Pipeline Flow Metering & Leak Detection — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 35 views
# Oil & Gas Template: Pipeline Flow Metering & Leak Detection
## 1. Overview
**Purpose:**
Continuously measure crude/gas flow through transmission pipeline (orifice plate, turbine, or ultrasonic meter) and detect leaks by comparing expected flow (from surface + subsurface meters) against actual outlet flow. A 2% daily discrepancy (100 bopd on 5000 bopd line) could indicate a crack, corrosion hole, or theft.
**Industry Standards:**
- API 14.1 (Design of Onshore Drilling Mud Treatment Systems)
- ISO 2186 (Measurement of Fluid Flow — Orifice Plates)
- ASME B39.1 (Nonmetallic Tube Fittings)
- AGA Report 3 (Orifice Metering for Natural Gas)
- ISO 9951 (Turbine Flow Meter)
**Critical Constraints:**
- **Orifice plate accuracy:** ±1–2% at design flow; drops to ±3–5% at 50% flow
- **Temperature compensation:** meter factor = k(T); oil meters sensitive to T shifts (±0.5% per 5°C)
- **Pressure drop:** orifice creates ΔP = meter reading; large lines must minimize parasitic loss
- **Meter factor drift:** orifice degrades over 2–3 years (erosion, deposits); periodic calibration required
- **Leak threshold:** operators typically alert on >1–2% unexplained loss
- **Detection lag:** pressure drops take 30 sec – 5 min to propagate down long pipeline; flow doesn't reflect immediately
**Relevant Physics:**
- **Orifice flow:** $Q = C_d × A × \sqrt{2 \times \Delta P / \rho}$ (Cd ≈ 0.6–0.65 for sharp-edge orifices)
- **Compressibility factor (Z):** real gas correction: $Z = 1 - \frac{BRT}{V}$ (virial coefficients)
- **Temperature viscosity:** meter output may require T correction: $Q_{corrected} = Q × f(T)$
---
## 2. Control Philosophy
```
LAYER 1: Multi-Point Flow Measurement
Points: Wellhead + subsurface + mid-pipeline + export header
Benefits: triangulate leak location (if any)
LAYER 2: Mass Balance Check
Input: sum of all inlet sources
Output: sum of all outlet flows
Expected = Measured? If not, leak exists
LAYER 3: Leak Localization
If inlet flow > outlet flow:
Is leak pre-meter-1 or post-meter-1?
Compare: wellhead − meter-1 vs. meter-1 − meter-2 etc.
LAYER 4: Pressure Profile Warning
If pressure drops abnormally at single location → localize via spatial derivative
```
---
## 3. Control Logic (Condensed)
```pascal
{ === PIPELINE FLOW METERING & LEAK DETECTION === }
PROCEDURE Pipeline_Leak_Detection_Master
CONSTANTS
NUM_METERS = 4 { wellhead, mid1, mid2, export }
METER_ACCURACY_PCT = 2.0 { orifice plate }
ACCEPTABLE_LOSS_PCT = 1.5 { 1.5% materialbalance error OK }
LEAK_ALARM_THRESHOLD_PCT = 2.0 { >2% triggers alert }
CONFIDENCE_WINDOW_HOURS = 2 { need 2 hrs stable flow for diagnosis }
VARIABLES
flow_measured_bopd[1..NUM_METERS] : REAL
flow_prev_bopd[1..NUM_METERS] : REAL
pressure_psi[1..NUM_METERS] : REAL
temperature_f[1..NUM_METERS] : REAL
mass_balance_input_bopd : REAL { sum of all sources }
mass_balance_output_bopd : REAL { sum of all sinks }
unaccounted_loss_pct : REAL
meter_k_factor[1..NUM_METERS] : REAL { calibration factor }
leak_detected : BOOLEAN
leak_location_segment : STRING { "well-to-mid1" etc }
leak_severity : ENUMERATION { MINOR | MODERATE | MAJOR | CRITICAL }
BEGIN
FOR m = 1 TO NUM_METERS DO
{ Read each meter }
flow_measured_bopd[m] = Read_Flow_Meter(m) { impulse / electronic }
pressure_psi[m] = Read_Pressure_Transmitter(m)
temperature_f[m] = Read_Temperature_Sensor(m)
{ Apply temperature correction to meter factor }
IF temperature_f[m] < > temperature_prev_f[m] THEN
RECALC_METER_K_FACTOR(m, temperature_f[m])
END IF
{ Apply calibration factor }
flow_measured_bopd[m] = flow_measured_bopd[m] × meter_k_factor[m]
END FOR
{ === MASS BALANCE CHECK === }
mass_balance_input_bopd = SUM(flow_measured_bopd[1..2]) { sources }
mass_balance_output_bopd = SUM(flow_measured_bopd[3..4]) { sinks }
unaccounted_loss_pct = ABS((mass_balance_input - mass_balance_output) / mass_balance_input) × 100
{ === LEAK DETECTION LOGIC === }
IF unaccounted_loss_pct > ACCEPTABLE_LOSS_PCT THEN
{ Possible leak; need to localize }
leak_detected = TRUE
{ Segment 1: wellhead to mid1 }
segment_1_loss = ABS(flow_measured_bopd[1] − flow_measured_bopd[2])
segment_1_loss_pct = (segment_1_loss / flow_measured_bopd[1]) × 100
{ Segment 2: mid1 to mid2 }
segment_2_loss = ABS(flow_measured_bopd[2] − flow_measured_bopd[3])
segment_2_loss_pct = (segment_2_loss / flow_measured_bopd[2]) × 100
{ Segment 3: mid2 to export }
segment_3_loss = ABS(flow_measured_bopd[3] − flow_measured_bopd[4])
segment_3_loss_pct = (segment_3_loss / flow_measured_bopd[3]) × 100
{ Find which segment is losing most }
IF segment_1_loss_pct > LEAK_ALARM_THRESHOLD_PCT THEN
leak_location_segment = "WELLHEAD_TO_MID1"
leak_severity = CRITICAL
ELSIF segment_2_loss_pct > LEAK_ALARM_THRESHOLD_PCT THEN
leak_location_segment = "MID1_TO_MID2"
leak_severity = MAJOR
ELSIF segment_3_loss_pct > LEAK_ALARM_THRESHOLD_PCT THEN
leak_location_segment = "MID2_TO_EXPORT"
leak_severity = MODERATE
ELSE
{ No single segment shows >2%, but total is high }
{ Possible distributed weeping or meter errors }
leak_location_segment = "DISTRIBUTED_OR_METERING"
leak_severity = MINOR
END IF
Log_Alarm("LEAK_DETECTED", segment=leak_location_segment, loss_pct=unaccounted_loss_pct)
ELSE
leak_detected = FALSE
END IF
{ === PRESSURE PROFILE ANALYSIS === }
{ If pressure drops sudden between two meters, likely restriction or small rupture }
FOR m = 1 TO NUM_METERS − 1 DO
pressure_drop_psi = pressure_psi[m] − pressure_psi[m+1]
expected_drop_psi = Get_Expected_Pressure_Drop(m, flow_measured_bopd[m])
IF pressure_drop_psi > expected_drop_psi × 1.2 THEN { 20% higher than expected }
Log_Warning("ABNORMAL_PRESSURE_DROP_SEGMENT_" + STR(m),
measured_drop=pressure_drop_psi, expected=expected_drop_psi)
END IF
END FOR
{ === METER DRIFT DETECTION === }
{ Over 2 hours, meter output should be stable ±0.5% }
IF MOD(scan_count, 240) = 0 THEN { every 2 hours }
FOR m = 1 TO NUM_METERS DO
hourly_avg = Average(flow_measured_bopd[m], last_60_minutes)
hourly_drift_pct = ABS(flow_measured_bopd[m] − hourly_avg) / hourly_avg × 100
IF hourly_drift_pct > 5 THEN { >5% swing }
Log_Warning("METER_DATA_NOISY_OR_INSTABLE", meter=m, drift_pct=hourly_drift_pct)
END IF
END FOR
END IF
{ === LOGGING === }
IF MOD(scan_count, 60) = 0 THEN { every 1 hr }
Log_Process_Data({
timestamp: Get_Timestamp(),
flow_bopd: flow_measured_bopd[],
pressure_psi: pressure_psi[],
temperature_f: temperature_f[],
mass_balance_loss_pct: unaccounted_loss_pct,
leak_detected: leak_detected,
leak_location: leak_location_segment
})
END IF
flow_prev_bopd[] := flow_measured_bopd[]
END PROCEDURE
```
---
## 4. Tag List
```
FLOW_METER_1_WELLHEAD_BOPD { source flow }
FLOW_METER_2_MID1_BOPD { first check point }
FLOW_METER_3_MID2_BOPD { second check point }
FLOW_METER_4_EXPORT_BOPD { sink measurement }
PRESSURE_SEGMENT_1_PSI { between meters 1 & 2 }
TEMPERATURE_METER_1_F { for meter factor correction }
MASS_BALANCE_INPUT_BOPD { total sourced }
MASS_BALANCE_OUTPUT_BOPD { total exported }
UNACCOUNTED_LOSS_PCT { leak indicator }
LEAK_DETECTED { boolean alarm }
LEAK_LOCATION_SEGMENT { geographic hint }
METER_DRIFT_PCT { stability check }
```
---
## 5. Alarm & Trip Matrix
| **Condition** | **Severity** | **Action** |
|---|---|---|
| **Loss > 2%** | 🔴 CRIT | Leak localization; dispatch inspection |
| **Pressure drop anomaly** | ⚠ WARN | Check segment; possible blockage |
| **Meter drift >5%** | ⚠ WARN | Meter possibly fouled; schedule maintenance |
---
**Document Version:** 1.0
**Last Updated:** 2026-04-13
**Status:** Ready for Production