I/O Rack & Module Mapping — Engineering Guide
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 39 views
#
I/O Rack & Module Mapping
Before writing a single line of PLC logic, you need a complete I/O map — which chassis slot
holds which module, and which terminal screw connects to which process instrument.
TSIMEREZIVO builds this map for you, generates a terminal schedule for electricians,
and automatically creates tags from channel assignments.
14 min
## Chassis Slot Numbering
Most rack-based PLCs (ControlLogix, CompactLogix, S7-300/400) number slots from left to right
starting at slot 0. Slot 0 is always the CPU module. Expansion modules fill slots 1+.
Remote I/O racks connected via EtherNet/IP or DP are identified by a rack number (0, 1, 2…).
Rack 0 — Local Chassis (Allen-Bradley ControlLogix 1756)
| slot | type | mod | label |
|---|---|---|---|
| 0 | CPU | 1756-L83E | Controller |
| 1 | ENET | 1756-EN2T | EtherNet |
| 2 | DI | 1756-IA16 | 16x DI |
| 3 | DO | 1756-OA16 | 16x DO |
| 4 | AI | 1756-IF16 | 16x AI |
| 5 | AO | 1756-OF8 | 8x AO |
| 6 | HSC | 1756-HSC | Hi-Speed |
| 7 | DI | 1756-IA16 | 16x DI |
| 8 | DO | 1756-OA16 | 16x DO |
| 9 | | (empty) | |
## Module Types Reference
| type | name | desc | addr |
|---|---|---|---|
| DI | Digital Input | 24VDC/120VAC discrete input. Used for switches, proximity sensors, motor status, valve limit switches. | %IX0.0 |
| DO | Digital Output | 24VDC/120VAC relay or transistor output. Drives motor starters, solenoid valves, pilot lights. | %QX0.0 |
| AI | Analogue Input | 4–20mA or 0–10V. Used for temperature (4–20mA from transmitter), pressure, flow, level. Converts to engineering units via scaling. | %IW0 |
| AO | Analogue Output | 4–20mA or 0–10V. Drives VFDs, control valves, positioners. Output span 0–27648 (Siemens) or 0–16383 (Allen-Bradley). | %QW0 |
| HSC | High-Speed Counter | Quadrature encoder input for flow meters, position feedback. Up to 1MHz count rate. Generates COUNT, RATE tags. | %IW0 |
| RTD | RTD Input | Pt100/Pt1000 resistance input for temperature. More accurate than 4–20mA over short distances. Direct Ω measurement. | %IW0 |
| TC | Thermocouple Input | J, K, T, E, R, S type thermocouple. Input module linearises mV signal to °C/°F. CJC (cold-junction compensation) is automatic. | %IW0 |
## IEC 61131-3 Addressing
> **IEC 61131-3 Direct Address Format** —
IEC 61131-3 defines the variable prefix that maps to hardware:
- `%I` = Input, `%Q` = Output, `%M` = Memory (internal)
- `X` = 1-bit (BOOL), `B` = 8-bit, `W` = 16-bit, `D` = 32-bit, `L` = 64-bit
- Syntax: `%IX[byte].[bit]` for digital, `%IW[word]` for analogue
```text
%IX0.0 Digital Input — Byte 0, Bit 0 (first DI channel)
%IX0.7 Digital Input — Byte 0, Bit 7 (8th DI channel)
%QX0.0 Digital Output — Byte 0, Bit 0 (first DO channel)
%IW0 Analogue Input — Word 0 (raw 0–27648 or 0–32767)
%QW0 Analogue Output— Word 0 (4–20mA output)
(* Allen-Bradley uses tag-based addressing, not IEC direct addressing.
ControlLogix: Local:2:I.Data[3] = Slot 2, AI Channel 3 raw value *)
Local:4:I.Data[0] (* Slot 4 AI Module, Channel 0 raw count *)
Local:3:O.Data[0] (* Slot 3 DO Module, Channel 0 output bit *)
Local:5:O.Data[0] (* Slot 5 AO Module, Channel 0 raw output *)
```
## Channel-to-Tag Assignment in TSIMEREZIVO
### Step 1 — Open I/O Mapping
Navigate to **Equipment → [Select PLC] → I/O Map**.
The I/O Map shows all modules in the chassis. Click a module to expand its channels.
### Step 2 — Assign Tags to Channels
For each channel, click **Assign Tag**.
Search for an existing tag, or click **+ New Tag** to create one inline.
For analogue channels, also configure:
| field | val |
|---|---|
| Raw Low | 0 (for 4mA, or 0V) |
| Raw High | 27648 (Siemens) / 16383 (AB) |
| Eng Low | e.g. 0.0 (kPa or °C) |
| Eng High | e.g. 600.0 (kPa or °C) |
| Eng Units | e.g. kPa, °C, m³/h |
| Fail Mode | FAILSAFE_LOW or FAILSAFE_HIGH |
### Step 3 — Validate the Map
Click **Validate I/O Map**.
TSIMEREZIVO checks:
- No two channels mapped to the same tag
- All analogue scaling ranges are non-zero
- No AI channel configured as DO (type mismatch)
- Safety-tagged channels (`_SIL`, `_STO`) are write-protected
## Terminal Schedule Generation
### Step 1 — Export Terminal Schedule
Once the I/O map is complete, click **Export → Terminal Schedule (CSV)**
or **Export → Terminal Schedule (PDF)**.
The terminal schedule is a wiring document for electricians showing:
| rack | slot | ch | type | tag | desc | term | cable | inst |
|---|---|---|---|---|---|---|---|---|
| 0 | 4 | 0 | AI | PT201_PV | Process Pressure kPa | TB4:1+ TB4:2− | C4-01 (BELDEN 9501) | PT-201 Yokogawa EJA110 |
| 0 | 4 | 1 | AI | TT201_PV | Reactor Temperature °C | TB4:3+ TB4:4− | C4-02 (BELDEN 9501) | TT-201 Rosemount 3144P |
| 0 | 4 | 2 | AI | FT401_PV | Cooling Water Flow m³/h | TB4:5+ TB4:6− | C4-03 (BELDEN 9501) | FT-401 Endress E+H Promag W |
| 0 | 3 | 0 | DO | XV102_OPN | XV-102 Open Command (24VDC) | TB3:1+ TB3:COM | C3-01 (LAPP KABEL) | XV-102 Rotork valve actuator |
| 0 | 2 | 0 | DI | XV102_OPN_FB | XV-102 Valve Open Limit SW | TB2:1 TB2:COM | C3-02 (LAPP KABEL) | XV-102 Limit switch (Open) |
| 0 | 2 | 1 | DI | XV102_CLS_FB | XV-102 Valve Closed Limit SW | TB2:2 TB2:COM | C3-02 (LAPP KABEL) | XV-102 Limit switch (Closed) |
The generated schedule includes panel reference, cable number, instrument tag, and terminal strip numbering —
everything the construction electrician needs to wire the field instruments to the panel.