Water Recycling Circuit & Density Balance — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 32 views
# Mining Template: Water Recycling Circuit & Density Balance
## 1. Overview
**Purpose:**
Mining operations recycle water from thickener overflow back to upstream processes (crusher, mill) to conserve water and recover valuable solids from clarified water. However, recycled water carries suspended fines and reagents (flotation collectors, pH modifiers) that can change process chemistry. This template monitors recycled water density, pH, and ionic composition to ensure it doesn't degrade metallurgical recovery. The controller blends fresh water with recycled water to maintain target chemistry while maximizing recycling ratio (% of water reused).
**Industry Standards:**
- ISO 9308 (Water Quality—Microbionuclides)
- ASME WQA (Water Quality Association) Guidelines
- EPA 40 CFR Part 421 (Nonferrous Metals Processing—Effluent Limits)
- ISO 5667 (Water Sampling—Guidance on Sampling Techniques)
**Critical Constraints:**
- **Recycled water density:** typically 1.01–1.05 sg (slightly denser than fresh due to dissolved minerals & fines); density affects flotation efficiency
- **Suspended solids:** recycled water may contain 50–200 ppm fines; excess fines reduce float recovery
- **pH range:** must be maintained 7.5–9.5 for optimal flotation; recycled water may drift acidic or basic
- **Ionic strength:** recycled water accumulates sodium, chloride, other salts; high ionic strength reduces bubble size
- **Recycling ratio:** target 70–90% recycled water; >90% causes mineral loss
- **Makeup water rate:** the difference; fresh water balances out losses to tailings
**Relevant Physics:**
- **Density of slurry:** $\rho = X_{solids} \rho_{solids} + (1 - X_{solids}) \rho_{water}$ (mass fraction, component densities)
- **Conductivity (ionic strength):** $\kappa = \sum_i c_i \lambda_i$ (concentration × molar conductivity of each ion)
- **Flotation bubble size:** $d_{bubble} \propto 1 / (1 + \kappa/\kappa_{ref})$ (inversely proportional to ionic strength)
- **Water balance:** $V_{in}(fresh + recycled) = V_{out}(product) + V_{loss}(tailings evap)$ (mass conservation)
---
## 2. Control Philosophy
```
LAYER 1: Recycled Water Quality Monitoring
Measure: density, pH, conductivity, turbidity
Setpoint: density 1.02 sg, pH 8.5, conductivity <5000 µS/cm
Feedback: inline sensors in recycled water header
LAYER 2: Fresh Water Makeup Cascade
If recycled quality degrades: blend more fresh water
Ratio control: 70% recycled + 30% fresh (nominal)
Adjust: if density or conductivity high, reduce recycled water proportion
LAYER 3: Recycle Ratio Optimization
Goal: maximize recycling % while maintaining metallurgy
Monitor: flotation recovery rate as downstream feedback
If recovery drops: increase fresh water ratio
LAYER 4: Acid/Base Addition for pH Control
Recycled water may drift acidic (CO₂ absorption) or basic (volatilization)
Add H₂SO₄ or NaOH as needed to maintain pH 8.5 setpoint
Meter pump command proportional to pH error
LAYER 5: Fines Settling Before Recirculation
Install settling weir or polishing screen
Allow 5–10 minutes settling to remove coarse fines
Periodic backflush of screen to return fines to thickener
```
---
## 3. Control Logic (Condensed)
```pascal
{ === MINING WATER RECYCLING & DENSITY BALANCE === }
PROCEDURE Water_Recycling_Control
CONSTANTS
RECYCLE_RATIO_TARGET_PCT = 75 { 75% recycled, 25% fresh }
RECYCLE_RATIO_MIN_PCT = 50 { safety minimum }
RECYCLE_RATIO_MAX_PCT = 90 { max before issues }
DENSITY_SETPOINT_SG = 1.02 { target specific gravity }
DENSITY_TOLERANCE_SG = 0.01 { ±0.01 sg acceptable }
DENSITY_HIGH_SG = 1.05 { too many fines }
DENSITY_LOW_SG = 1.00 { too much fresh }
PH_SETPOINT = 8.5 { optimal for flotation }
PH_TOLERANCE = 0.3 { ±0.3 pH }
CONDUCTIVITY_HIGH_USPS_CM = 5000 { excessive salts }
TURBIDITY_HIGH_NTU = 100 { too many fines }
FLOW_TOTAL_T_HR = 200 { total water circuit }
VARIABLES
water_density_sg : REAL { recycled water density }
water_density_error_sg : REAL
water_ph : REAL
water_ph_error : REAL
water_conductivity_usps_cm : REAL { ionic strength }
water_turbidity_ntu : REAL { suspended solids }
fresh_water_flow_t_hr : REAL { makeup }
recycled_water_flow_t_hr : REAL { from thickener }
total_flow_t_hr : REAL { sum }
recycle_ratio_pct : REAL { (recycled / total) × 100 }
recycle_ratio_error_pct : REAL
acid_dose_kg_hr : REAL { H₂SO₄ for pH control }
base_dose_kg_hr : REAL { NaOH for pH control }
flotation_recovery_pct : REAL { feedback from downstream }
recovery_trend_pct_per_day : REAL
water_circuit_status : ENUMERATION { NORMAL | HIGH_FINES | POOR_CHEMISTRY | DEGRADED_RECOVERY }
BEGIN
{ === SENSOR INPUT === }
water_density_sg = Read_Density_Transmitter() { recycled header }
water_ph = Read_pH_Transmitter()
water_conductivity_usps_cm = Read_Conductivity_Sensor()
water_turbidity_ntu = Read_Turbidity_Meter()
recycled_water_flow_t_hr = Read_Recycled_Water_Flowmeter()
fresh_water_flow_t_hr = Read_Fresh_Water_Flowmeter()
total_flow_t_hr = recycled_water_flow_t_hr + fresh_water_flow_t_hr
flotation_recovery_pct = Read_Flotation_Recovery_Feedback() { from flotation circuit }
{ === RECYCLING RATIO CONTROL === }
recycle_ratio_pct = (recycled_water_flow_t_hr / total_flow_t_hr) × 100
recycle_ratio_error_pct = RECYCLE_RATIO_TARGET_PCT − recycle_ratio_pct
{ Adjust fresh water flow to maintain recycle ratio }
fresh_water_setpoint_t_hr = total_flow_t_hr × (100 − RECYCLE_RATIO_TARGET_PCT) / 100
{ Clamp to avoid extreme ratios }
IF recycle_ratio_pct < RECYCLE_RATIO_MIN_PCT THEN
fresh_water_setpoint_t_hr = 0 { use all recycled available }
END IF
IF recycle_ratio_pct > RECYCLE_RATIO_MAX_PCT THEN
fresh_water_setpoint_t_hr = total_flow_t_hr × 0.15 { force 15% fresh minimum }
END IF
Command_Fresh_Water_Pump_Setpoint(fresh_water_setpoint_t_hr)
{ === WATER QUALITY MONITORING === }
water_circuit_status = NORMAL { initialize }
{ Density check (fines content) }
water_density_error_sg = DENSITY_SETPOINT_SG − water_density_sg
IF water_density_sg > DENSITY_HIGH_SG THEN
water_circuit_status = HIGH_FINES
Log_Alarm("RECYCLED_WATER_HIGH_DENSITY_FINES", density=water_density_sg)
{ Emergency: increase fresh water ratio to dilute }
recycle_ratio_pct = RECYCLE_RATIO_MIN_PCT { drop to 50% recycled }
ELSIF water_density_sg < DENSITY_LOW_SG THEN
{ Very dilute; likely fresh water overfeed }
Log_Warning("RECYCLED_WATER_LOW_DENSITY", density=water_density_sg)
END IF
{ pH Control (acid/base addition) }
water_ph_error = PH_SETPOINT − water_ph
IF ABS(water_ph_error) > PH_TOLERANCE THEN
{ Proportional dose control (Kp = 0.5 kg/hr per pH unit) }
IF water_ph < PH_SETPOINT THEN
{ Water too acidic; add base (NaOH) }
base_dose_kg_hr = 0.5 × ABS(water_ph_error)
acid_dose_kg_hr = 0
ELSE
{ Water too basic; add acid (H₂SO₄) }
acid_dose_kg_hr = 0.5 × water_ph_error
base_dose_kg_hr = 0
END IF
Command_Acid_Pump_Setpoint(acid_dose_kg_hr)
Command_Base_Pump_Setpoint(base_dose_kg_hr)
Log_Info("PH_ADJUSTMENT", current_ph=water_ph, dose_acid_kg_hr=acid_dose_kg_hr, dose_base_kg_hr=base_dose_kg_hr)
END IF
{ Conductivity (ionic strength) check }
IF water_conductivity_usps_cm > CONDUCTIVITY_HIGH_USPS_CM THEN
Log_Warning("HIGH_IONIC_STRENGTH_SALTS", conductivity=water_conductivity_usps_cm)
{ Likely causes: evaporation, salt concentration; increase fresh water ratio }
recycle_ratio_pct = recycle_ratio_pct − 10 { reduce recycled by 10% }
END IF
{ Turbidity (suspended fines) check }
IF water_turbidity_ntu > TURBIDITY_HIGH_NTU THEN
water_circuit_status = HIGH_FINES
Log_Alarm("RECYCLED_WATER_HIGH_TURBIDITY_FINES", turbidity=water_turbidity_ntu)
{ Trigger settling weir backflush or increase settling time }
Command_Settling_Weir_Backflush()
END IF
{ === DOWNSTREAM METALLURGICAL FEEDBACK === }
{ Monitor flotation recovery; if declining, recycle chemistry may be at fault }
IF MOD(scan_count, 86400) = 0 THEN { every 24 hours }
recovery_trend_pct_per_day = flotation_recovery_pct − prev_recovery_pct
{ If recovery declining >2% per day, suspect recycle water issue }
IF recovery_trend_pct_per_day < −2 THEN
water_circuit_status = DEGRADED_RECOVERY
Log_Alarm("FLOTATION_RECOVERY_DECLINING_CHECK_WATER", recovery=flotation_recovery_pct, trend_pct_day=recovery_trend_pct_per_day)
{ Emergency response: increase fresh water ratio to 50% minimum }
recycle_ratio_pct = RECYCLE_RATIO_MIN_PCT
END IF
END IF
{ === CHEMISTRY OVERRIDE LOGIC === }
{ If ANY water quality parameter out of spec, increase fresh water as safety }
chemistry_alert_count = 0
IF ABS(water_density_error_sg) > DENSITY_TOLERANCE_SG THEN chemistry_alert_count + + END IF
IF ABS(water_ph_error) > PH_TOLERANCE THEN chemistry_alert_count + + END IF
IF water_conductivity_usps_cm > CONDUCTIVITY_HIGH_USPS_CM THEN chemistry_alert_count + + END IF
IF chemistry_alert_count >= 2 THEN
{ Multiple parameters out of spec; increase fresh water safety margin }
recycle_ratio_pct = RECYCLE_RATIO_TARGET_PCT − 20 { drop to 55% recycled }
water_circuit_status = POOR_CHEMISTRY
Log_Alarm("MULTIPLE_CHEMISTRY_PARAMETERS_OUT_SPEC")
END IF
{ === DATA LOGGING (every hour) === }
IF MOD(scan_count, 3600) = 0 THEN
Log_Process_Data({
timestamp: Get_Timestamp(),
water_density_sg: water_density_sg,
water_ph: water_ph,
water_conductivity_usps_cm: water_conductivity_usps_cm,
water_turbidity_ntu: water_turbidity_ntu,
recycled_flow_t_hr: recycled_water_flow_t_hr,
fresh_flow_t_hr: fresh_water_flow_t_hr,
recycle_ratio_pct: recycle_ratio_pct,
acid_dose_kg_hr: acid_dose_kg_hr,
base_dose_kg_hr: base_dose_kg_hr,
flotation_recovery_pct: flotation_recovery_pct,
water_circuit_status: water_circuit_status
})
END IF
prev_recovery_pct = flotation_recovery_pct
END PROCEDURE
```
---
## 4. Tag List
```
WATER_DENSITY_SG { recycled header density }
WATER_DENSITY_ERROR_SG { deviation from setpoint }
WATER_PH { acidity/basicity }
WATER_PH_ERROR { vs. 8.5 setpoint }
WATER_CONDUCTIVITY_USPS_CM { ionic strength }
WATER_TURBIDITY_NTU { suspended solids }
RECYCLED_WATER_FLOW_T_HR { from thickener }
FRESH_WATER_FLOW_T_HR { makeup water }
FRESH_WATER_SETPOINT_T_HR { pump command }
RECYCLE_RATIO_PCT { 75% nominal }
ACID_DOSE_KG_HR { H₂SO₄ pump }
BASE_DOSE_KG_HR { NaOH pump }
FLOTATION_RECOVERY_PCT { downstream feedback }
WATER_CIRCUIT_STATUS { quality indicator }
SETTLING_WEIR_BACKFLUSH { command }
```
---
## 5. Alarm & Trip Matrix
| **Condition** | **Severity** | **Action** |
|---|---|---|
| **Density > 1.05 sg** | 🔴 CRIT | High fines; increase fresh water to 50% |
| **pH out ±0.3** | ⚠ WARN | Add acid or base to setpoint |
| **Conductivity > 5000 µS/cm** | ⚠ WARN | Reduce recycled ratio; check evaporation |
| **Turbidity > 100 NTU** | ⚠ WARN | Backflush settling weir; increase RT |
| **Recovery decline > 2%/day** | 🔴 CRIT | Increase fresh water; check chemistry |
---