Paint Mixing 3 Component — PLC Control Template

Shared by TSIMEREZIVO Team · 4 Oct 2026 · 35 views

# Paint Mixing 3 Component — Usage Guide ## Overview Three-component paint batching using loadcell-based gravimetric dosing and an agitator mix phase. Component ratios must total 100% before the sequence can start. ## Commissioning 1. Verify loadcell calibration at empty and test weights 2. Confirm each doser shuts off at its batch mass target 3. Validate agitator mix time for product homogeneity --- ## Control Logic — Vendor-Agnostic Pseudocode # Paint Mixing 3 Component — Logic ## Standards: IEC 61131-3 | ISA-88 | ISA-18.2 ## Scan Rate: 100ms | Pattern: recipe ratio dosing with agitator ``` ROUTINE: PaintMixingThreeComponent SCAN_RATE: 100ms // SECTION 1 — BATCH TARGET CALCULATION TARGET_A := BATCH_TOTAL_KG * RATIO_A / 100.0 TARGET_B := BATCH_TOTAL_KG * RATIO_B / 100.0 TARGET_C := BATCH_TOTAL_KG * RATIO_C / 100.0 RATIO_VALID := ABS((RATIO_A + RATIO_B + RATIO_C) - 100.0) <= 0.1 IF NOT RATIO_VALID THEN SET_ALARM(ALM_RATIO_INVALID, HIGH) END_IF // SECTION 2 — ISA-88 STYLE SEQUENCE CASE SEQ_STATE OF 0: IF START_CMD AND RATIO_VALID THEN SEQ_STATE := 1; CURRENT_WEIGHT := 0.0 END_IF 1: DOSER_A_CMD := CURRENT_WEIGHT < TARGET_A; IF CURRENT_WEIGHT >= TARGET_A THEN DOSER_A_CMD := FALSE; SEQ_STATE := 2 END_IF 2: DOSER_B_CMD := CURRENT_WEIGHT < (TARGET_A + TARGET_B); IF CURRENT_WEIGHT >= (TARGET_A + TARGET_B) THEN DOSER_B_CMD := FALSE; SEQ_STATE := 3 END_IF 3: DOSER_C_CMD := CURRENT_WEIGHT < (TARGET_A + TARGET_B + TARGET_C); IF CURRENT_WEIGHT >= (TARGET_A + TARGET_B + TARGET_C) THEN DOSER_C_CMD := FALSE; SEQ_STATE := 4 END_IF 4: AGITATOR_CMD := TRUE; MIX_TMR := MIX_TMR + 1; IF MIX_TMR >= MIX_TIME_TICKS THEN AGITATOR_CMD := FALSE; MIX_TMR := 0; SEQ_STATE := 5 END_IF 5: COMPLETE := TRUE; IF ACK_CMD THEN COMPLETE := FALSE; SEQ_STATE := 0 END_IF END_CASE // SECTION 3 — ALARMS IF LOADCELL_FAULT THEN SET_ALARM(ALM_LOADCELL_FAULT, HIGH) END_IF IF ESTOP_ACTIVE THEN SET_ALARM(ALM_ESTOP, CRITICAL) END_IF // SECTION 4 — HMI OUTPUTS HMI_SEQ_STATE := SEQ_STATE HMI_WEIGHT := CURRENT_WEIGHT HMI_TARGET_TOTAL := TARGET_A + TARGET_B + TARGET_C END_ROUTINE ``` --- ## Tag List ```csv Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address START_CMD,Batch Start Command,BOOL,input,,,,FALSE, ACK_CMD,Batch Complete Acknowledge,BOOL,input,,,,FALSE, ESTOP_ACTIVE,E-Stop Active,BOOL,input,,,,FALSE,DI:0:0.0 LOADCELL_FAULT,Loadcell Fault,BOOL,input,,,,FALSE,DI:0:0.1 CURRENT_WEIGHT,Current Vessel Weight,REAL,input,kg,0,10000,0,AI:0:0.0 BATCH_TOTAL_KG,Requested Batch Total,REAL,input,kg,0,10000,100, RATIO_A,Component A Ratio,REAL,input,%,0,100,50, RATIO_B,Component B Ratio,REAL,input,%,0,100,30, RATIO_C,Component C Ratio,REAL,input,%,0,100,20, RATIO_VALID,Recipe Ratio Sum Valid,BOOL,calculated,,,,FALSE, TARGET_A,Component A Target Mass,REAL,calculated,kg,0,10000,0, TARGET_B,Component B Target Mass,REAL,calculated,kg,0,10000,0, TARGET_C,Component C Target Mass,REAL,calculated,kg,0,10000,0, SEQ_STATE,Batch Sequence State,INT,internal,,0,5,0, DOSER_A_CMD,Component A Doser Command,BOOL,output,,,,FALSE,DO:1:0.0 DOSER_B_CMD,Component B Doser Command,BOOL,output,,,,FALSE,DO:1:0.1 DOSER_C_CMD,Component C Doser Command,BOOL,output,,,,FALSE,DO:1:0.2 AGITATOR_CMD,Agitator Run Command,BOOL,output,,,,FALSE,DO:1:0.3 MIX_TMR,Mix Timer,INT,internal,,0,100000,0, MIX_TIME_TICKS,Mix Duration (100ms ticks),INT,internal,,0,100000,1800, COMPLETE,Batch Complete Flag,BOOL,internal,,,,FALSE, ALM_RATIO_INVALID,Recipe Ratios Do Not Total 100%,BOOL,calculated,,,,FALSE, ALM_LOADCELL_FAULT,Loadcell Fault Alarm,BOOL,calculated,,,,FALSE, ALM_ESTOP,E-Stop Alarm,BOOL,calculated,,,,FALSE, HMI_SEQ_STATE,HMI: Sequence State,INT,output,,0,5,0, HMI_WEIGHT,HMI: Current Weight,REAL,output,kg,0,10000,0, HMI_TARGET_TOTAL,HMI: Total Target Weight,REAL,output,kg,0,10000,0, ``` --- ## Alarm Matrix ```csv Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge ALM_ESTOP,ESTOP_ACTIVE = TRUE,N/A,critical,safety,Emergency stop active. Batch motion stopped immediately.,0s,No ALM_LOADCELL_FAULT,LOADCELL_FAULT = TRUE,N/A,high,equipment,Weight signal unreliable. Stop dosing and inspect instrumentation.,0s,No ALM_RATIO_INVALID,RATIO_VALID = FALSE,100% required,high,process,Recipe ratio sum invalid. Correct recipe before starting batch.,0s,Yes ```

More like this

Rate, comment, and get full access

Members can download files, rate contributions, and discuss fixes with the engineers who posted them — free.

Join the library