Conveyor Belt Speed & Load Control — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 36 views
# Manufacturing Template: Conveyor Belt Speed & Load Control
## 1. Overview
**Purpose:**
Modular conveyor control with variable-frequency drive (VFD) motor, load sensing, anti-slip protection, and emergency stop interlocks. Common in packaging, food processing, automotive assembly, pharmaceutical manufacturing. Coordinates with upstream feeders and downstream equipment.
**Industry Standards:**
- ASME B20.1 (Safety Standard for Conveyors)
- NFPA 70 / IEC 61800-1 (VFD electrical safety)
- ISO 13849-1 (Machinery safety — control systems)
- ISO 13850 (Emergency stop / E-stop)
**Critical Constraints:**
- **Anti-slip threshold:** Product must not accelerate >0.5 m/s² relative to belt (prevent spillage or damage)
- **Load sensing:** Current-based load estimator; if current >85% rated, reduce speed or halt feed
- **Emergency stop:** Must de-energize motor AND engage mechanical brake within 0.5 sec
- **Jammed product detection:** If belt current spikes 150% of nominal, automatic reversal + alarm
- **Mechanical brake:** Spring-applied, power-released; holds belt at standstill
- **Belt speed range:** 0.1–2.0 m/s; typical setpoint 0.8–1.2 m/s
**Relevant Physics:**
- Motor torque: **τ = k_t × I_motor** (proportional to current; linear region <85% rated)
- Belt tension: **T = (μ × m_load × g) / radius** (friction balances weight)
- Slip condition: If acceleration > 0.5 m/s² and friction exhausted → slip occurs
- Power dissipation: **P = τ × ω = V_motor × I_motor** (if P increases rapidly = jam)
---
## 2. Control Philosophy
**Challenge:**
A high-speed conveyor with inbound products must accelerate products smoothly (avoid spillage), detect overload conditions (prevent motor burnout), and respond to emergency stops instantly. Fixed-speed operation causes jams; variable speed creates control complexity.
**Solution: Load-Adaptive VFD + Slip Detection**
```
Base Mode: Speed Regulation
- Target speed setpoint: 1.0 m/s (operator selectable 0.1–2.0)
- VFD ramp-up: +0.2 m/s per second (8 sec to reach full speed, prevents sudden jolts)
- Proportional-only control: Kp=0.15 (slow, smooth response for mechanical inertia)
- Feedback: Encoder speed (or tachometer); closed-loop maintains ±5% of setpoint
Load Monitoring:
- Measure motor current continuously
- If I_motor > 85% I_rated → "High Load" warning; reduce speed 10%
- If I_motor > 100% I_rated → "Overload" alarm; reduce speed 20% or stop
- If I_motor spikes >150% in <2 sec → "Jam Detected"; reverse belt 0.5 sec then stop
Anti-Slip Detection:
- Compare product acceleration (vision or proximity sensor) to belt acceleration
- If product lags belt by >0.2 m/s → slip condition; reduce speed 30%
- Once grip resumed → gradually restore speed (ramp +0.1 m/s per sec)
Emergency Stop:
- E-stop signal → immediate VFD off (motor coast to stop via mechanical inertia)
- Brake solenoid de-energizes → spring-applied brake grips belt
- Stop time: typically 2–5 seconds (friction deceleration)
- Recovery: operator acknowledges fault, restarts sequence
Feed Coordination:
- If "conveyor stopped" signal from upstream feeder, accept products but don't accelerate past 0.3 m/s
- If "output backed up" signal from downstream, reduce speed 50% (prevent overflow)
```
**Why this works:**
- Load-adaptive speed prevents motor burnout (most common failure mode)
- Ramp rate limiting (<0.2 m/s²) prevents product spillage (measured acceptability threshold)
- Slip detection via current monitoring catches bearing friction asymmetry early
- Jam reversal releases stuck products; manual inspection occurs before restart
---
## 3. Control Logic
**Pseudocode: Conveyor Master Control**
```pascal
{ === CONVEYOR BELT SPEED CONTROL === }
{ States: IDLE → RUNNING → OVERLOAD_FAULT / JAMMING / SLIP → IDLE }
PROCEDURE Conveyor_Belt_Master
CONSTANTS
SPEED_SETPOINT_DEFAULT = 1.0 { m/s }
RAMP_RATE_UP = 0.2 { m/s per second (0.2 m/s² accel) }
RAMP_RATE_DOWN = 0.3 { m/s per second (0.3 m/s² decel) }
SPEED_MIN = 0.1 { m/s, minimum practical speed }
SPEED_MAX = 2.0 { m/s, maximum safe speed }
LOAD_WARNING_THRESHOLD = 0.85 { 85% rated current }
LOAD_CRITICAL_THRESHOLD = 1.00 { 100% rated current }
JAM_DETECTION_THRESHOLD = 1.50 { 150% rated current spike }
JAM_DETECTION_RISE_TIME = 2.0 { seconds for current rise }
CURRENT_SMOOTHING_TIME = 5.0 { sec, moving average filter }
SLIP_THRESHOLD = 0.2 { m/s product lag vs. belt }
SLIP_SPEED_REDUCTION = 0.30 { 30% speed reduction on slip }
SPEED_RECOVERY_RATE = 0.1 { m/s per sec recovery }
ENCODER_COUNTS_PER_REV = 2048 { encoder resolution }
BELT_CIRCUMFERENCE_M = 1.57 { π × 0.5m pulley radius }
VARIABLES
state : ENUMERATION { IDLE, STARTING, RUNNING, OVERLOAD, JAM_REVERSING, E_STOP }
speed_setpoint : REAL { m/s, operator input or reduced by logic }
speed_actual : REAL { m/s, measured from encoder }
speed_command : REAL { m/s, target sent to VFD }
motor_current : REAL { A, scaled 0–200A range }
motor_current_filtered : REAL { A, moving average }
current_rise_rate : REAL { A per second }
load_warning_flag : BOOLEAN
load_critical_flag : BOOLEAN
jam_detected_flag : BOOLEAN
slip_detected_flag : BOOLEAN
cycle_timer : INTEGER { seconds }
jam_reversal_timer : INTEGER
vfd_frequency_cmd : REAL { Hz, 0–60 Hz for 60 Hz motor }
brake_solenoid_cmd : INTEGER { 0/1 = engaged/released }
BEGIN
{ === READ SENSORS === }
encoder_pulses = Read_Encoder_DI()
speed_actual = (encoder_pulses / ENCODER_COUNTS_PER_REV) × BELT_CIRCUMFERENCE_M / SCAN_INTERVAL_SEC
motor_current = Read_Current_AI() × (200.0 / 4095.0) { scale 4095 ADC counts → 200A }
{ === FILTER CURRENT (moving average, 5-sec window) === }
motor_current_filtered = 0.9 × motor_current_filtered + 0.1 × motor_current
current_rise_rate = (motor_current - motor_current_filtered) / SCAN_INTERVAL_SEC
{ === LOAD MONITORING === }
load_warning_flag := (motor_current_filtered > LOAD_WARNING_THRESHOLD × 200.0)
load_critical_flag := (motor_current_filtered > LOAD_CRITICAL_THRESHOLD × 200.0)
{ === JAM DETECTION === }
IF current_rise_rate > (JAM_DETECTION_THRESHOLD × 200.0 / JAM_DETECTION_RISE_TIME) THEN
jam_detected_flag = TRUE
ELSE
jam_detected_flag = FALSE
END IF
{ === SLIP DETECTION (if product presence sensor available) === }
product_speed := Read_Product_Speed_From_Vision() { m/s }
IF (speed_actual - product_speed) > SLIP_THRESHOLD THEN
slip_detected_flag = TRUE
ELSE
slip_detected_flag = FALSE
END IF
{ === STATE MACHINE === }
SELECT state
CASE IDLE:
speed_command := 0.0
vfd_frequency_cmd := 0.0
brake_solenoid_cmd := 0 { brake engaged, belt locked }
cycle_timer := 0
{ Start sequence when operator presses START or upstream feeder signals }
IF Conveyor_Start_Signal THEN
speed_setpoint := SPEED_SETPOINT_DEFAULT
state := STARTING
Log_Event("CONVEYOR_START_REQUESTED")
END IF
CASE STARTING:
{ === Ramp-up phase === }
IF speed_command < speed_setpoint THEN
speed_command := speed_command + RAMP_RATE_UP × SCAN_INTERVAL_SEC
speed_command := MIN(speed_command, speed_setpoint)
END IF
{ Soft-start: activate brake solenoid (release mechanical brake) }
brake_solenoid_cmd := 1
{ === Load check during ramp === }
IF load_critical_flag THEN
speed_command := speed_command × 0.8 { reduce speed 20% }
Log_Warning("LOAD_CRITICAL_DURING_RAMP")
END IF
{ === Transition to RUNNING when close to setpoint === }
IF ABS(speed_actual - speed_setpoint) < 0.05 THEN
state := RUNNING
Log_Event("CONVEYOR_RUNNING_AT_SPEED")
END IF
CASE RUNNING:
{ === Closed-loop speed control (proportional only) === }
speed_error = speed_setpoint - speed_actual
proportional_correction = Kp_run × speed_error { Kp=0.15 }
speed_command = speed_command + proportional_correction × SCAN_INTERVAL_SEC
speed_command := Clamp(speed_command, SPEED_MIN, speed_setpoint)
brake_solenoid_cmd := 1 { brake solenoid energized (brake released) }
{ === Handle high load conditions === }
IF load_critical_flag THEN
speed_setpoint := speed_setpoint × 0.8 { reduce operator setpoint by 20% }
Log_Warning("OVERLOAD_DETECTED", motor_current_filtered)
state := OVERLOAD
ELSIF load_warning_flag AND NOT load_warning_acknowledged THEN
{ Warning only; continue running }
Log_Warning("HIGH_LOAD", motor_current_filtered)
END IF
{ === Handle jam conditions === }
IF jam_detected_flag THEN
jam_detected_flag = TRUE
state := JAM_REVERSING
Log_Alarm("JAM_DETECTED_REVERSING")
END IF
{ === Handle slip conditions === }
IF slip_detected_flag THEN
speed_setpoint := speed_setpoint × (1.0 - SLIP_SPEED_REDUCTION)
slip_detected_flag = TRUE
Log_Warning("SLIP_CONDITION_REDUCING_SPEED")
ELSIF slip_detected_flag = FALSE AND speed_setpoint < SPEED_SETPOINT_DEFAULT THEN
{ Slip resolved; gradually restore speed }
speed_setpoint := speed_setpoint + SPEED_RECOVERY_RATE × SCAN_INTERVAL_SEC
speed_setpoint := MIN(speed_setpoint, SPEED_SETPOINT_DEFAULT)
END IF
{ === Downstream backup handling === }
IF Downstream_Backup_Signal THEN
speed_setpoint := speed_setpoint × 0.5 { reduce 50% }
END IF
CASE OVERLOAD:
{ === Load shedding / halt sequence === }
{ Speed command ramps down to stop }
IF speed_command > SPEED_MIN THEN
speed_command := speed_command - RAMP_RATE_DOWN × SCAN_INTERVAL_SEC
ELSE
speed_command := 0.0
END IF
{ === Wait for load to clear === }
cycle_timer := cycle_timer + 1
IF (NOT load_critical_flag) AND cycle_timer > 30 THEN { 30 sec wait }
state := IDLE
Log_Event("OVERLOAD_CLEARED_RETURNING_TO_IDLE")
speed_setpoint := SPEED_SETPOINT_DEFAULT
END IF
CASE JAM_REVERSING:
{ === Reverse belt to release trapped product === }
IF jam_reversal_timer < 5 THEN { 5 seconds of reverse }
speed_command := -0.5 { reverse at 0.5 m/s }
vfd_frequency_cmd := -25.0 { negative frequency for reverse }
jam_reversal_timer := jam_reversal_timer + 1
ELSE
{ Reverse complete; stop and alert }
speed_command := 0.0
vfd_frequency_cmd := 0.0
Log_Alarm("JAM_REVERSED_MANUAL_INSPECTION_REQUIRED")
state := IDLE
jam_reversal_timer := 0
END IF
CASE E_STOP:
{ === Emergency stop override === }
speed_command := 0.0
vfd_frequency_cmd := 0.0
brake_solenoid_cmd := 0 { de-energize solenoid; mechanical brake engages }
{ Coast-to-stop via mechanical friction }
cycle_timer := cycle_timer + 1
IF speed_actual < 0.05 AND cycle_timer > 10 THEN
state := IDLE
Log_Event("E_STOP_COMPLETE_BELT_HALTED")
END IF
END SELECT { state }
{ === PRIORITY OVERRIDE: EMERGENCY STOP === }
IF Emergency_Stop_Button_Pressed OR Fault_Trip_Signal THEN
state := E_STOP
speed_command := 0.0
vfd_frequency_cmd := 0.0
brake_solenoid_cmd := 0
Log_Alarm("EMERGENCY_STOP_ACTIVATED")
END IF
{ === CONVERT SPEED TO VFD FREQUENCY === }
{ VFD: 0–60 Hz = 0–2 m/s }
vfd_frequency_cmd := (speed_command / SPEED_MAX) × 60.0
vfd_frequency_cmd := Clamp(vfd_frequency_cmd, -30.0, 60.0)
{ === WRITE OUTPUTS === }
Set_VFD_Frequency_Command(vfd_frequency_cmd)
Set_Brake_Solenoid(brake_solenoid_cmd)
{ === DIAGNOSTICS / LOGGING === }
IF cycle_timer MOD 60 = 0 THEN { every 60 scan cycles = 1 minute }
Log_Diagnostic("SPEED_ACTUAL=" + STR(speed_actual) + " CURRENT=" + STR(motor_current_filtered))
END IF
END PROCEDURE
```
**Key Tuning Constants:**
```
Proportional gain (Kp_run) = 0.15
→ At ±0.1 m/s speed error, correction = 0.015 m/s per scan
→ Smooth response; no overshoot; settles in 5–10 scans (10–20 seconds)
Ramp rate = 0.2 m/s per second = 0.2 m/s²
→ Product acceleration = 0.2 m/s² well below slip threshold (0.5 m/s²)
→ 8 seconds to reach 1.6 m/s from standstill (safe acceleration)
Current filtering = 5-second moving average
→ Smooths noise from VFD switching (10 kHz PWM)
→ Allows legitimate current transients to pass through
```
---
## 4. Tag List
**Analog Inputs (Measurements)**
```
BELT_SPEED_ACTUAL { Encoder counts → m/s; 0–2 m/s range }
MOTOR_CURRENT_DRAW { CT transformer, 0–200 A; scaled 4–20 mA }
MOTOR_VOLTAGE_LINE { 3-phase line voltage monitor, 380–480V }
MOTOR_TEMPERATURE { RTD on motor frame, 0–80°C }
PRODUCT_SPEED_DETECTED { Vision or laser sensor, 0–2 m/s (if available) }
BELT_TENSION_ESTIMATE { Calculated from motor current and load model }
```
**Analog Outputs (Commands)**
```
VFD_FREQUENCY_COMMAND { 0–60 Hz (or -30 to +60 for reverse) }
BRAKE_SOLENOID_COMMAND { 0/1 = engaged/released }
UPSTREAM_FEEDER_SPEED_REQUEST { 0–100%, feedback to feeder control }
```
**Digital Inputs**
```
CONVEYOR_START_SIGNAL { 0/1, start button or external system }
CONVEYOR_STOP_SIGNAL { 0/1, stop button }
EMERGENCY_STOP_BUTTON { 0/1, E-stop button (hardwired) }
CONVEYOR_FAULT_RESET { 0/1, acknowledge and clear alarm }
DOWNSTREAM_EQUIPMENT_BACKUP { 0/1, signal = slow/stop conveyor }
UPSTREAM_FEEDER_READY { 0/1, ready to feed products }
MECHANICAL_BRAKE_ENGAGED { 0/1 feedback, brake status }
```
**Calculated / Diagnostic Tags**
```
SPEED_ERROR { m/s, setpoint - actual }
MOTOR_LOAD_PERCENT { 0–100%, current / rated }
CURRENT_RISE_RATE { A/sec, for jam detection }
STATE { IDLE / STARTING / RUNNING / OVERLOAD / JAM / E_STOP }
LOAD_WARNING_FLAG { Boolean, I > 85% }
LOAD_CRITICAL_FLAG { Boolean, I > 100% }
JAM_DETECTED_FLAG { Boolean, current spike >150% }
SLIP_CONDITION_FLAG { Boolean, product speed < belt speed }
CYCLE_TIMER { seconds, time in current state }
VFD_FREQUENCY_ACTUAL { Hz, feedback from VFD display }
ENCODER_COUNTS_PER_SAMPLE { raw pulse count per scan }
BELT_RUNTIME_HOURS { cumulative; maintenance tracking }
```
---
## 5. Alarm & Trip Matrix
| **Condition** | **Setpoint** | **Severity** | **Action** | **Recovery** |
|---|---|---|---|---|
| **Load Warning** | I > 85% rated | ⚠ WARN | Log, reduce speed 10% | Auto when I < 80% |
| **Load Critical** | I > 100% rated | 🔴 CRIT | Ramp down, go to OVERLOAD | Operator clears load, 30sec wait |
| **Jam Detected** | I spike >150% in <2 sec | 🔴 CRIT | Reverse belt 5 sec, halt | Manual inspection; restart required |
| **Slip Detected** | Product lag >0.2 m/s | ⚠ WARN | Reduce speed 30%, log | Auto-recover when grip resumes |
| **Motor Overtemp** | RTD >75°C | 🔴 CRIT | Stop conveyor, alert | Cool motor; resume after 10 min |
| **E-Stop Activated** | Button pressed OR fault trip | 🔴 CRIT | Brake solenoid de-energize, stop | Manual reset + acknowledge |
| **Brake Failure** | Solenoid current <100mA for 5 sec | 🔴 CRIT | Disable VFD, safety halt | Maintenance required |
| **Encoder Fault** | Speed stuck constant >10 sec | ⚠ WARN | Set speed to SAFE (0.3 m/s) | Verify encoder connection |
| **VFD Comm Loss** | No heartbeat >2 sec | 🔴 CRIT | E-stop equivalent (brake engage) | Restart VFD power |
| **Downstream Backup** | Backup signal continuous >5 min | ⚠ WARN | Run at 50% speed | Operator resolves downstream |
| **Voltage Sag** | 3-phase <360V for >5 sec | 🔴 CRIT | Stop and latch off | Wait for power recovery |
---
## 6. HMI Layout
**Main Conveyor Control Screen**
```
╔════════════════════════════════════════════════════════════════╗
║ CONVEYOR BELT SPEED & LOAD CONTROL — LINE A PACKAGING ║
╚════════════════════════════════════════════════════════════════╝
CURRENT STATE: [ RUNNING ] UPTIME: 14 hr 23 min RUNTIME: 1,247 hrs (total)
┌─────────────────────────────────────────────────────────────┐
│ SPEED CONTROL SETPOINT: 1.0 m/s │
│ │
│ ┌──────────────────────────────────────────────────────┐ │
│ │ 0.98 m/s (within ±0.05 m/s) │ │
│ │ 0─────●────2 m/s │ │
│ │ Load: 78% I_rated Motor: 156 A │ │
│ │ Ramp Rate: 0.2 m/s per sec [GREEN] │ │
│ └──────────────────────────────────────────────────────┘ │
│ │
│ LOAD MONITORING │
│ [████████░░░░░░░░░░░░] 78% of rated current (156 A / 200 A) │
│ │
│ ⚠ Above 85% threshold — Monitor closely │
│ ✓ No slip detected │
│ ✓ No jam detected │
│ │
│ BRAKE STATUS: [RELEASED] (solenoid energized) │
│ VFD FREQUENCY: 48.9 Hz (sends to 60 Hz motor) │
│ │
└─────────────────────────────────────────────────────────────┘
MOTOR HEALTH SYSTEM STATUS
Temp: 62°C ✓ Upstream Ready: ✓
Voltage: 415V ✓ Downstream Backed: ✗
Phase Balance: OK ✓ E-Stop Clear: ✓
BUTTONS:
[ Start ] [ Stop ] [ Speed ▼ / ▲ ] [ E-Stop ] [ Reset ]
TREND (Last 30 min):
┌──────────────────────────────────────────────────┐
│ 200 A │ │
│ 150 A │ ╱────────────────────── │
│ 100 A │╱ │
│ 50 A │ │
│ 0 │──────────────────────────────────────── │
│ └──────────────────────────────────────────┘
│ 0 10 20 30 min │
└──────────────────────────────────────────────────┘
```
**Speed Setpoint Adjustment (Operator Control)**
```
╔════════════════════════════════════════════════════════════════╗
║ SPEED SETPOINT ADJUSTMENT ║
╠════════════════════════════════════════════════════════════════╣
│ │
│ Current Setpoint: 1.0 m/s │
│ │
│ New Setpoint: [0.8_] m/s { range 0.1 to 2.0 } │
│ │
│ Ramp Rate: 0.2 m/s per sec (fixed; cannot adjust) │
│ │
│ [ CONFIRM CHANGE ] [ CANCEL ] │
│ │
╚════════════════════════════════════════════════════════════════╝
```
---
## 7. Configuration
**JSON Configuration (conveyor_belt_config.json)**
```json
{
"conveyor": {
"name": "Conveyor Belt A — Packaging Line",
"belt_circumference_m": 1.57,
"max_distance_m": 25.0,
"nominal_speed_mps": 1.0,
"max_speed_mps": 2.0,
"min_speed_mps": 0.1,
"ramp_up_rate_mps_per_sec": 0.2,
"ramp_down_rate_mps_per_sec": 0.3,
"scan_interval_ms": 200
},
"motor": {
"type": "3-phase AC induction",
"rated_power_kw": 7.5,
"rated_current_a": 15.0,
"rated_speed_rpm": 1800,
"pole_pairs": 2,
"vfd_frequency_range_hz": [0, 60],
"soft_start": true,
"brake_type": "spring_applied_power_released",
"brake_engagement_time_sec": 0.5
},
"sensors": {
"speed_encoder": {
"type": "incremental_rotary",
"counts_per_revolution": 2048,
"pulley_circumference_m": 0.785,
"di_channel": 0,
"di_channel_quad": 1
},
"motor_current": {
"type": "current_transformer_0_200a",
"ai_channel": 0,
"scaling": "linear",
"filter_time_constant_sec": 5.0
},
"motor_temperature": {
"type": "RTD_Pt100",
"ai_channel": 1,
"alarm_threshold_c": 75.0
},
"line_voltage_3phase": {
"type": "voltage_monitor_0_480v",
"ai_channel": 2,
"low_voltage_threshold_v": 360
},
"product_presence_vision": {
"type": "AI_camera_feed",
"estimated_speed_mps": "via image_processing",
"optional": true
}
},
"actuators": {
"vfd_drive": {
"type": "ABB_ACS380",
"rated_output_current_a": 15.0,
"ao_channel_frequency": 0,
"communication_protocol": "Modbus_RTU",
"baudrate_bps": 19200
},
"brake_solenoid": {
"type": "24VDC_solenoid",
"do_channel": 0,
"engage_action": "de_energize",
"release_action": "energize"
}
},
"control_parameters": {
"speed_regulation": {
"kp": 0.15,
"ki": 0.0,
"kd": 0.0,
"proportional_band_percent": 10.0
},
"load_management": {
"warning_threshold_percent_rated": 85,
"critical_threshold_percent_rated": 100,
"speed_reduction_on_warning": 0.10,
"speed_reduction_on_critical": 0.20
},
"jam_detection": {
"current_spike_threshold_percent": 150,
"rise_time_window_sec": 2.0,
"reversal_duration_sec": 5,
"reversal_speed_mps": 0.5
},
"slip_detection": {
"product_lag_threshold_mps": 0.2,
"slip_speed_reduction_factor": 0.30,
"recovery_ramp_rate_mps_per_sec": 0.1
}
},
"safety": {
"emergency_stop_response_sec": 0.5,
"motor_overheat_threshold_c": 80.0,
"brake_current_check_ma": 100,
"brake_current_timeout_sec": 5,
"e_stop_solenoid_de_energize_ms": 10,
"downstream_backup_speed_reduction": 0.50,
"encoder_loss_safe_speed_mps": 0.3
}
}
```
---
## 8. Implementation Checklist
### Pre-Commissioning (Days 1–2)
**Mechanical**
- [ ] Belt tension verified with torque wrench; tension = 50–100 N at midspan (depends on load)
- [ ] Pulley alignment checked with laser alignment tool; <1 mm runout acceptable
- [ ] Bearings lubricated per OEM spec; no grinding noise at full speed
- [ ] Mechanical brake tested manually; application force >500 N holds belt against weight
- [ ] Brake release solenoid bench-tested; pulls plunger at 24 VDC ±10%
**Electrical**
- [ ] 3-phase motor phase sequence verified (A→B→C rotation direction correct)
- [ ] VFD motor output terminals checked after soft-start board (should see PWM signal ~10 kHz)
- [ ] Current transformer secondary grounded (CT secondary short-circuit protection)
- [ ] Encoder connection to PLC verified; all 4 lines (power, GND, A, B) seated
- [ ] E-stop circuit hardwired directly to brake solenoid AND VFD stop input
**Software**
- [ ] Speed setpoint limits set: 0.1–2.0 m/s in HMI
- [ ] Ramp rate constants uploaded: RAMP_RATE_UP=0.2, RAMP_RATE_DOWN=0.3
- [ ] All alarm thresholds entered: warning 85%, critical 100%, jam 150%
- [ ] Manual speed control tested: slider 0–2 m/s → VFD frequency output changes linearly
### Hot Commissioning — Day 3 (No-Load Startup)
**Initial VFD Test (Belt Stationary)**
- [ ] Power VFD; confirm LED "ready" indicator
- [ ] Set frequency command to 10 Hz; verify motor doesn't rotate (no load/brake applied)
- [ ] Ramp frequency to 30 Hz; listen for smooth motor tone (no crackling)
- [ ] Reduce to 0 Hz; confirm smooth coast to stop (no clunking)
**Brake Solenoid Test**
- [ ] Energize solenoid with 24 VDC; confirm clunking noise (plunger pulls)
- [ ] De-energize; confirm spring action (belt held by friction)
- [ ] Verify current draw changes <50 mA on/off transition
**Speed Control Test (Belt Moving, No Product)**
- [ ] Release brake and start VFD at 10 Hz (0.33 m/s)
- [ ] Gradually increase frequency; verify speed increases smoothly
- [ ] At 30 Hz (1.0 m/s), verify speed stabilizes within ±5%
- [ ] Check encoder accuracy: count pulses; calculate speed; compare to displaywelcome
### Full Load Commissioning — Days 4–5 (With Products)
**Ramp-Up Phase Test**
- [ ] Start conveyor at low speed (0.3 m/s); manually place product on belt
- [ ] Verify product accelerates with belt; product acceleration <0.5 m/s² (no slip visible)
- [ ] Increase speed to 1.0 m/s; verify smooth ramp over 8 seconds
- [ ] Monitor current: should not exceed 50% during no-load acceleration
**Load Test**
- [ ] Run conveyor empty; measure baseline current (should be ~20–30 A)
- [ ] Add product weight; gradually increase to design load
- [ ] At 85% current (127 A), verify system reduces speed by 10% and logs warning
- [ ] At 100% current (150 A), verify system ramps to stop and transitions to OVERLOAD state
**Jam Test (Controlled)**
- [ ] Block belt with lever; motor current spikes
- [ ] Verify current rise >150% within 2 seconds → jam detection triggers
- [ ] Verify belt reverses at 0.5 m/s for 5 seconds
- [ ] Verify jam reversal completes; belt stops and waits for manual reset
**Slip Simulation (if vision available)**
- [ ] Load conveyor with low-friction product (plastic parts)
- [ ] Accelerate to 1.5 m/s; observe product slipping visibly behind belt
- [ ] Camera detects product speed <belt speed by 0.2 m/s
- [ ] Verify system reduces speed by 30% automatically
- [ ] Verify speed recovers gradually when slip ceases
**E-Stop Response Test**
- [ ] Belt running at 1.0 m/s
- [ ] Press E-stop button
- [ ] Measure time to stop: should be <5 seconds (mechanical friction deceleration)
- [ ] Verify solenoid de-energizes (heard release sound)
- [ ] Verify brake holds (manual push on belt should not move)
### Baseline Data (Days 6–7)
**24-Hour Run Recording**
- [ ] Log all transitions: IDLE → STARTING → RUNNING → OVERLOAD → IDLE
- [ ] Capture CSV: timestamp, speed_setpoint, speed_actual, motor_current, state
- [ ] Calculate: ramp time (should be consistent ≤10 sec), settling time (< 20 sec)
- [ ] Measure power consumption during 8-hour production run
---
## 9. Expected Performance
### Steady-State Speed Regulation
| **Metric** | **Target** | **Acceptable** | **Measured** |
|---|---|---|---|
| Speed setpoint accuracy | ±2% | ±5% | _______ |
| Speed ripple (oscillation) | <±0.02 m/s | <±0.05 m/s | _______ |
| Response to 20% load step | Settle <5 sec | Settle <15 sec | _______ |
| Motor current baseline | 25 A ±5 A | 20–35 A | _______ |
| Proportional band width | ±0.15 m/s | ±0.30 m/s | _______ |
### Ramp-Up Phase (0→1.0 m/s)
| **Metric** | **Target** | **Acceptable** | **Measured** |
|---|---|---|---|
| Total ramp time | 6–8 sec | <15 sec | _______ |
| Smoothness (no jerks) | Continuous | <2 visible jerks | _______ |
| Product acceleration | <0.5 m/s² | <0.8 m/s² | _______ |
| Overshoot above setpoint | None | <5% | _______ |
| Current during ramp | <40 A | <60 A | _______ |
### Load Handling
| **Metric** | **Target** | **Acceptable** | **Measured** |
|---|---|---|---|
| Load warning trigger | 85% I_rated (127 A) | ±5% | _______ |
| Load critical trigger | 100% I_rated (150 A) | ±5% | _______ |
| Speed reduction response | <3 sec | <10 sec | _______ |
| Jam detection current | 150% I_rated spike | ±10% | _______ |
| Jam reversal duration | 5 sec ±0.5 sec | 4–6 sec | _______ |
### System Reliability
| **Metric** | **Target** | **Measured** |
|---|---|---|
| Uptime (mean time between failures) | >200 hours | _______ |
| False jam detections per 100 hr | <2 | _______ |
| Encoder error rate | <0.1% | _______ |
| Motor thermal stability | ±3°C variation | _______ |
---
## 10. Advanced Variations
### 10.1 Multi-Zone Conveyor (Coordinated Speed)
If Line A feeds into Line B:
- Measure queue depth between zones (proximity sensors)
- If queue at junction >threshold, reduce downstream speed
- Feedforward upstream queue depth into speed setpoint calculation
### 10.2 Dynamic Load Balancing (Multiple Parallel Conveyors)
- Monitor load (current) on 4 parallel conveyor lines
- Distribute incoming product evenly: if Line A has high load, reduce speed; if Line B idle, increase speed
- Centralized load-balancing algorithm
### 10.3 Predictive Maintenance
- Track motor current trend over weeks
- If current increases >10% at same load → bearing wear; schedule inspection
- If encoder slip events increase → belt tension drifting; schedule tension check
### 10.4 Product Speed Matching (With Downstream Assembly)
- If downstream robot arm speed = 1.2 m/s, conveyor automatically matches 1.2 m/s
- Reduces product jitter at handoff
- Requires vision feedback or communication link to downstream PLC
---
**Document Version:** 1.0
**Last Updated:** 2026-04-13
**Status:** Ready for Production
**Approval:** Manufacturing Engineering (pending)