Gas Monitoring Alarm — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 28 views
# Gas Monitoring Alarm — Usage Guide
## Overview
Combustible gas monitoring template with warning, ventilation, and evacuation thresholds expressed as %LEL. Includes latched evacuation output with manual reset below a safe threshold.
## Safety Notes
- Gas trip logic should be backed by site-certified detection and shutdown hardware
- Set thresholds to site hazardous-area study and detector manufacturer guidance
- Treat detector faults as potentially dangerous conditions during operation
## Commissioning
1. Verify detector calibration and 4-20mA scaling
2. Simulate warning and evacuation thresholds with certified test gas
3. Confirm ventilation and evacuation outputs drive the intended field devices
---
## Control Logic — Vendor-Agnostic Pseudocode
# Gas Monitoring Alarm — Logic
## Standards: IEC 61131-3 | ISA-18.2 | IEC 61508 SIL1
## Scan Rate: 250ms | Pattern: LEL alarm stages with ventilation and evacuation outputs
```
ROUTINE: GasMonitoringAlarm
SCAN_RATE: 250ms
// SECTION 1 — GAS INPUT VALIDATION
GAS_MA := SCALE(GAS_RAW, 0, 27648, 4.0, 20.0)
GAS_VALID := (GAS_MA >= 3.8) AND (GAS_MA <= 20.5)
IF GAS_VALID THEN
GAS_LEL_PV := SCALE(GAS_MA, 4.0, 20.0, 0.0, 100.0)
GAS_LAST_GOOD := GAS_LEL_PV
ELSE
GAS_LEL_PV := GAS_LAST_GOOD
GAS_FAULT := TRUE
END_IF
// SECTION 2 — ALARM ZONES
IF GAS_LEL_PV >= EVAC_SP THEN EVAC_CMD := TRUE; VENT_CMD := TRUE; TRIP_LATCH := TRUE END_IF
IF GAS_LEL_PV >= VENT_SP THEN VENT_CMD := TRUE END_IF
IF GAS_LEL_PV < (VENT_SP - HYST_SP) THEN VENT_CMD := FALSE END_IF
// SECTION 3 — SAFETY TRIP LATCH
IF RESET_CMD AND GAS_LEL_PV < RESET_SAFE_SP AND NOT GAS_FAULT THEN
TRIP_LATCH := FALSE
EVAC_CMD := FALSE
END_IF
// SECTION 4 — ALARMS
IF GAS_FAULT THEN SET_ALARM(ALM_GAS_SENSOR_FAULT, HIGH) END_IF
IF GAS_LEL_PV >= WARN_SP THEN SET_ALARM(ALM_GAS_WARN, HIGH) END_IF
IF GAS_LEL_PV >= EVAC_SP THEN SET_ALARM(ALM_GAS_EVAC, CRITICAL) END_IF
// SECTION 5 — HMI
HMI_GAS_LEL := GAS_LEL_PV
HMI_VENT := VENT_CMD
HMI_EVAC := EVAC_CMD
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
GAS_RAW,Gas Detector Raw ADC,INT,input,,0,27648,,AI:0:0.0
GAS_MA,Gas Detector mA,REAL,calculated,mA,3.8,20.5,,
GAS_VALID,Gas Detector Healthy,BOOL,calculated,,,,TRUE,
GAS_LEL_PV,Gas Concentration,REAL,calculated,%LEL,0,100,0,
GAS_LAST_GOOD,Last Good Gas Reading,REAL,internal,%LEL,0,100,0,
GAS_FAULT,Gas Detector Fault,BOOL,internal,,,,FALSE,
WARN_SP,Warning Gas Threshold,REAL,internal,%LEL,0,100,10,
VENT_SP,Ventilation Start Threshold,REAL,internal,%LEL,0,100,20,
EVAC_SP,Evacuation Threshold,REAL,internal,%LEL,0,100,40,
RESET_SAFE_SP,Reset Safe Threshold,REAL,internal,%LEL,0,100,5,
HYST_SP,Ventilation Reset Hysteresis,REAL,internal,%LEL,0,20,3,
VENT_CMD,Ventilation Command,BOOL,output,,,,FALSE,DO:1:0.0
EVAC_CMD,Evacuation Alarm Command,BOOL,output,,,,FALSE,DO:1:0.1
RESET_CMD,Manual Reset Command,BOOL,input,,,,FALSE,
TRIP_LATCH,Gas Trip Latched,BOOL,internal,,,,FALSE,
ALM_GAS_SENSOR_FAULT,Gas Sensor Fault Alarm,BOOL,calculated,,,,FALSE,
ALM_GAS_WARN,Gas Warning Alarm,BOOL,calculated,,,,FALSE,
ALM_GAS_EVAC,Gas Evacuation Alarm,BOOL,calculated,,,,FALSE,
HMI_GAS_LEL,HMI: Gas Concentration,REAL,output,%LEL,0,100,0,
HMI_VENT,HMI: Ventilation Output,BOOL,output,,,,FALSE,
HMI_EVAC,HMI: Evacuation Output,BOOL,output,,,,FALSE,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_GAS_SENSOR_FAULT,GAS_VALID = FALSE,wire-break,high,safety,Gas detector fault. Treat as dangerous until proven otherwise and inspect sensor loop.,2s,No
ALM_GAS_WARN,GAS_LEL_PV >= WARN_SP,10%LEL,high,process,Combustible gas warning. Increase supervision and investigate source.,2s,No
ALM_GAS_EVAC,GAS_LEL_PV >= EVAC_SP,40%LEL,critical,safety,Evacuation threshold exceeded. Ventilation and evacuation outputs active. Manual reset only below safe threshold.,0s,No
```