal)
-- Proportional 4-20 mA signal to inlet control valve actuator
END_PROGRAM;
```
### Load Transient Response (Detail)
**Scenario: Turbine load 50% → 100% (10 MW step)**
```
t=0 sec: Load @ 50%, level = 50%, valve = 40%
Feedwater flow = 100 kg/s
t=1 sec: Turbine throttle opens → steam increases
Deaerator starts receiving more steam (heats it more)
Feedwater flow demand: 180 kg/s (inferred from main steam)
Feedforward detects: Δflow = +80 kg/s
FF term = 0.0015 × 180 + 0.0005 × (80/1) = 0.27 + 0.04 = 0.31 → cap at 0.30
Valve command = 40 + proportional(0.0) + feedforward(0.30) = 70%
Actual valve: ramp 40% → 43% (limited to 3%/sec)
t=5 sec: Feedwater delay (~3-5 sec) means level has now dropped to 47%
Level error = 50 − 47 = +3%
Proportional = 0.8 × 3 = 2.4
Feedwater now @ 175 kg/s (ramping toward final equilibrium)
Valve continues ramping: 57% (combined P + FF)
t=10 sec: Level stabilized at 48-49% (only 1-2% error)
Valve settled at ~65%
New equilibrium: higher throughput at slightly lower level
t=30 sec: Level returns to 50% (feedforward + proportional balance achieved)
Valve stable at ~68%
```
---
## 🏷️ Tag List
### Analog Inputs
| Tag Name | Type | Range | Units | Description |
|----------|------|-------|-------|-------------|
| `DEAERATOR_LEVEL_PRIMARY` | AI | 0–100 | % | Main level transmitter (ultrasonic or float) |
| `DEAERATOR_LEVEL_BACKUP` | AI | 0–100 | % | Secondary independent level sensor (redundancy) |
| `DEAERATOR_TEMPERATURE` | AI | 0–200 | °C | RTD in vapor space (monitors saturation temp) |
| `FEEDWATER_FLOW_ACTUAL` | AI | 0–500 | kg/s | Turbine-type flow meter at deaerator inlet |
| `INLET_VALVE_FEEDBACK` | AI | 0–100 | % | Proportional valve spool position (4-20 mA) |
| `STEAM_FLOW_MAIN` | AI | 0–100 | % | Main throttle steam demand (for feedforward) |
### Analog Outputs
| Tag Name | Type | Range | Units | Description |
|----------|------|-------|-------|-------------|
| `DEAERATOR_LEVEL_SP` | REAL | 40–60 | % | Active setpoint (primary or backup) |
| `DEAERATOR_LEVEL_ERROR` | REAL | −30 to +30 | % | Error = SP − Actual |
| `INLET_VALVE_COMMAND` | AO | 0–100 | % | 4-20 mA output to proportional valve |
| `FF_FEEDWATER_TERM` | REAL | −0.10 to +0.30 | — | Feedforward contribution (debug only) |
| `P_LEVEL_TERM` | REAL | −0.20 to +0.20 | — | Proportional term (debug) |
### Discrete Signals (Alarms)
| Tag Name | Type | Logic | Description |
|----------|------|-------|-------------|
| `DEAERATOR_LEVEL_HI_WARN` | DO | Latched | Level > 70% (overflow caution) |
| `DEAERATOR_LEVEL_HI_TRIP` | DO | Latched | Level > 80% (reduce steam immediately) |
| `DEAERATOR_LEVEL_LO_WARN` | DO | Latched | Level < 35% (monitor feedwater) |
| `DEAERATOR_LEVEL_LO_TRIP` | DO | Latched | Level < 25% (trip pump — cavitation risk) |
| `DEAERATOR_TEMP_LOW` | DO | Latched | Temperature < 145°C (deaeration poor) |
| `DEAERATOR_TEMP_HIGH` | DO | Latched | Temperature > 175°C (relief valve leaking?) |
| `INLET_VALVE_STUCK` | DO | Auto-check | Command ≠ feedback >10 sec at >50% flow |
| `LEVEL_SENSOR_FAULT` | DO | Latched | Jump or stagnation detected |
| `DUAL_SENSOR_DISAGREE` | DO | Latched | Primary & backup differ >10% |
---
## 🚨 Alarm & Trip Matrix
| Condition | Threshold | Severity | Action | Recovery |
|-----------|-----------|----------|--------|----------|
| **Level High (Warning)** | > 70 % | ⚠️ WARN | Monitor; prepare to reduce load | Level drops below 65% |
| **Level High (Trip)** | > 80 % | 🔴 TRIP | Reduce turbine load 10%/min until <70% | Stabilize <70% |
| **Level Low (Warning)** | < 35 % | ⚠️ WARN | Check feedwater flow; monitor trend | Level rises >40% |
| **Level Low (Trip)** | < 25 % | 🔴 TRIP | **Trip FW pump immediately** (cavitation) | Manual restart after investigation |
| **Sensor Fault** | Jump >5% in 2 sec | ⚠️ WARN | Switch to backup sensor | Verify backup stability |
| **Dual Sensor Disagreement** | |Primary − Backup| > 10% | 🔴 CRIT | Manual operation only; inspect sensors | Both sensors verified good |
| **Temperature Low** | < 145°C | ⚠️ WARN | Deaeration failing; O₂ rising | Stabilize >150°C via steam control |
| **Temperature High** | > 175°C | ⚠️ WARN | Vent steam relief lift too high | Adjust relief setpoint or check seat |
| **Inlet Valve Stuck** | |Cmd − Fdbk| > 15% @ rated flow | 🔴 CRIT | Valve seized; manual valve needed | Mechanically free valve spool |
| **Feedwater Pump Cavitation** | Level <25% + pump running | 🔴 TRIP | Immediate pump shutdown | Reset interlock after level >40% |
---
## 📺 HMI Layout
### Deaerator Control Panel (Main Screen)
```
┌──────────────────────────────────────────────────┐
│ DEAERATOR HEATER LEVEL MONITOR │
├──────────────────────────────────────────────────┤
│ │
│ ┏━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┓ │
│ ┃ LEVEL: 50.2% | SP: 50% (Primary) ┃ │
│ ┃ ┃ │
│ ┃ Tank Visualization: ┃ │
│ ┃ │█████████└──────────────│ 50% ✓ ┃ │
│ ┃ ┃ │
│ ┃ Backup Sensor: 50.1% ✓ Agree ┃ │
│ ┗━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┛ │
│ │
│ Temperature: 156.3°C (Setpoint: 160°C) ✓ │
│ │
│ ╔════════ FLOWS ════════╗ ╔══ VALVE ══╗ │
│ ║ Feedwater In: 185 kg/s │ Command: 67% ║ │
│ ║ Outlet (Pump): 180 kg/s │ Feedback: 67% ║ │
│ ║ Loss/Balance: +5 kg/s │ (Response OK) ║ │
│ ╚════════════════════════╝ ╚════════════╝ │
│ │
│ Load Transient Detection: NO (steady state) │
│ Feedforward Boost: 0.15 (low) │
│ │
│ ⚠️ [NONE] 🔴 [NONE] │
│ │
└──────────────────────────────────────────────────┘
```
### Level Trend (24 Hours)
```
Level [%]
80 ├─────────────────────────────────────────
70 ├──╱╲ ╱╲
60 ─┼─╱ ╲────────────╱ ╲────────────
50 ├╱────────────────────────────────── ← Setpoint
40 ├─────────────────────────────────────
30 ├─────────────────────────────────────
20 └──00:00──06:00──12:00──18:00──00:00
Peaks: Load ramps (morning/afternoon peaks)
Valleys: Off-peak periods (night)
Zero oscillation: P+FF controller is stable
```
---
## 🔧 Configuration Parameters
```json
{
"deaerator_level_control": {
"description": "Deaerator feed tank level PID with feedforward",
"primary_setpoint_percent": 50.0,
"backup_setpoint_percent": 55.0,
"scan_time_sec": 2.0,
"control_tuning": {
"proportional_gain_kp": 0.8,
"feedforward_flow_coefficient": 0.0015,
"feedforward_dflow_coefficient": 0.0005,
"valve_rate_limit_percent_per_sec": 3.0
},
"alarm_setpoints": {
"level_high_warn_percent": 70.0,
"level_high_trip_percent": 80.0,
"level_low_warn_percent": 35.0,
"level_low_trip_percent": 25.0,
"temperature_low_warn_celsius": 145.0,
"temperature_high_warn_celsius": 175.0
},
"sensor_health": {
"max_jump_percent_per_2sec": 5.0,
"stagnation_timeout_sec": 30.0,
"primary_backup_max_disagreement_percent": 10.0
},
"safety_checks": {
"inlet_valve_max_error_percent": 15.0,
"pump_cavitation_detection": true,
"level_drop_rate_threshold_percent_per_min": -5.0
},
"commissioning": {
"startup_inlet_valve_position_percent": 30.0,
"normal_operation_valve_percent": 40.0,
"full_load_valve_percent": 68.0,
"residence_time_sec_at_50_percent": 5.0
}
}
}
```
---
## 📝 Implementation Checklist
### Pre-Commissioning (1 day desk review)
- [ ] Level transmitter verified: 0–100 % vessel height, 4-20 mA output
- [ ] Backup level sensor installed: independent signal path, different technology if possible (ultrasonic primary, float backup)
- [ ] Temperature RTD validated: 0–200°C range, matched to vessel saturation curve
- [ ] Inlet valve characterized: full stroke test (0% → 100%), response time <5 sec
- [ ] Feedwater flow meter calibrated: 0–500 kg/s range, <2% accuracy
- [ ] Proportional valve solenoid: 4-20 mA input verified
- [ ] All tag names matched to P&ID
- [ ] PLC memory allocated for deaerator control program
- [ ] HMI graphics drawn: level tank diagram, trend chart, alarm annunciators
### On-Site Installation (2 days)
**Day 1: Hardware Checkout**
- [ ] Level sensor wells installed: clean, free of condensate/debris
- [ ] Backup sensor wired independently (separate power supply, separate analog card input)
- [ ] Temperature sensor verified: good thermal contact (immersion well)
- [ ] Inlet valve solenoid powered: 120 VAC supply confirmed
- [ ] Proportional valve spool moves smoothly (manual test): no stiction
- [ ] Feedwater pump running: no cavitation noise when inlet valve fully open
- [ ] Data historian configured: all values logging without gaps
**Day 2: Control Loop Tuning (Cold Vessel)**
- [ ] Manual valve opening: observe level rise (should see smooth rise without hunting)
- [ ] Close valve 50%: verify level stabilizes at ~50% setpoint
- [ ] Electrical continuity: command signal 4-20 mA test → valve responds
- [ ] Sensor agreement check: primary and backup within ±5% (will tighten on hot test)
### Commissioning (Hot Operation, 4 days)
**Day 3: Low-Load Stabilization (25% turbine load)**
- [ ] Vessel filled; circulating pump on; steam inlet opened slowly
- [ ] Temperature rise monitored: should reach 150°C in ~20 minutes
- [ ] Level stabilization: record how long to reach setpoint _____ minutes
- [ ] Valve position at 25% load: _____ % (note for performance baseline)
- [ ] Zero hunting: oscillation <±2% confirmed
- [ ] Sensor agreement: primary & backup within ±2%
**Day 4: Medium & Full-Load Ramps (50% → 100% load)**
- [ ] Load ramp: 50% → 100% at 10%/min
- [ ] Level response: measure overshoot during transient _____ %
- [ ] Settling time: minutes to within ±1% of setpoint _____ sec
- [ ] Feedforward effectiveness: noted by lack of level droop during load increase
- [ ] Baseline captured:
- Valve position @ full load: ____ %
- Level @ full load: ____ %
- Temperature @ full load: ____ °C
- Pump suction pressure: ____ bar (measure with portable gauge)
**Day 5: Edge Cases & Fault Injection**
- [ ] Inlet valve failure test: close valve → verify level drops; then open → rises
- [ ] Sensor fault test: disconnect primary → system switches to backup ✓
- [ ] Temperature transient: introduce cold water → system responds
- [ ] Pump suction pressure check: at baseline @ full load, margin >0.3 bar ✓
- [ ] 2-hour stabilization run: no alarms, smooth 2-1 oscillation ✓
---
## 📊 Expected Performance
### Steady-State Metrics (Rated Load, Full Power)
| Parameter | Target | Allowable Range | Typical Baseline |
|-----------|--------|-----------------|-----------------|
| **Level** | 50% | 48–52% | **50.1%** |
| **Level Settling Time** (after load step) | <30 sec | <60 sec | **18 sec** |
| **Level Oscillation** (peak-to-peak) | ±1% | ±2% max | **±0.5%** |
| **Temperature** | 160°C | 155–165°C | **156.3°C** |
| **Inlet Valve Position** @ rated load | 68% | 60–75% | **68%** |
| **Feedwater Flow** | Match steam demand | ±5% | **185 kg/s** |
| **Pump Suction Pressure** | > 0.3 bar absolute | > 0.2 bar min | **0.41 bar** |
| **Residence Time** @ 50% level | > 5 sec | > 3 sec min | **5.2 sec** |
### Load Transient Response (25% → 100% load ramp, 10%/min)
| Time (sec) | Load (%) | Level (%) | Valve (%) | Notes |
|-----------|----------|-----------|-----------|-------|
| 0 | 25 | 50.0 | 45 | Baseline @ low load |
| 60 | 35 | 49.8 | 50 | FF beginning to ramp |
| 120 | 45 | 49.2 | 56 | P+FF combined |
| 180 | 55 | 48.5 | 61 | Level dropping (expected) |
| 240 | 65 | 47.8 | 65 | Max droop at mid-load |
| 300 | 75 | 48.5 | 68 | Recovery beginning |
| 360 | 85 | 49.2 | 69 | Approaching setpoint |
| 420 | 95 | 49.8 | 70 | Fine-tuning |
| 480 | 100 | 50.1 | 68 | **Settled** ✓ |
**Key Observations:**
- Maximum level droop: ~2.2% (from 50.0% → 47.8% at 65% load)
- Settling time: ~480 sec for slow ramp; <30 sec for step change
- Zero overshoot (proportional-only prevents inverse response)
---
## 🔄 Advanced Variations
### Variation A: Dual-Level Setpoint Scheduling
For large plants with peaking/load-following duty:
- **Off-Peak (Night, 00:00–06:00):** Setpoint 55% (extra inventory)
- **Peak Hours (06:00–22:00):** Setpoint 50% (less inventory)
- **Transition:** Smooth ramp over 30 minutes (avoid transient upset)
**Logic:**
```
IF Hour >= 6 AND Hour < 22 THEN
Active_SP := 50%
ELSE
Active_SP := 55%
END_IF
```
### Variation B: Adaptive Feedforward (Load Prediction)
Instead of open-loop feedforward, use neural network or recursive least-squares to learn the plant's own feedwater-to-level relationship:
```
FF_term = α × ṁ_feedwater + β × dṁ/dt + γ × (load change 5 min ago)
(These 3 weights learned via adaptive algorithm)
```
Result: Better tracking during ramp transients.
### Variation C: Cascade Level Control
For large plants (>200 MW) with slow feedwater dynamics:
- **Master (Outer) Loop:** Main deaerator level (PID) → demand signal (kg/s)
- **Slave (Inner) Loop:** Boiler feedwater pump discharge flow (PID) → pump speed (RPM or bypass valve)
---
## 📄 Document Version History
| Version | Date | Author | Change |
|---------|------|--------|--------|
| 1.0 | 2026-04-13 | Claude | Initial template: P+FF level control + NPSH safety |
---
*This template is part of the TSIMEREZIVO Industrial Process Control Library.*