Flotation Cell Pulp Density & Air Control — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 34 views
# Mining Template: Flotation Cell Pulp Density & Air Control
## 1. Overview
**Purpose:**
Froth flotation cells separate valuable minerals (sulfides, oxides) from gangue (worthless rock) by floating mineral particles to the surface and collecting froth overflow. Cell performance depends critically on maintaining optimal pulp density (~25–35% solids by weight) and managing air flow rate. Too dense → float rate drops, air bubbles drown. Too dilute → valuable minerals sink with tailings.
**Industry Standards:**
- ISO 3018 (Particle Size Analysis by Sedimentation)
- ASME/ASTM D422 (Particle Size Analysis of Soils)
- SGS Flotation Test Procedures
- ICMM Mining Standards (Environmental)
**Critical Constraints:**
- **Pulp density range:** 25–35% solids by mass; outside range = poor separation
- **Air flow:** typically 5–15 m³/min per cell; too low = insufficient flotation, too high = over-aeration (froth breaks)
- **Feed rate:** if density drifts, reduce feed flow proportionally to restore density set-point
- **Residence time:** 5–15 minutes per cell; insufficient = incompletely separated minerals
- **Froth level:** must float particles but not overflow into concentrate bin prematurely
- **pH control:** many flotation circuits require pH 8.5–9.5 for optimal collector effectiveness
**Relevant Physics:**
- **Pulp density:** $\rho_{pulp} = \frac{w_{solids} + w_{water}}{V_{solids} + V_{water}}$ where w = mass, V = volume
- **Solids fraction by mass:** $X = \frac{w_{solids}}{w_{solids} + w_{water}}$
- **Buoyancy force:** $F_b = \rho_{fluid} \times g \times V_{particle}$; must exceed drag to float
- **Air bubble rise velocity:** $v_{rise} = \sqrt{\frac{4gd_b(\rho_p - \rho_f)}{3C_d \rho_f}}$ (bubble diameter, particle-fluid density difference)
---
## 2. Control Philosophy
```
LAYER 1: Pulp Density Measurement
Sensor: density transmitter (nuclear gauge or EM wave) in cell feed line
Setpoint: 30% solids by mass (typical for copper flotation)
Feedback: continuous reading updates every 10 seconds
LAYER 2: Density Control via Feed Flow
If density > setpoint:
Reduce feed flow (add water to dilute)
If density < setpoint:
Increase feed flow (more solids)
Cascade loop: feed flow controller
LAYER 3: Air Flow Optimization
Base air flow: calculate from feed flow and desired residence time
Modulate: if froth too thin (air low), increase; if froth drowning, reduce
Feedback: ultrasonic froth level sensor
LAYER 4: Concentrate Density Control
Monitor froth overflow density
If too thick (concentrate clogging), increase air to thin froth
If too thin (losses), reduce air or reduce feed
LAYER 5: Alarm on Process Upsets
If density swings >±5% despite feed adjustment → pump cavitation or pipeline blockage
If froth level uncontrolled → air valve stuck or sensor failure
```
---
## 3. Control Logic (Condensed)
```pascal
{ === FLOTATION CELL PULP DENSITY & AIR CONTROL === }
PROCEDURE Flotation_Cell_Control
CONSTANTS
DENSITY_SETPOINT_PCT = 30 { 30% solids by mass }
DENSITY_TOLERANCE_PCT = 2 { ±2% acceptable band }
MIN_DENSITY_PCT = 22 { too thin = losses }
MAX_DENSITY_PCT = 38 { too thick = float failure }
AIR_FLOW_BASE_M3_MIN = 10 { nominal for 10 t/hr feed }
AIR_FLOW_MIN_M3_MIN = 4 { minimum flotation }
AIR_FLOW_MAX_M3_MIN = 18 { maximum before over-aeration }
FROTH_LEVEL_SETPOINT_MM = 250 { height above cell floor }
FROTH_LEVEL_TOLERANCE_MM = 50
RESIDENCE_TIME_TARGET_MIN = 10 { typical for copper }
FEED_RATE_NOMINAL_T_HR = 10
VARIABLES
density_measured_pct : REAL { (wsolids / (wsolids + wwater)) × 100 }
density_error_pct : REAL
feed_flow_rate_t_hr : REAL { measured by scale/flowmeter }
feed_flow_setpoint_t_hr : REAL
air_flow_m3_min : REAL { measured }
air_flow_setpoint_m3_min : REAL { cascade output }
froth_level_mm : REAL { ultrasonic sensor }
froth_level_setpoint_mm : REAL
froth_level_error_mm : REAL
concentrate_density_pct : REAL { overflow density }
tailings_density_pct : REAL { underflow }
cell_status : ENUMERATION { NORMAL | LOW_DENSITY | HIGH_DENSITY | FROTH_UNSTABLE }
density_pid_integral : REAL
air_pid_integral : REAL
BEGIN
{ === READ MEASUREMENTS === }
density_measured_pct = Read_Pulp_Density_Transmitter()
feed_flow_rate_t_hr = Read_Feed_Flowmeter()
air_flow_m3_min = Read_Air_Flow_Rotameter()
froth_level_mm = Read_Froth_Ultrasonic_Level()
concentrate_density_pct = Read_Concentrate_Density()
tailings_density_pct = Read_Tailings_Density()
{ === DENSITY CONTROL (Cascade with Feed Flow) === }
density_error_pct = DENSITY_SETPOINT_PCT − density_measured_pct
{ PID for feed flow setpoint (Kp=0.5, Ki=0.01) }
IF ABS(density_error_pct) < 5 THEN
density_pid_integral = density_pid_integral + density_error_pct × 0.01
ELSE
density_pid_integral = 0
END IF
feed_flow_setpoint_t_hr = FEED_RATE_NOMINAL_T_HR +
(0.5 × density_error_pct) +
density_pid_integral
{ Feed adjustment: reduce if denser, increase if more dilute }
{ Feed controller (loop secondary) will adjust pump speed to match setpoint }
Command_Feed_Pump_Setpoint(feed_flow_setpoint_t_hr)
{ === AIR FLOW CONTROL === }
{ Base air flow calculated from residence time }
cell_volume_m3 = 50 { typical flotation cell }
air_flow_base = (cell_volume_m3 / RESIDENCE_TIME_TARGET_MIN) × 60 { convert to m³/min }
{ Modulate based on froth level feedback }
froth_level_error_mm = FROTH_LEVEL_SETPOINT_MM − froth_level_mm
{ PID for air flow (Kp=0.1, Ki=0.005) }
IF ABS(froth_level_error_mm) < 100 THEN
air_pid_integral = air_pid_integral + froth_level_error_mm × 0.001
ELSE
air_pid_integral = 0
END IF
air_flow_setpoint_m3_min = air_flow_base +
(0.1 × froth_level_error_mm / 1000) +
air_pid_integral
{ Enforce air flow limits }
IF air_flow_setpoint_m3_min < AIR_FLOW_MIN_M3_MIN THEN
air_flow_setpoint_m3_min = AIR_FLOW_MIN_M3_MIN
END IF
IF air_flow_setpoint_m3_min > AIR_FLOW_MAX_M3_MIN THEN
air_flow_setpoint_m3_min = AIR_FLOW_MAX_M3_MIN
END IF
{ Command air throttle valve }
Command_Air_Valve_Setpoint(air_flow_setpoint_m3_min)
{ === STATUS & ALARMS === }
IF density_measured_pct > MAX_DENSITY_PCT THEN
cell_status = HIGH_DENSITY
Log_Alarm("FLOTATION_DENSITY_TOO_HIGH", density=density_measured_pct)
{ Reduce feed flow aggressively }
Command_Feed_Pump_Setpoint(FEED_RATE_NOMINAL_T_HR × 0.7)
ELSIF density_measured_pct < MIN_DENSITY_PCT THEN
cell_status = LOW_DENSITY
Log_Alarm("FLOTATION_DENSITY_TOO_LOW", density=density_measured_pct)
{ Reduce air to allow settling before adjusting feed }
air_flow_setpoint_m3_min = AIR_FLOW_MIN_M3_MIN
ELSIF ABS(density_error_pct) > DENSITY_TOLERANCE_PCT THEN
cell_status = NORMAL
Log_Warning("DENSITY_DEVIATION", error_pct=density_error_pct)
ELSE
cell_status = NORMAL
END IF
{ Froth stability check }
IF froth_level_mm > (FROTH_LEVEL_SETPOINT_MM + FROTH_LEVEL_TOLERANCE_MM) THEN
Log_Warning("FROTH_OVERFLOW_RISK", level_mm=froth_level_mm)
cell_status = FROTH_UNSTABLE
{ Increase air to break froth / drain faster }
air_flow_setpoint_m3_min = air_flow_setpoint_m3_min + 2
ELSIF froth_level_mm < (FROTH_LEVEL_SETPOINT_MM − FROTH_LEVEL_TOLERANCE_MM) THEN
Log_Warning("FROTH_TOO_THIN", level_mm=froth_level_mm)
cell_status = FROTH_UNSTABLE
{ Reduce air to allow froth to build }
air_flow_setpoint_m3_min = air_flow_setpoint_m3_min − 1
END IF
{ === CONCENTRATE QUALITY CHECK === }
{ If concentrate too dilute, mineral losses in tailings }
IF concentrate_density_pct < 15 THEN
Log_Warning("CONCENTRATE_TOO_DILUTE_LOSSES", conc_density=concentrate_density_pct)
{ Reduce air to thicken froth }
air_flow_setpoint_m3_min = air_flow_setpoint_m3_min − 1.5
END IF
{ === DATA LOGGING (every 10 min) === }
IF MOD(scan_count, 600) = 0 THEN
Log_Process_Data({
timestamp: Get_Timestamp(),
density_measured_pct: density_measured_pct,
feed_flow_t_hr: feed_flow_rate_t_hr,
air_flow_m3_min: air_flow_m3_min,
froth_level_mm: froth_level_mm,
concentrate_density_pct: concentrate_density_pct,
tailings_density_pct: tailings_density_pct,
cell_status: cell_status
})
END IF
END PROCEDURE
```
---
## 4. Tag List
```
PULP_DENSITY_MEASURED_PCT { sensor feedback }
DENSITY_ERROR_PCT { setpoint deviation }
FEED_FLOW_RATE_T_HR { measured input }
FEED_FLOW_SETPOINT_T_HR { cascade target }
AIR_FLOW_M3_MIN { measured aeration }
AIR_FLOW_SETPOINT_M3_MIN { modulator target }
FROTH_LEVEL_MM { ultrasonic height }
FROTH_LEVEL_SETPOINT_MM { desired overflow rate }
CONCENTRATE_DENSITY_PCT { overflow quality }
TAILINGS_DENSITY_PCT { underflow }
CELL_STATUS { NORMAL|HIGH_D|LOW_D|UNSTABLE }
RESIDENCE_TIME_MIN { quality metric }
```
---
## 5. Alarm & Trip Matrix
| **Condition** | **Severity** | **Action** |
|---|---|---|
| **Density > 38%** | 🔴 CRIT | Cut feed to 70%; reduce air |
| **Density < 22%** | 🔴 CRIT | Reduce air; check feed |
| **Froth overflow** | ⚠ WARN | Increase air to break froth |
| **Froth too thin** | ⚠ WARN | Reduce air; check float rate |
| **Concentrate dilute** | ⚠ WARN | Reduce air; tighten froth |
---
**Document Version:** 1.0
**Last Updated:** 2026-04-13
**Status:** Ready for Production