Superheater Outlet Temperature Control (Spray Water Attemperator) — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 39 views
# Power Plant Template: Superheater Outlet Temperature Control (Spray Water Attemperator)
**Version**: 1.0
**Complexity**: High
**Industry**: Power Generation (All Fuel Types)
**Plant Size**: 50–500 MWe steam generators
**Standard**: ASME PG-60 (Superheater & Reheater Tube Code) + IEEE 1010
**Safety Level**: SIL 2 (tube protection; high-energy steam)
---
## 📋 Overview
Maintain superheated steam outlet temperature at exactly setpoint (±3°C typical) using proportional
spray water injection into the superheater tube bundle. Temperature control is **critical**:
- **Too hot** (>65°C above SP): Tube metal creep, reduction in wall thickness → rupture risk (50-year design life compromised)
- **Too cold** (<10°C below SP): Wet steam delivery to turbine → blade erosion, efficiency loss
**Why Attemperator Spray?**
```
Furnace heat = FIXED by fuel burning rate
Superheater outlet temp = Variable with:
- Fuel type (coal/gas/biomass: different combustion profiles)
- Load changes (100 MWe → 200 MWe → temp RISES by 20-40°C if uncontrolled)
- Air supply (furnace pressure changes)
- Tube cleanliness (soot deposits reduce heat transfer)
Solution: Inject small flow of cold water (saturated at drum pressure)
into the steam path, cooling the steam via contact & mixing.
Cost: One water pump (0.5-2 L/min) + one proportional control valve
Benefit: Maintain ±3°C accuracy → extends tube life 10+ years
```
**Typical 300 MWe Coal-Fired Boiler:**
```
Main steam: 540°C, 175 bar @ rated load
Attemperator spray: 30°C water from deaerator
Spray flow range: 0.5–5 L/min (proportional valve 4-20 mA)
Temperature setpoint: 540°C (±5°C alarm)
Accuracy requirement: ±3°C (ASME PG-60: ±5°C for steam generators >20 MWe)
Control response: <30 seconds to step change
```
---
## 🎯 Control Philosophy
```
ATTEMPERATOR SPRAY (SIMPLE PROPORTIONAL CONTROL)
Hot Superheat Steam
(540°C)
↓
┌─────────────┐
│ Superheater │
│ Tube │
│ Bundle │
└─────────────┘
↓
T_outlet = Current Temp
┌─────────────────────────────────────┐
│ T_outlet Feedback │
│ (RTD measurement) │
└────────────────────┬────────────────┘
│
Error = SP - Actual
│
[PI(D) Controller]
↓
Spray Water Valve
(0-20 mA proportional)
│
Cold Water ↓ (30°C)
0.5-5 L/min
↓
┌─────────────┐
│ Superheater │
│ Tube Path │
│ (Spray Zone)│
└─────────────┘
↓
T_out = SP ✓
Mechanism:
1. If T_out > SP: Spray more water (increase valve current)
2. If T_out < SP: Spray less water (decrease valve current)
3. At equilibrium: Spray rate = mist, controlled by proportional valve
```
**Why NOT On/Off?**
```
On/Off relay would cause:
- Temperature oscillates: 535°C → 545°C → 535°C → 545°C (±10°C)
- Thermal shock: tube metal contracts/expands 20 times/minute
- Metal fatigue: cracking in 5-10 years (vs 40-year design life)
- Creep rupture: peaks at 545°C weaken tube structure
Proportional spray:
- Temperature smooth: 540.0°C → 540.2°C → 540.1°C (±0.3°C)
- No mechanical shock: tube stress constant
- Creep risk minimal: operates within design envelope
```
---
## 🏗️ Control Logic (Pseudocode)
```pascal
PROGRAM Superheater_Outlet_Temperature_Control
VAR
(* ─── SETPOINT & MODE ─── *)
Temperature_Setpoint_C : REAL := 540.0; (* °C at rated load *)
Temperature_Setpoint_Trim : REAL := 0.0; (* ±10°C adj by operator *)
Load_Demand_Pct : REAL; (* Boiler load 0-100% *)
Manual_Override : BOOL := FALSE;
Manual_Valve_Cmd_mA : REAL := 0.0; (* 4-20 mA manual *)
(* ─── PRIMARY FEEDBACK: SUPERHEATER OUTLET TEMPERATURE ─── *)
SH_Outlet_Temperature_C : REAL; (* RTD sensor *)
SH_Outlet_Temp_Error : REAL;
SH_Outlet_Temp_Error_Last : REAL := 0.0;
SH_Outlet_Temp_Error_Integral : REAL := 0.0;
(* ─── PID TUNING ─── *)
KP : REAL := 0.15; (* Proportional gain *)
KI : REAL := 0.008; (* Integral gain *)
KD : REAL := 0.02; (* Derivative gain (helps with fast response) *)
Integral_Limit : REAL := 5.0; (* ±5°C accumulated error limit *)
Deadband : REAL := 0.3; (* Hysteresis to prevent hunting *)
(* ─── SPRAY VALVE OUTPUT ─── *)
Spray_Valve_Command_mA : REAL := 0.0; (* 4-20 mA *)
Spray_Valve_Actual_mA : REAL := 0.0; (* Feedback *)
(* ─── SPRAY WATER FLOW & CONDITIONS ─── *)
Spray_Water_Pressure_Bar : REAL; (* Must exceed steam pressure *)
Spray_Water_Temperature_C : REAL; (* Usually 30-50°C from deaerator *)
Spray_Water_Flow_LPM : REAL; (* 0-10 L/min typical *)
Spray_Water_Flow_Max_LPM : REAL := 5.0;
(* ─── SUPERHEATER CONDITIONS ─── *)
SH_Inlet_Pressure_Bar : REAL; (* Steam pressure upstream *)
SH_Inlet_Temperature_C : REAL; (* Reference: should be lower *)
SH_Tube_Metal_Temp_C : REAL; (* Estimated from outlet + model *)
SH_Tube_Metal_Max_C : REAL := 600.0; (* ASME limit for 540°C steam *)
(* ─── REHEATER (If Present) ─── *)
Reheat_Outlet_Temp_C : REAL; (* 2nd-stage superheater *)
Reheat_Setpoint_C : REAL := 540.0;
Reheat_Valve_Command : REAL := 0.0; (* Separate attemperator *)
(* ─── LOAD & FEEDFORWARD ─── *)
Load_Change_Rate : REAL; (* °C/min rate *)
Load_Last : REAL := 50.0;
Feedforward_Offset : REAL; (* Load-dependent baseline *)
(* ─── FAULT DETECTION ─── *)
SH_Temperature_High : BOOL := FALSE; (* >545°C *)
SH_Temperature_Low : BOOL := FALSE; (* <535°C *)
Spray_Valve_Stuck : BOOL := FALSE;
Spray_Water_Supply_Lost : BOOL := FALSE; (* Pressure <SH pressure *)
RTD_Sensor_Fault : BOOL := FALSE; (* No signal change >30 sec *)
Tube_Metal_Overtemp : BOOL := FALSE; (* >600°C estimated *)
Thermal_Shock_Risk : BOOL := FALSE; (* Temp change >2°C/sec *)
(* ─── DATA LOGGING ─── *)
SH_Temp_History : ARRAY[0..119] OF REAL; (* Last 2 minutes, 1 Hz *)
Spray_Flow_History : ARRAY[0..119] OF REAL;
Valve_Command_History : ARRAY[0..119] OF REAL;
Tube_Metal_Temp_Est_History : ARRAY[0..119] OF REAL;
(* ─── DIAGNOSTICS ─── *)
Control_Status : STRING := "Initializing";
Valve_Hysteresis_Active : BOOL := FALSE;
Control_Mode : STRING := "Auto"; (* or "Manual" *)
END_VAR
(* ═════════════════════════════════════════════════════════════ *)
(* 1. SENSOR ACQUISITION *)
(* ═════════════════════════════════════════════════════════════ *)
(* Superheater outlet temperature: RTD Pt100 Class A *)
SH_Outlet_Temperature_C :=
((READ_ANALOG_INPUT(AI_SH_OUTLET_TEMP) / 4095.0) * 700.0) - 50.0; (* -50…+650°C range *)
(* Spray water pressure (must be > steam pressure for injection) *)
Spray_Water_Pressure_Bar :=
(READ_ANALOG_INPUT(AI_SPRAY_PRESSURE) / 4095.0) * 250.0; (* 0-250 bar *)
(* Spray water flow (from flow transmitter on pump discharge) *)
Spray_Water_Flow_LPM :=
(READ_ANALOG_INPUT(AI_SPRAY_FLOW) / 4095.0) * 10.0; (* 0-10 L/min *)
(* Spray water temperature from deaerator *)
Spray_Water_Temperature_C :=
(READ_ANALOG_INPUT(AI_SPRAY_WATER_TEMP) / 4095.0) * 100.0; (* 0-100°C *)
(* Steam inlet pressure (upstream of superheater) *)
SH_Inlet_Pressure_Bar :=
(READ_ANALOG_INPUT(AI_SH_INLET_PRESSURE) / 4095.0) * 250.0;
(* Superheater inlet temperature *)
SH_Inlet_Temperature_C :=
((READ_ANALOG_INPUT(AI_SH_INLET_TEMP) / 4095.0) * 700.0) - 50.0;
(* Spray valve actual current (feedback for diagnostics) *)
Spray_Valve_Actual_mA :=
(READ_ANALOG_INPUT(AI_VALVE_CURRENT) / 4095.0) * 25.0; (* 0-25 mA *)
(* ═════════════════════════════════════════════════════════════ *)
(* 2. SENSOR HEALTH MONITOR *)
/* ═════════════════════════════════════════════════════════════ */
(* RTD fault: signal hasn't changed in >30 seconds → sensor stuck or wiring broken *)
IF ABS(SH_Outlet_Temperature_C - SH_Outlet_Temp_Error_Last) < 0.2 FOR > 30.0 sec THEN
RTD_Sensor_Fault := TRUE;
ALARM_RTD_FAULT := TRUE;
Control_Status := "ERROR: RTD sensor not responding";
ELSE
RTD_Sensor_Fault := FALSE;
END_IF;
(* Spray water pressure loss *)
IF Spray_Water_Pressure_Bar < (SH_Inlet_Pressure_Bar + 3.0) THEN
(* Pump pressure must exceed steam pressure by ≥3 bar for spray injection *)
Spray_Water_Supply_Lost := TRUE;
ALARM_SPRAY_WATER_LOST := TRUE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 3. TUBE METAL TEMPERATURE ESTIMATION *)
/* ═════════════════════════════════════════════════════════════ */
(* Tube metal temperature = outlet steam temp + thermal resistance of tube wall *)
(* Simplified: metal_temp ≈ outlet_temp + (heat_flux / h_convective) *)
(* For SH tubes: ΔT ≈ 20-40°C above steam at rated load *)
VAR ΔT_Tube_Wall := 30.0; (* Estimate based on tube geometry *)
SH_Tube_Metal_Temp_C := SH_Outlet_Temperature_C + ΔT_Tube_Wall;
(* Alert if tube metal exceeds ASME limit *)
IF SH_Tube_Metal_Temp_C > SH_Tube_Metal_Max_C THEN
Tube_Metal_Overtemp := TRUE;
ALARM_TUBE_OVERTEMP := TRUE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 4. ERROR CALCULATION & DEADBAND *)
/* ═════════════════════════════════════════════════════════════ */
(* Effective setpoint = nominal + load-dependent trim *)
VAR Effective_Setpoint := Temperature_Setpoint_C + Temperature_Setpoint_Trim;
(* Temperature error *)
SH_Outlet_Temp_Error := Effective_Setpoint - SH_Outlet_Temperature_C;
(* Apply deadband to reduce valve oscillation *)
IF ABS(SH_Outlet_Temp_Error) < Deadband THEN
SH_Outlet_Temp_Error := 0.0;
Valve_Hysteresis_Active := TRUE;
ELSE
Valve_Hysteresis_Active := FALSE;
END_IF;
(* Detect thermal shock: temperature change >2°C/second *)
VAR Temp_Rate_C_Per_Sec := ABS(SH_Outlet_Temperature_C - SH_Outlet_Temp_Error_Last) / SCAN_TIME_SEC;
IF Temp_Rate_C_Per_Sec > 2.0 THEN
Thermal_Shock_Risk := TRUE;
ALARM_THERMAL_SHOCK := TRUE;
ELSE
Thermal_Shock_Risk := FALSE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 5. PID CONTROL LAW *)
/* ═════════════════════════════════════════════════════════════ *)
IF Manual_Override THEN
Spray_Valve_Command_mA := Manual_Valve_Cmd_mA;
Control_Mode := "Manual";
ELSE
Control_Mode := "Auto";
(* Proportional term *)
VAR P_Term := KP * SH_Outlet_Temp_Error;
(* Integral term (with anti-windup) *)
SH_Outlet_Temp_Error_Integral := SH_Outlet_Temp_Error_Integral +
(KI * SH_Outlet_Temp_Error * SCAN_TIME_SEC);
SH_Outlet_Temp_Error_Integral := CLAMP(SH_Outlet_Temp_Error_Integral,
-Integral_Limit,
+Integral_Limit);
VAR I_Term := SH_Outlet_Temp_Error_Integral;
(* Derivative term (rate of change) *)
VAR D_Error := SH_Outlet_Temp_Error - SH_Outlet_Temp_Error_Last;
VAR D_Term := KD * (D_Error / SCAN_TIME_SEC);
(* Total PID output (in mA equivalent) *)
VAR Total_PID := P_Term + I_Term + D_Term;
(* Map to valve command: 0°C error → 12 mA (middle),
full positive load → 20 mA (max spray), full negative → 4 mA (min spray) *)
Spray_Valve_Command_mA := 12.0 + (Total_PID * 0.4); (* Scale factor *)
(* Clamp to valid 4-20 mA range *)
Spray_Valve_Command_mA := CLAMP(Spray_Valve_Command_mA, 4.0, 20.0);
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 6. SPRAY VALVE OUTPUT & FEEDBACK *)
/* ═════════════════════════════════════════════════════════════ *)
WRITE_ANALOG_OUTPUT(AO_SPRAY_VALVE, Spray_Valve_Command_mA);
(* Estimate actual spray flow from valve command *)
(* Proportional valve: 4 mA = 0 L/min, 20 mA = 5 L/min *)
IF Spray_Valve_Actual_mA < 4.0 THEN
Spray_Water_Flow_LPM := 0.0;
ELSE
Spray_Water_Flow_LPM := ((Spray_Valve_Actual_mA - 4.0) / 16.0) * Spray_Water_Flow_Max_LPM;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 7. ALARM GENERATION & STATUS *)
/* ═════════════════════════════════════════════════════════════ *)
(* Temperature too high *)
IF SH_Outlet_Temperature_C > (Effective_Setpoint + 5.0) THEN
SH_Temperature_High := TRUE;
ALARM_SH_TEMP_HIGH := TRUE;
Control_Status := "ALARM: Superheater outlet over-temperature";
ELSE
SH_Temperature_High := FALSE;
END_IF;
(* Temperature too low (possible wet steam condition) *)
IF SH_Outlet_Temperature_C < (Effective_Setpoint - 10.0) THEN
SH_Temperature_Low := TRUE;
ALARM_SH_TEMP_LOW := TRUE;
ELSE
SH_Temperature_Low := FALSE;
END_IF;
(* Spray valve stuck: command high but actual low *)
IF Spray_Valve_Command_mA > 18.0 AND Spray_Valve_Actual_mA < 10.0 FOR > 5.0 sec THEN
Spray_Valve_Stuck := TRUE;
ALARM_SPRAY_VALVE_STUCK := TRUE;
END_IF;
(* ═════════════════════════════════════════════════════════════ *)
(* 8. DATA LOGGING (for trending & diagnostics) *)
/* ═════════════════════════════════════════════════════════════ *)
(* Shift arrays and add current values *)
FOR i := 0 TO 118 DO
SH_Temp_History[i] := SH_Temp_History[i + 1];
Spray_Flow_History[i] := Spray_Flow_History[i + 1];
Valve_Command_History[i] := Valve_Command_History[i + 1];
Tube_Metal_Temp_Est_History[i] := Tube_Metal_Temp_Est_History[i + 1];
END_FOR;
SH_Temp_History[119] := SH_Outlet_Temperature_C;
Spray_Flow_History[119] := Spray_Water_Flow_LPM;
Valve_Command_History[119] := Spray_Valve_Command_mA;
Tube_Metal_Temp_Est_History[119] := SH_Tube_Metal_Temp_C;
(* Update last values for next scan *)
SH_Outlet_Temp_Error_Last := SH_Outlet_Temp_Error;
END_PROGRAM
```
---
## 🏷️ Tag List
| Tag | Type | I/O | Range | Description |
|-----|------|-----|-------|-------------|
| `SH_OUTLET_TEMP_SP` | REAL | Param | 500…570 °C | Superheater outlet setpoint |
| `SH_OUTLET_TEMP_ACT` | REAL | Feedback | 0…700 °C | Actual superheater outlet temp |
| `SH_OUTLET_TEMP_ERROR` | REAL | Diag | ±50 °C | Setpoint − Actual |
| `SH_INLET_TEMP` | REAL | Feedback | 200…600 °C | Upstream steam temp (reference) |
| `SH_INLET_PRESSURE` | REAL | Feedback | 0…250 bar | Steam pressure upstream |
| `SH_TUBE_METAL_EST` | REAL | Calc | 500…700 °C | Estimated tube wall temp |
| `SPRAY_VALVE_CMD` | REAL | Output | 4…20 mA | Proportional control valve |
| `SPRAY_VALVE_ACT` | REAL | Feedback | 4…20 mA | Actual valve current (pos feedback) |
| `SPRAY_WATER_FLOW` | REAL | Feedback | 0…10 L/min | Spray water flow rate |
| `SPRAY_WATER_PRESS` | REAL | Feedback | 0…250 bar | Spray pump pressure |
| `SPRAY_WATER_TEMP` | REAL | Feedback | 0…100 °C | Spray water inlet temp |
| `REHEAT_OUTLET_TEMP` | REAL | Feedback | 200…600 °C | Reheat outlet (if applicable) |
| `REHEAT_SETPOINT` | REAL | Param | 500…570 °C | Reheat target (if applicable) |
| `REHEAT_SPRAY_VALVE_CMD` | REAL | Output | 4…20 mA | Reheat attemperator (separate) |
| `KP_GAIN` | REAL | Param | 0.05…0.30 | Proportional gain |
| `KI_GAIN` | REAL | Param | 0.001…0.020 | Integral gain |
| `KD_GAIN` | REAL | Param | 0.001…0.050 | Derivative gain |
| `INTEGRAL_STATE` | REAL | State | ±5 °C | Accumulated error |
| `TEMP_ERROR_INTEGRAL` | REAL | State | ±5 °C | Integral accumulation |
| `SH_TEMP_HIGH_ALARM` | BOOL | Alarm | - | Outlet > SP + 5°C |
| `SH_TEMP_LOW_ALARM` | BOOL | Alarm | - | Outlet < SP − 10°C |
| `SPRAY_VALVE_STUCK` | BOOL | Alarm | - | Valve not responding to command |
| `SPRAY_WATER_LOST` | BOOL | Alarm | - | Pump pressure insufficient |
| `RTD_SENSOR_FAULT` | BOOL | Alarm | - | Temperature sensor not changing |
| `TUBE_METAL_OVERTEMP` | BOOL | Alarm | - | Est. tube wall > 600°C |
| `THERMAL_SHOCK` | BOOL | Alarm | - | Temp change >2°C/sec |
| `CONTROL_MODE` | STRING | Status | - | "Auto" or "Manual" |
---
## 🚨 Alarm & Trip Matrix
| Alarm | Condition | Severity | Action |
|-------|-----------|----------|--------|
| **SH Over-Temperature** | Outlet > SP + 5°C for >30 sec | Warning | Increase spray; alert operator |
| **SH Under-Temperature** | Outlet < SP − 10°C | Warning | Decrease spray; check water supply |
| **Spray Valve Stuck** | Command 18+ mA but actual <10 mA for >5 sec | Critical | Manual valve operation or replacement |
| **Spray Water Lost** | Pump pressure < steam pressure for >10 sec | Critical | Check pump; cannot operate |
| **RTD Sensor Fault** | No signal change for >30 sec | Critical | Use manual mode; replace sensor |
| **Tube Metal Over-Temp** | Estimated tube >600°C | Critical | Reduce load; increase spray |
| **Thermal Shock Risk** | Temperature change >2°C/sec | Warning | Reduce load ramp; tune PI gains |
---
## 📺 HMI Layout
```
┌──────────────────────────────────────────────┐
│ SUPERHEATER OUTLET TEMPERATURE CONTROL │
│ (Spray Water Attemperator) │
├──────────────────────────────────────────────┤
│ │
│ Status: STABLE 🟢 Load: 75% │
│ │
│ ┌────────────────────────────────────────┐ │
│ │ SUPERHEATER OUTLET TEMPERATURE │ │
│ │ Setpoint: 540.0°C │ │
│ │ Actual: 540.1°C ✓ │ │
│ │ Error: -0.1°C (excellent) │ │
│ │ [████████░░░░░░░░░░] Trend: → flat │ │
│ │ │ │
│ │ Tube Metal (Est.): 570.5°C / 600 max │ │
│ │ Safe margin: 29.5°C ✓ │ │
│ └────────────────────────────────────────┘ │
│ │
│ ┌────────────────────────────────────────┐ │
│ │ SPRAY WATER SYSTEM │ │
│ │ Valve Command: 8.5 mA (50% open) │ │
│ │ Valve Actual: 8.3 mA ✓ │ │
│ │ Flow Rate: 2.4 L/min │ │
│ │ Supply Pressure: 182 bar ✓ │ │
│ │ Water Temp: 45°C (from deaerator) │
│ └────────────────────────────────────────┘ │
│ │
│ PID Status: │
│ Kp = 0.15 (proportional) │
│ Ki = 0.008 (integral: +0.3°C/) │
│ Kd = 0.02 (derivative: damping) │
│ Deadband: 0.3°C (hysteresis active) │
│ │
│ Reheat Outlet: 540.2°C (if secondary) │
│ │
│ Last 2 minutes: Stable ±0.2°C │
│ │
└──────────────────────────────────────────────┘
```
---
## 🔧 Configuration Parameters
```json
{
"temperature_setpoint_c": 540.0,
"temperature_alarm_high_c": 545.0,
"temperature_alarm_low_c": 530.0,
"temperature_setpoint_max_c": 570.0,
"tube_metal_max_allowable_c": 600.0,
"spray_valve_min_ma": 4.0,
"spray_valve_max_ma": 20.0,
"spray_valve_neutral_ma": 12.0,
"spray_flow_max_lpm": 5.0,
"spray_pressure_min_margin_bar": 3.0,
"proportional_gain_kp": 0.15,
"integral_gain_ki": 0.008,
"derivative_gain_kd": 0.02,
"integral_limit_c": 5.0,
"deadband_c": 0.3,
"thermal_shock_rate_threshold_c_per_sec": 2.0,
"rtd_fault_timeout_sec": 30,
"valve_stuck_detection_timeout_sec": 5,
"tube_wall_temp_margin_c": 30.0,
"control_scan_interval_sec": 1.0,
"data_history_seconds": 120.0
}
```
---
## 📝 Implementation Checklist
### Hardware Validation
- [ ] **Superheater outlet RTD** (Pt100 Class A, −50…+650°C range)
- Installed in steam path (post-superheater)
- Sealant/fitting rated for 540°C + 10 bar overpressure
- Verified against boiler outlet saturation temperature
- [ ] **Spray water proportional control valve** (4-20 mA solenoid)
- Capacity: 0-5 L/min spray water at SH inlet pressure
- Integral flow control (not blocked when power lost)
- Tested: full open/close stroke + linearity check
- [ ] **Spray water pump** (small centrifugal or gear pump)
- Discharge pressure setpoint: SH inlet pressure + 3 bar
- Relief valve setting verified
- Suction: deaerator tank (≥0.5 bar) to prevent cavitation
- [ ] **Spray water flow measurement** (turbine or electromagnetic meter)
- 0-10 L/min range
- Calibrated to ±2%
- 4-20 mA output
- [ ] **Spray water temperature measurement** (RTD)
- Located at pump discharge (before entering superheater)
- Typical 30-50°C from deaerator
- [ ] **Spray pump pressure transmitter**
- Range: 0-250 bar
- Must monitor to ensure spray injection possible
- [ ] **Reheater outlet RTD** (if applicable, separate attemperator)
- Same class as SH outlet
- Separate control valve (proportional)
### Commissioning (7-Day Procedure)
**Day 1: Hardware Installation Verification**
1. Pressure test spray valve isolation block with 1.5× working pressure
2. Verify water flows through bypass (pump discharge relief)
3. Run pump 1 hour to inspect for leaks, noise
4. RTD response test: apply 50°C water, verify signal
**Day 2: Low-Load Tuning (25-30% Capacity)**
1. Bring boiler to 25% load, manually position spray valve at 50% (12 mA)
2. Observe outlet temperature: record for 30 minutes (should stabilize)
3. Manually increase spray by 10% → observe temperature drop
4. Record response: ideal <5 seconds to steady state
**Day 3: PID Gains (Conservative Start)**
1. Enable automatic control with minimal gains:
- Kp = 0.05, Ki = 0.001, Kd = 0
2. Allow controller to trim once; observe settling
3. Increase Kp to 0.10 → test step response
4. Increase Ki to 0.002 → test offset removal over 1 minute
**Day 4: Load Ramp Test (25% → 50% → 75%)**
1. At each load step, hold for 20 minutes
2. Record temperature, valve command, spray flow
3. Verify no excessive overshoot (>3°C)
4. Adjust Kd if response too slow (add 0.01 at a time)
**Day 5: Full Load Test (80-95%)**
1. Ramp to 90% load in 10 minutes
2. Run 1 hour at constant load
3. Monitor for oscillation (±1°C peak-to-peak acceptable)
4. Record efficiency: should be optimal (lowest fuel cost)
**Day 6: Reheater Commissioning** (if applicable)
1. Tune separate reheater attemperator same as superheater
2. Verify both loops independent + stable
3. Cross-check: reheater outlet should be <10°C below SH outlet
**Day 7: Fault Scenario Testing**
1. Simulate spray water loss: shut pump discharge valve
- Temperature should rise; alarm should trigger within 10 seconds
- Operator should switch to manual valve adjustment
2. Simulate RTD failure: disconnect RTD
- System should detect loss of signal; display fault
- Allow manual mode takeover
3. Thermal shock test: ramp load 50% → 80% in 5 minutes
- Monitor for temperature overshoot & undershoot
- Verify no instability
---
## 📊 Expected Performance
| Metric | Target | Achievable | Notes |
|--------|--------|-----------|-------|
| **Temperature accuracy** | ±3°C @ SP | ±1-2°C | Well-tuned PID |
| **Response time** | <30 sec | 10-20 sec | Load step change |
| **Overshoot** | <5°C | 1-3°C | Derivative damping |
| **Settling time** | <2 minutes | 1-1.5 min | To within ±1°C |
| **Spray valve response** | <2 sec | 1-1.5 sec | Solenoid + hydraulics |
| **Tube metal margin** | >20°C below limit | 30-40°C typical | Safety factor |
| **Oscillation** | ±1°C max | ±0.5-1°C | Deadband prevents chatter |
---
## 🔄 Advanced Variations
### Load-Based Feedforward
If load changes predictably (ramp rate known):
- Calculate expected temperature rise: ΔT = Load_Change × 0.25°C per % load
- Pre-open spray valve 50 ms before load increase
- Result: temperature stays within ±2°C during ramp (vs ±5°C without FF)
### Dual-Element Superheater
If furnace has primary + secondary superheater banks:
- Separate attemperator on secondary (cross-flow arrangement)
- Primary heats to 480°C; secondary → outlet 540°C
- Two cascaded loops: more stable response
### Evaporator Temperature Trim
In combined cycle plants (boiler + GT):
- If GT exhaust temperature rises (more gas available):
- Automatically trim SH setpoint down 5°C
- Reduce steam rate demanded; improve plant efficiency
- Cascade: gas temp → steam temp FF
### Creep Rupture Protection (Long-Term)
Monitor tube metal temperature trend:
- If running consistently 15°C above nominal design:
- Alert for inspection (creep damage accumulation)
- Estimate remaining tube life: decreases exponentially with ΔT
- Schedule replacement before rupture risk significant
---
**Critical power plant steam temperature control — essential for boiler tube protection & plant efficiency.**
> **MANDATORY**: Every power boiler with main superheater must implement spray water
> attemperator per ASME PG-60. This template provides the baseline for SIL 2 temperature
> control and creep rupture prevention.