HVAC Control — AHU and Chiller Plant — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 44 views
# BMS Template: HVAC Control — AHU and Chiller Plant
## 1. Overview
**Purpose:**
Building Management System (BMS) control of an Air Handling Unit (AHU) and chilled water plant serving a commercial or industrial facility. Covers supply air temperature, mixed-air economizer, variable-volume supply air, and chiller plant sequencing.
**Industry Standards:**
- ASHRAE 90.1 (Energy Standard for Buildings)
- ASHRAE 135 (BACnet Communication Protocol)
- ASHRAE 62.1 (Ventilation for Acceptable Indoor Air Quality — minimum OA requirements)
- ASHRAE Guideline 36 (High-Performance Sequences of Operation for HVAC Systems)
- EN 15232 (Energy Performance of Buildings — BACS)
- ISO 7730 (Ergonomics of the Thermal Environment — PMV/PPD)
**Critical Constraints:**
- **Freeze protection:** Preheat coil MUST fire when OA temperature < 2°C — coil freeze-up is catastrophic
- **Minimum OA:** AHU minimum OA damper position per ASHRAE 62.1 (typically 20–30%) at all times when occupied
- **Chiller minimum run time:** 15 minutes ON, 5 minutes OFF (compressor thermal and oil cycling)
- **Discharge air temperature (DAT):** Minimum 13°C — risk of condensation and drip on ceiling
- **Fan interlock:** AHU fans MUST be proven ON before any heating or cooling is activated
- **CO₂ demand ventilation:** Increase OA when CO₂ > 800 ppm (ASHRAE 62.1 Appendix C)
- **Economizer lockout:** Economizer disabled when OA > RA dew point (enthalpy or temperature comparison)
- **VFD minimum:** AHU supply fan minimum 15% Hz (motor stall protection)
**Relevant Physics:**
- Cooling load: **Q = ṁ_air × c_p_air × (T_return − T_supply)**
- c_p_air ≈ 1.006 kJ/(kg·K) at atmospheric pressure
- ṁ_air = ρ_air × volumetric_flow = 1.2 kg/m³ × m³/s
- Economizer savings: **ΔP_chiller_saved = Q_econ / COP_chiller**
- PMV comfort: **PMV = f(T_air, T_radiant, v_air, humidity, metabolic rate, clothing)**
- Chiller efficiency: **COP = Q_cooling / P_compressor** (good chiller: COP 4–6)
- Enthalpy: **h = c_p × T + ω × (2501 + 1.86 × T)** kJ/kg dry air (ω = humidity ratio)
---
## 2. Control Philosophy
**ASHRAE Guideline 36 Sequences of Operation**
```
AHU Operating Modes:
0: UNOCCUPIED_NIGHT — Fan off; heating setback (18°C); no cooling
1: WARM_UP — Fan ON; heating to occupied setpoint; no cooling
2: OCCUPIED — Normal operation (see below)
3: ECONOMIZER — Free cooling from outside air (OA enthalpy < RA)
4: SETBACK — Weekend/holiday reduced heating
5: FREEZE_PROTECT — OA < 2°C; preheat coil ON regardless of occupancy
Supply Air Temperature Reset (SAT Reset):
- Optimal start: Raise DAT setpoint when zone loads are low (14→18°C)
- Zone with highest cooling demand drives DAT down (trim-and-respond)
- Floor: 13°C (condensation limit); Ceiling: 20°C (comfort limit)
VFD Fan Speed Control:
- Primary: Static pressure setpoint at duct (e.g., 125 Pa)
- Zone VAV boxes feedback drives duct pressure
- Minimum: 15% (motor stall limit)
- Maximum: 100%
Chiller Sequencing:
Chiller 1 (lead): Starts when cooling demand > 30% capacity
Chiller 2 (lag): Starts when Chiller 1 runs > 15 min and demand still > 90%
Staging down: Lag chiller stops when total demand < 50% for > 10 min
CHW Supply Temp: 6°C setpoint; reset to 8°C when OAT < 15°C (energy saving)
```
---
## 3. Control Logic
```pascal
{ === AHU AND CHILLER PLANT BMS CONTROL === }
{ ASHRAE Guideline 36 compliant sequences }
PROGRAM AHU_Chiller_Control
CONSTANTS
OAT_FREEZE_C = 2.0 { °C — freeze protection activation }
OAT_ECON_LOCK_C = 22.0 { °C — economizer lockout outdoor temperature }
CO2_OA_BOOST_PPM = 800 { ppm — CO₂ demand ventilation threshold }
CO2_MAX_PPM = 1000 { ppm — ASHRAE 62.1 maximum acceptable }
DAT_MIN_C = 13.0 { °C — minimum discharge air temp (condensation) }
DAT_MAX_C = 20.0 { °C — maximum discharge air temp (comfort) }
DAT_SETPOINT_NOM = 14.0 { °C — nominal discharge air setpoint }
RAT_SETPOINT_C = 22.0 { °C — return air / zone temp setpoint }
CHW_SP_NOM_C = 6.0 { °C — chilled water supply temp nominal }
CHW_SP_WARM_C = 8.0 { °C — CHW supply temp when OAT < 15°C }
CHILLER_MIN_RUN_S = 900 { s — minimum chiller ON time }
CHILLER_MIN_OFF_S = 300 { s — minimum chiller OFF time }
FAN_MIN_PCT = 15.0 { % — VFD fan minimum speed }
DUCT_PRESS_SP_PA = 125.0 { Pa — duct static pressure setpoint }
OA_MIN_PCT = 25.0 { % — minimum OA damper (ASHRAE 62.1) }
KP_FAN = 0.8 { Fan speed PI controller Kp }
KI_FAN = 0.15 { Fan speed PI controller Ki }
KP_CHW = 1.2 { Chiller plant valve Kp }
KI_CHW = 0.05 { Chiller plant valve Ki }
VARIABLES
{ Inputs }
oat_c : REAL { °C — Outdoor air temperature }
oat_rh_pct : REAL { % — Outdoor air relative humidity }
rat_c : REAL { °C — Return air temperature }
rat_rh_pct : REAL { % — Return air RH }
dat_c : REAL { °C — Discharge air temperature (after coils) }
duct_press_pa : REAL { Pa — Supply duct static pressure }
zone_co2_ppm : REAL { ppm — representative zone CO₂ }
zone_temp_avg_c : REAL { °C — average zone temperature }
chw_supply_c : REAL { °C — chilled water supply temperature }
chw_return_c : REAL { °C — chilled water return temperature }
chw_flow_lpm : REAL { L/min — CHW flow }
ch1_status : BOOL { Chiller 1 healthy / available }
ch2_status : BOOL { Chiller 2 healthy / available }
supply_fan_fb : BOOL { Supply fan proven status }
return_fan_fb : BOOL { Return fan proven status }
occupancy_signal : BOOL { BMS occupancy input (BACnet / PIR) }
{ Outputs }
supply_fan_cmd : BOOL
return_fan_cmd : BOOL
supply_fan_spd : REAL { % VFD speed }
oa_damper_pos : REAL { % open — outdoor air }
ra_damper_pos : REAL { % open — return air }
ea_damper_pos : REAL { % open — exhaust air }
preheat_valve : REAL { % — hot water preheat valve }
cooling_valve : REAL { % — CHW cooling coil valve }
ch1_start_cmd : BOOL
ch2_start_cmd : BOOL
chw_pump_cmd : BOOL
alarm_freeze : BOOL
alarm_co2 : BOOL
alarm_fan_fail : BOOL
{ Internals }
ahu_mode : INT { 0=unoccupied 2=occupied 3=economizer 5=freeze }
dat_setpoint : REAL { °C — active DAT setpoint }
fan_integral : REAL
chw_integral : REAL
ch1_on_timer : TON
ch2_on_timer : TON
ch1_off_timer : TOF
ch2_off_timer : TOF
econ_eligible : BOOL
cooling_demand_pct: REAL
CONST
MODE_UNOCCUPIED = 0
MODE_OCCUPIED = 2
MODE_ECONOMIZER = 3
MODE_FREEZE = 5
BEGIN
{ --- Freeze Protection (highest priority) --- }
alarm_freeze := oat_c < OAT_FREEZE_C
IF alarm_freeze THEN
ahu_mode := MODE_FREEZE
preheat_valve := 100.0
ELSIF NOT occupancy_signal THEN
ahu_mode := MODE_UNOCCUPIED
ELSE
{ Default occupied }
ahu_mode := MODE_OCCUPIED
END_IF
{ --- Economizer Eligibility --- }
{ Simple OA temperature comparison; use enthalpy comparison if sensors available }
econ_eligible := oat_c < OAT_ECON_LOCK_C AND
oat_c < rat_c - 2.0 AND { OA cooler than return }
oat_rh_pct < 85.0 { Not excessively humid }
IF econ_eligible AND ahu_mode = MODE_OCCUPIED THEN
ahu_mode := MODE_ECONOMIZER
END_IF
{ --- AHU Mode Execution --- }
CASE ahu_mode OF
MODE_UNOCCUPIED:
supply_fan_cmd := FALSE; return_fan_cmd := FALSE
supply_fan_spd := 0.0
oa_damper_pos := 0.0; ra_damper_pos := 100.0; ea_damper_pos := 0.0
cooling_valve := 0.0
preheat_valve := MAX(0.0, (18.0 - rat_c) * 20.0) { Setback heating to 18°C }
MODE_OCCUPIED, MODE_ECONOMIZER:
supply_fan_cmd := TRUE; return_fan_cmd := TRUE
{ Fan speed PI — static pressure control }
IF supply_fan_fb THEN
fan_integral := fan_integral + (DUCT_PRESS_SP_PA - duct_press_pa) * SCAN_TIME_S
supply_fan_spd := FAN_MIN_PCT + KP_FAN * (DUCT_PRESS_SP_PA - duct_press_pa) + KI_FAN * fan_integral
supply_fan_spd := MAX(FAN_MIN_PCT, MIN(100.0, supply_fan_spd))
ELSE
supply_fan_spd := 0.0
alarm_fan_fail := TRUE
END_IF
{ OA Damper Position }
IF ahu_mode = MODE_ECONOMIZER THEN
oa_damper_pos := 100.0 { Full outside air for free cooling }
ra_damper_pos := 0.0
ea_damper_pos := 100.0
ELSE
{ Minimum OA + CO₂ demand boost }
IF zone_co2_ppm > CO2_OA_BOOST_PPM THEN
oa_damper_pos := MIN(100.0, OA_MIN_PCT + (zone_co2_ppm - CO2_OA_BOOST_PPM) / 5.0)
ELSE
oa_damper_pos := OA_MIN_PCT
END_IF
ra_damper_pos := 100.0 - oa_damper_pos
ea_damper_pos := oa_damper_pos
END_IF
{ CO₂ Alarm }
alarm_co2 := zone_co2_ppm > CO2_MAX_PPM
{ DAT Reset: Zone trim-and-respond (simplified) }
dat_setpoint := DAT_SETPOINT_NOM +
MAX(-3.0, MIN(4.0, (zone_temp_avg_c - RAT_SETPOINT_C) * 1.5))
dat_setpoint := MAX(DAT_MIN_C, MIN(DAT_MAX_C, dat_setpoint))
{ Cooling Coil Valve (PI) — only if fan proven }
IF supply_fan_fb AND dat_c > dat_setpoint + 0.2 THEN
chw_integral := chw_integral + (dat_c - dat_setpoint) * SCAN_TIME_S
cooling_valve := KP_CHW * (dat_c - dat_setpoint) + KI_CHW * chw_integral
cooling_valve := MAX(0.0, MIN(100.0, cooling_valve))
preheat_valve := 0.0
ELSIF dat_c < dat_setpoint - 0.2 THEN
cooling_valve := MAX(0.0, cooling_valve - 1.0) { Ramp closed }
preheat_valve := MAX(0.0, (dat_setpoint - dat_c - 0.5) * 15.0)
preheat_valve := MIN(100.0, preheat_valve)
END_IF
MODE_FREEZE:
supply_fan_cmd := TRUE; return_fan_cmd := TRUE
supply_fan_spd := 30.0 { Minimum circulation }
oa_damper_pos := 0.0 { Close OA — freeze protection }
ra_damper_pos := 100.0
preheat_valve := 100.0 { Full preheat }
cooling_valve := 0.0
END_CASE
{ --- Chiller Plant Sequencing --- }
{ CHW supply temp setpoint — reset when warm outside }
{ chw_setpoint := CHW_SP_WARM_C if oat_c < 15°C else CHW_SP_NOM_C (handled in chiller PLC) }
{ Cooling demand estimate from cooling valve position (proxy) }
cooling_demand_pct := cooling_valve
{ Chiller 1 (lead) — start when demand > 30%, stop when < 20% }
IF cooling_demand_pct > 30.0 AND NOT ch1_start_cmd AND ch1_status THEN
ch1_off_timer(IN := FALSE)
IF ch1_off_timer.Q OR NOT ch1_start_cmd THEN
ch1_start_cmd := TRUE
chw_pump_cmd := TRUE
END_IF
ELSIF cooling_demand_pct < 20.0 AND ch1_start_cmd THEN
ch1_on_timer(IN := ch1_start_cmd, PT := T#900s)
IF ch1_on_timer.Q THEN
ch1_start_cmd := FALSE
END_IF
END_IF
{ Chiller 2 (lag) — start when demand > 90% for sustained period }
IF cooling_demand_pct > 90.0 AND ch1_start_cmd AND NOT ch2_start_cmd AND ch2_status THEN
ch1_on_timer(IN := ch1_start_cmd, PT := T#900s) { Chiller 1 must be running 15 min }
IF ch1_on_timer.Q THEN
ch2_start_cmd := TRUE
END_IF
END_IF
{ Stage off lag: demand < 50% for 10 min }
IF cooling_demand_pct < 50.0 AND ch2_start_cmd THEN
ch2_on_timer(IN := TRUE, PT := T#600s)
IF ch2_on_timer.Q THEN
ch2_start_cmd := FALSE
END_IF
ELSE
ch2_on_timer(IN := FALSE)
END_IF
{ Stop all if no AHU cooling demand }
IF ahu_mode = MODE_UNOCCUPIED THEN
ch1_start_cmd := FALSE; ch2_start_cmd := FALSE; chw_pump_cmd := FALSE
END_IF
alarm_fan_fail := supply_fan_cmd AND NOT supply_fan_fb
END_PROGRAM
```
---
## 4. Tag List (ISA-5.1 Naming — BACnet Object Reference)
| Tag Name | BACnet Object | Description | EGU | Lo | Hi |
|---|---|---|---|---|---|
| `AHU01_OAT_PV` | AI-1 | Outdoor air temperature | °C | −20 | 50 |
| `AHU01_OAT_RH_PV` | AI-2 | Outdoor air relative humidity | % | 0 | 100 |
| `AHU01_RAT_PV` | AI-3 | Return air temperature | °C | 10 | 35 |
| `AHU01_DAT_PV` | AI-4 | Discharge air temperature | °C | 5 | 30 |
| `AHU01_DUCT_PR_PV` | AI-5 | Supply duct static pressure | Pa | 0 | 500 |
| `AHU01_CO2_PV` | AI-6 | Zone CO₂ concentration | ppm | 300 | 2000 |
| `AHU01_CHW_SUP_PV` | AI-7 | CHW supply temperature | °C | 4 | 15 |
| `AHU01_SF_RUN_FB` | BI-1 | Supply fan run feedback | — | — | — |
| `AHU01_RF_RUN_FB` | BI-2 | Return fan run feedback | — | — | — |
| `AHU01_OCC_IN` | BI-3 | Occupancy signal | — | — | — |
| `AHU01_SF_CMD` | BO-1 | Supply fan start command | — | — | — |
| `AHU01_RF_CMD` | BO-2 | Return fan start command | — | — | — |
| `AHU01_SF_SPD_CV` | AO-1 | Supply fan VFD speed | % | 15 | 100 |
| `AHU01_OA_DPR_CV` | AO-2 | OA damper position | % | 0 | 100 |
| `AHU01_COOL_VLV_CV` | AO-3 | CHW cooling coil valve | % | 0 | 100 |
| `AHU01_PREHEAT_CV` | AO-4 | Preheat coil valve | % | 0 | 100 |
| `CH01_START_CMD` | BO-3 | Chiller 1 start command | — | — | — |
| `CH02_START_CMD` | BO-4 | Chiller 2 start command | — | — | — |
| `CHW_PUMP_CMD` | BO-5 | CHW primary pump | — | — | — |
| `AHU01_MODE` | AV-1 | AHU operating mode | — | 0 | 5 |
---
## 5. Alarm Configuration
| Alarm | Priority | Setpoint | Action |
|---|---|---|---|
| `AHU01_FREEZE_ALM` | Critical | OAT < 2°C | Preheat 100%; close OA damper |
| `AHU01_FAN_FAIL_ALM` | Critical | Fan commanded but no proof | Inhibit coils; alert maintenance |
| `AHU01_CO2_HIGH_ALM` | High | CO₂ > 1000 ppm | Increase OA damper; alert |
| `AHU01_DAT_LOW_ALM` | High | DAT < 13°C | Close cooling valve; check setpoint |
| `AHU01_CHW_HI_TEMP_ALM` | High | CHW supply > 9°C | Check chiller status; reduce load |
| `CH01_FAULT_ALM` | High | Chiller 1 fault | Switch to Chiller 2; alert maintenance |
| `CH02_FAULT_ALM` | High | Chiller 2 fault | Operate on Chiller 1 only |